| Clearance | Air cleaner nozzle distance from element | 1 | inch | 25 mm minimum |
| Pressure | Air cleaner cleaning air pressure | 30 | psi | 207 kPa; DFW, DFY and DFZ |
| Pressure | Crankcase breather drying air pressure | 30 | psi | maximum (OSHA) |
| Pressure | Low oil pressure shutdown setpoint | 14 | psi | 97 kPa; time delayed about 10 seconds following starter disconnect |
| Pressure | Normal engine oil pressure range | 50 to 70 | psi | 345 to 483 kPa |
| Pressure | Pre-low oil pressure alarm (optional 12-lamp system) | 20 | psi | 137 kPa or less |
| Pressure | Radiator air discharge static pressure | 0.25 | inch H2O | 0.018 inch Hg; 450 DM, 500 DM, 600 DFY, 750 DFZ |
| Pressure | Radiator air discharge static pressure | 0.5 | inch H2O | 0.037 inch Hg; 450 DFW |
| Resistance | Battery specific gravity (recharge below) | 1.260 | specific gravity | use a hydrometer |
| Speed | Cycle cranking option | 15 | seconds | three 15-second cranking cycles with two 15-second rest periods |
| Speed | Fine speed adjustment range (SPEED ADJUST potentiometer) | ±100 | RPM | less than |
| Speed | Frequency meter speed relation | 30 | r/min | each hertz equals 30 r/min |
| Speed | No-load governed speed, 50 Hz 3% droop | 1545 | RPM | 51.5 Hz |
| Speed | No-load governed speed, 50 Hz 5% droop | 1575 | RPM | 52.5 Hz |
| Speed | No-load governed speed, 50 Hz isochronous | 1500 | RPM | 50.0 Hz |
| Speed | No-load governed speed, 60 Hz 3% droop | 1854 | RPM | 61.8 Hz |
| Speed | No-load governed speed, 60 Hz 5% droop | 1890 | RPM | 63.0 Hz |
| Speed | No-load governed speed, 60 Hz isochronous | 1800 | RPM | 60.0 Hz |
| Speed | Overcrank cranking limit (standard control) | 75 | seconds | starter disengages after 75 seconds of cranking |
| Speed | Overspeed shutdown, 50 Hz units | 1850 ± 50 | r/min | |
| Speed | Overspeed shutdown, 60 Hz units | 2100 ± 90 | r/min | |
| Speed | Starter disconnect speed | 450 to 570 | r/min | |
| Temperature | High engine temperature shutdown | 215 | °F | 102°C; time delayed about 10 seconds following starter disconnect |
| Temperature | LO ENG TEMP lamp setpoint | 70 | °F | 21°C or lower engine water jacket temperature |
| Temperature | Pre-high engine temperature alarm | 205 | °F | 97°C; optional 12-lamp system |
| Torque | Oil drain plug | 60-70 | ft.lb | also 81-95 N·m |
| Voltage | Electrical system starting voltage | 24 | Volts DC | |
| Voltage | Random voltage variation | ±1 | % | constant loads |
| Voltage | Rating condition, ambient temperature | 77 | °F | 25°C; also altitude 300 feet (92 m) |
| Voltage | Voltage adjust rheostat range | ±5 | % | optional; of rated output voltage |
| Voltage | Voltage regulation, VRAS-2 regulator | ±2 | % | from no load to full load |