Cummins/Onan QSK60-G19 NR2 Engine

The Cummins/Onan QSK60-G19 NR2 is a 60.2 L 16-cylinder turbocharged and low temperature after-cooled engine rated at 1800 rpm, producing up to 2715 kW. It powers generator sets from Cummins/Onan, including the DQKAN. It holds 378 L (99.9 gal) of oil and 681.4 L (180.0 gal) of coolant.

Also known as: Cummins Inc. QSK60-G19 NR2

60.2 L
Displacement
16
Cylinders
1800 rpm
Rated speed
2715 kW
Gross power

Engine specifications

Oil capacity378.0 L
Coolant capacity681.4 L
Displacement60.2 L
Cylinders16
AspirationTurbocharged and low temperature after-cooled
Rated speed1800 rpm
Gross power2715 kW

Common problems

13
  • The control will not allow the starter to attempt to engage or to crank Cranking lockout
    Cause: Not specified in text
  • Some shutdown faults are bypassed Battle short mode
  • Output power of the genset is reduced in response to a fault condition Derate
  • Indicates that engine temperature may not be high enough for a 10 second start or proper load acceptance Low coolant temperature warning
    Cause: Engine temperature is low
  • Indicates status of battery charging system (failure) Low and high battery voltage warning
    Cause: Continuously monitoring battery voltage
  • Emergency stop
    Fix: Annunciated whenever either emergency stop signal is received from external switch.
  • Derate
    Fix: The Derate function reduces output power of the genset in response to a fault condition. If a Derate command occurs while operating on an isolated bus, the control will issue commands to reduce the load on the genset via contact closures or Modbus. If a Derate command occurs while in utility parallel mode, the control will actively reduce power by lowering the base load kW to the derated target kW.
  • Control system indicates a fault if the genset fails to start by the completion of the engine crack sequence Fail to start (overcrank) shutdown
    Cause: Genset fails to start
  • Control has signaled starter to crank engine but engine does not rotate Fail to crank shutdown
    Cause: Engine does not rotate
  • Can be set up to be a warning or shutdown Low coolant level warning
    Cause: Set up in control
  • Battle short mode
    Fix: If a bypassed shutdown fault occurs, the fault code and description will still be annunciated, but the genset will not shutdown. This will be followed by a fail to shutdown fault.
  • Battery indicates impending failure Weak battery warning
    Cause: Control system tests the battery each time the genset is signaled to start
  • Annunciated whenever either emergency stop signal is received from external switch Emergency stop

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSK60-G19 NR2.

Maintenance schedule

ItemSpecCapacityPart #Interval
Fuel filterA055Y798 Amazon eBay $5944.00

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
FuelNo. 2-D dieselASTM D97540-48 cetane

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

9
CodeNameMeaningSeverityAction
27Low AC voltage shutdownVoltage on any phase dropped below preset value; adjustable 50-95% of reference, 2-20 s delay, default 85% for 10 sShutdownShut down genset
32Reverse power shutdownAdjustable 5-20% of standby kW rating, 1-15 s delay, default 10% for 3 sShutdownShut down genset
40Reverse Var shutdownAdjustable 15-50% of rated Var output, 10-60 s delay, default 20% for 10 sShutdownShut down genset
46Negative sequence overcurrent warningProtects generator from damage due to excessive imbalances in three phase load currents and/or power factorsWarningWarning alarm
51Overcurrent warning/shutdownThermal damage curve with instantaneous trip based on CT ratio and application power ratingShutdownShut down genset
51GGround fault overcurrentDetects ground fault via external ground fault relay contact input or external current transformer; delays and thresholds adjustableShutdownShut down genset
59High AC voltage shutdownOutput voltage on any phase exceeds preset values; adjustable 105-125% of nominal, 0.1-10 s delay, default 110% for 10 sShutdownShut down genset
81oOver frequency shutdown/warningGenset operating at damaging frequency; adjustable 2-10 Hz above nominal, 1-20 s delay, default 6 Hz for 20 s, disabledShutdownShut down genset
81uUnder frequency shutdownGenset output frequency cannot be maintained; adjustable 2-10 Hz below reference, 5-20 s delay, default 6 Hz for 10 sShutdownShut down genset

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
1247033 Ph Wye6Temp rise 105°C, Duty S, Max surge 11213 kVA, Winding No. 91, ADS-533, B568
1320033 Ph Wye6Temp rise 105°C, Duty S, Max surge 11213 kVA, Winding No. 91, ADS-533, B501
1380033 Ph Wye6Temp rise 80°C, Duty S, Max surge 11213 kVA, Winding No. 91, ADS-533, B610
240-208single240-208 volt connectionCoolant heater; for 240-208 volt move jumpers as shown
38033 Ph Wye6Temp rise 105°C, Duty S, Max surge 13024 kVA, Winding No. 13, ADS-531, B408
41633 Ph Wye6Temp rise 150°C, Duty S, Max surge 9719 kVA, Winding No. 12, ADS-517, B682
416033 Ph Wye6Temp rise 80°C, Duty S, Max surge 11185 kVA, Winding No. 51, ADS-545, B605
44033 Ph Wye6Temp rise 105°C, Duty S, Max surge 13024 kVA, Winding No. 12, ADS-531, B664
48033 Ph Wye6Temp rise 125°C, Duty S, Max surge 8412 kVA, Winding No. 12, ADS-516, B246
480single480 volt connectionCoolant heater; jumpers are factory installed in the 480 volt configuration
60033 Ph Wye6Temp rise 125°C, Duty S, Max surge 8189 kVA, Winding No. 7, ADS-516, B602

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Cummins/Onan QSK60-G19 NR2?

The Cummins/Onan QSK60-G19 NR2 engine has an oil capacity of 378.0 liters.

What is the displacement of the Cummins/Onan QSK60-G19 NR2?

The Cummins/Onan QSK60-G19 NR2 has a displacement of 60.2 liters with 16 cylinders.

Which generators use the Cummins/Onan QSK60-G19 NR2 engine?

The Cummins/Onan QSK60-G19 NR2 powers 1 generator set(s), including Cummins/Onan DQKAN.

What is a common problem with the Cummins/Onan QSK60-G19 NR2 engine?

A commonly reported issue on generators using the Cummins/Onan QSK60-G19 NR2 is: The control will not allow the starter to attempt to engage or to crank. Cause: Not specified in text.