Maintenance schedule
| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Fuel filter | A055Y798 | Amazon eBay $5944.00 |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
The Cummins/Onan QSK60-G19 NR2 is a 60.2 L 16-cylinder turbocharged and low temperature after-cooled engine rated at 1800 rpm, producing up to 2715 kW. It powers generator sets from Cummins/Onan, including the DQKAN. It holds 378 L (99.9 gal) of oil and 681.4 L (180.0 gal) of coolant.
Also known as: Cummins Inc. QSK60-G19 NR2
| Oil capacity | 378.0 L |
|---|---|
| Coolant capacity | 681.4 L |
| Displacement | 60.2 L |
| Cylinders | 16 |
| Aspiration | Turbocharged and low temperature after-cooled |
| Rated speed | 1800 rpm |
| Gross power | 2715 kW |
How to read your Cummins/Onan engine serial & model number →
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSK60-G19 NR2.
| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Fuel filter | A055Y798 | Amazon eBay $5944.00 |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | No. 2-D diesel | ASTM D975 | 40-48 cetane |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 27 | Low AC voltage shutdown | Voltage on any phase dropped below preset value; adjustable 50-95% of reference, 2-20 s delay, default 85% for 10 s | Shutdown | Shut down genset |
| 32 | Reverse power shutdown | Adjustable 5-20% of standby kW rating, 1-15 s delay, default 10% for 3 s | Shutdown | Shut down genset |
| 40 | Reverse Var shutdown | Adjustable 15-50% of rated Var output, 10-60 s delay, default 20% for 10 s | Shutdown | Shut down genset |
| 46 | Negative sequence overcurrent warning | Protects generator from damage due to excessive imbalances in three phase load currents and/or power factors | Warning | Warning alarm |
| 51 | Overcurrent warning/shutdown | Thermal damage curve with instantaneous trip based on CT ratio and application power rating | Shutdown | Shut down genset |
| 51G | Ground fault overcurrent | Detects ground fault via external ground fault relay contact input or external current transformer; delays and thresholds adjustable | Shutdown | Shut down genset |
| 59 | High AC voltage shutdown | Output voltage on any phase exceeds preset values; adjustable 105-125% of nominal, 0.1-10 s delay, default 110% for 10 s | Shutdown | Shut down genset |
| 81o | Over frequency shutdown/warning | Genset operating at damaging frequency; adjustable 2-10 Hz above nominal, 1-20 s delay, default 6 Hz for 20 s, disabled | Shutdown | Shut down genset |
| 81u | Under frequency shutdown | Genset output frequency cannot be maintained; adjustable 2-10 Hz below reference, 5-20 s delay, default 6 Hz for 10 s | Shutdown | Shut down genset |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12470 | 3 | 3 Ph Wye | 6 | Temp rise 105°C, Duty S, Max surge 11213 kVA, Winding No. 91, ADS-533, B568 |
| 13200 | 3 | 3 Ph Wye | 6 | Temp rise 105°C, Duty S, Max surge 11213 kVA, Winding No. 91, ADS-533, B501 |
| 13800 | 3 | 3 Ph Wye | 6 | Temp rise 80°C, Duty S, Max surge 11213 kVA, Winding No. 91, ADS-533, B610 |
| 240-208 | single | 240-208 volt connection | Coolant heater; for 240-208 volt move jumpers as shown | |
| 380 | 3 | 3 Ph Wye | 6 | Temp rise 105°C, Duty S, Max surge 13024 kVA, Winding No. 13, ADS-531, B408 |
| 416 | 3 | 3 Ph Wye | 6 | Temp rise 150°C, Duty S, Max surge 9719 kVA, Winding No. 12, ADS-517, B682 |
| 4160 | 3 | 3 Ph Wye | 6 | Temp rise 80°C, Duty S, Max surge 11185 kVA, Winding No. 51, ADS-545, B605 |
| 440 | 3 | 3 Ph Wye | 6 | Temp rise 105°C, Duty S, Max surge 13024 kVA, Winding No. 12, ADS-531, B664 |
| 480 | 3 | 3 Ph Wye | 6 | Temp rise 125°C, Duty S, Max surge 8412 kVA, Winding No. 12, ADS-516, B246 |
| 480 | single | 480 volt connection | Coolant heater; jumpers are factory installed in the 480 volt configuration | |
| 600 | 3 | 3 Ph Wye | 6 | Temp rise 125°C, Duty S, Max surge 8189 kVA, Winding No. 7, ADS-516, B602 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Cummins/Onan QSK60-G19 NR2 engine has an oil capacity of 378.0 liters.
The Cummins/Onan QSK60-G19 NR2 has a displacement of 60.2 liters with 16 cylinders.
The Cummins/Onan QSK60-G19 NR2 powers 1 generator set(s), including Cummins/Onan DQKAN.
A commonly reported issue on generators using the Cummins/Onan QSK60-G19 NR2 is: The control will not allow the starter to attempt to engage or to crank. Cause: Not specified in text.