Cummins/Onan L634D Engine

The Cummins/Onan L634D is a 6-cylinder naturally aspirated engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the DL6. It holds 8.5 L (2.2 gal) of oil and 16.8 L (4.4 gal) of coolant.

Also known as: Onan L634D

6
Cylinders
1800 rpm
Rated speed
8.5 L
Oil capacity

Engine specifications

Oil capacity8.5 L
Coolant capacity16.8 L
Cylinders6
Aspirationnaturally aspirated
Rated speed1800 rpm

Common problems

15
  • Engine does not crank
    Cause: Battery dead; start solenoid K1 does not energize; less than 7 volts DC between K1 terminal S and ground; less than 7 volts DC between B1 starter solenoid terminal and ground; K1 fault relay not energized; faulty battery cables or connections; faulty B1 starter solenoid or motor; faulty K1 start solenoid, K2 on/off relay, K3 and K11 start-disconnect relays, S10 switch, or connections
    Fix: Check battery per Checkout [A] and recharge or replace; check alternator operation per Checkout [C]; check K1 start solenoid, K2 on/off relay, K3 and K11 start-disconnect relays, S10 switch, and all connections per Checkouts D, E, and G; check wiring and connections between K1 terminal I and the solenoid terminal B1; check for possible fault conditions and, if ok, check K1 fault relay per Checkout E; check battery cables for clean and tight connections per Checkout [B]; check B1 starter solenoid and motor and repair or replace if bad; jumper battery cable B+ connection to B1 starter solenoid terminal and check whether engine cranks
  • Engine cranks but does not start
    Cause: K3 fuel solenoid does not energize when S10 is in Start position; preheat system not operating properly; no fuel from fuel supply system (fuel tank, shutoff valves, fuel lines and connections, fuel filters, transfer pump); fault condition indicated by panel light (S1 engine temp. switch, S6 overspeed switch, S3 oil pressure switch, K1 fault relay short to ground); battery voltage not read between stop terminal of S10 and ground as RPM increases; incorrect fuel; K2 on/off relay faulty
    Fix: Check K3 fuel solenoid (Test F) and related wiring; check heater solenoid K2 and switch S11 per Checkouts [D] and [G]; check wiring and heater elements; check fuel supply system: fuel tank, shutoff valves, fuel lines and connections, fuel filters and transfer pump; check for possible fault condition and, if OK, check S1 engine temp. switch, S6 overspeed switch, and S3 oil pressure switch, and check K1 fault relay for short to ground; check switch S10 and related wiring for open circuit or short to ground; use correct fuel per Operator's Manual recommendations; jump normally open contacts of K2 on/off relay and check whether engine starts and runs; replace all engine monitor circuit board
  • Engine will not crank
    Cause: Indicates possible fault with control or starting system; fault lamp on
    Fix: Correct fault and reset control
  • Engine starts but stops after running several seconds
    Cause: K2 on/off relay faulty
    Fix: Replace K2 on/off relay
  • Unstable output voltage, engine speed stable at rated r/min
    Fix: Refer to Flow Chart B for troubleshooting procedures
  • Unstable output voltage, engine speed stable 1800 RPM
    Fix: Refer to Flow Chart B for the troubleshooting procedures
  • Unbalanced generator output voltage
    Fix: Refer to Flow Chart E for the troubleshooting procedures
  • SWITCH OFF lamp flashes
    Cause: Indicates Start/Stop/Remote switch is in the Stop position which will prevent automatic starting if an automatic transfer switch is used
    Fix: Move the Start/Stop/Remote switch to the Remote position for automatic starting
  • PRELO OIL PRES lamp lights. Engine continues to operate
    Cause: Indicates engine oil pressure has dropped to 20 psi (138 kPa)
    Fix: If engine can be stopped, follow procedures in step 5; if generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure
  • PRE HI ENG TEMP lamp lights. Engine continues to operate
    Cause: Indicates engine has begun to overheat and engine temperature has risen to approximately 215°F (102°C)
    Fix: If engine can be stopped, follow procedures in step 3; if generator is powering critical loads and cannot be shutdown: check air inlets and outlets and remove any obstructions to airflow; open doors or windows in generator area to increase ventilation; reduce load if possible by turning off non-critical loads
  • OVERCRANK lamp lights and engine stops cranking after 45 to 75 seconds
    Cause: Indicates possible fuel system problem
    Fix: When the engine has cooled, make the following checks: check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required; check for dirty fuel filter and replace if necessary (see MAINTENANCE section); check for dirty or plugged air filter and replace if necessary (see MAINTENANCE section); reset the control and restart after correcting the problem; contact an Onan Dealer or Distributor for service if none of the above
  • Output voltage too high or low
    Fix: Refer to Flow Chart C for the troubleshooting procedures
  • No fuel at injection nozzle but fuel to injection pump
    Cause: Fuel solenoid may be defective
    Fix: Listen for a click in injection pump when start switch is placed in the run position; if no click is heard and there is power to solenoid with the start switch in the run position, replace the fuel solenoid
  • No AC output voltage at rated engine RPM
    Cause: Control panel field breaker CB3 not ON; field breaker open; residual voltage across TB2-2 and H1 less than 5 to 10 VAC; exciter field voltage across TB1-5 & 6 less than 5 VDC; defective diodes or SCR's on bridge assembly CR21; faulty exciter field wiring harness; open fuses F2 and F3 on VR21 regulator PC board; faulty exciter field winding; faulty reactor L21 or transformer T21; faulty voltage regulator assembly
    Fix: Push to reset breaker; replace defective field breaker; flash exciter field per TEST [D]; disconnect stator leads 7 (4) and 8 (1) from TB2-2 and H1 and recheck residual voltage; check reactor L21 and transformer T21 per TESTS [B] and [E]; check diodes and SCR's on bridge assembly CR21 per TEST [C]; check exciter field wiring harness per TEST [M]; check fuses F2 and F3 for continuity on VR21 regulator PC board; check exciter field winding per TEST [H] and replace if bad; test voltage regulator assembly per procedure (S) and replace the regulator PC board per procedure (F) if defective
  • No AC output voltage at rated engine r/min
    Fix: Refer to Flow Chart A for troubleshooting procedures

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan L634D.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterGuide, Valve Intake110-3496 Amazon eBay
Fuel filterFilter, Fuel149-1754 Amazon eBay $54.34
Oil filterFilter, Oil122-0550 Amazon eBay $21.84 NAPA $18.20

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

16
ItemActionHoursMonthsNotes
Coolant LevelCheck50 hr
Crankcase Oil and FilterChange200 hrFirst service — Perform after first 50 hours on new sets
Fan BeltCheck50 hr
Generator SetInspect50 hrWith engine running, visually/audibly check exhaust for leaks
Oil LevelCheck50 hr
Valve Lash ClearanceCheck400 hrFirst service — Perform after first 50 hours on new sets; refer to L-Series Engine Service Manual
Air CleanerCheck100 hrPerform more often under extremely dusty/dirty conditions
Exhaust Condensate TrapDrain100 hr
Fuel LevelCheck100 hr
Battery ConditionCheck200 hr
Electrolyte LevelCheck200 hr
Generator AssemblyClean200 hr
Air Cleaner ElementChange400 hr
Crankcase Breather Cap (DL6TB)Clean400 hr
Fuel FilterChange400 hr12 moWhichever comes first
Generator BearingInspect500 hrReplace every five years

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceTrailer brake actuator stroke length1inch (25 mm)maximum before brake shoe readjustment
GapFloat switch test feeler gauge0.125inch (3 mm)between float and C-clip stop
GapMagnetic pickup adjustment1/2 turn out from toothturnafter contact with flywheel tooth
GapOverspeed switch air gap0.005inch (0.13 mm)minimum
GapOverspeed switch air gapnot less than 0.005inch (0.13 mm)
GapOverspeed switch magnetic air gap0.005inch (0.13 mm)must not be less than
GapOverspeed switch magnetic air gap0.005 inch (0.13 mm) minimuminch
OtherBattery electrolyte specific gravity1.260specific gravityfully charged battery at 80F (27C)
OtherBattery electrolyte specific gravityabout 1.260specific gravityfully charged at 80°F (27°C)
OtherBattery electrolyte specific gravity (fully charged)about 1.260specific gravityat 80 deg F (27 deg C)
OtherBrake shoe adjustment10clicksback off from point wheel cannot be turned by hand
OtherControl breaker rating7amperes
OtherControl heater element power75watts at 120 VAC
OtherField breaker rating5amperes
OtherLow Oil Pressure Delay before shutdown/pre-alarm7.5 to 12.5secondsafter Start-Disconnect Relay energized
OtherLow oil pressure delay circuit7.5 to 12.5secondsafter start-disconnect relay energized
OtherMaximum allowable exhaust back pressure41inches (1041 mm) H2O
OtherOil pressure gauge range0 to 100 psi (0 to 700 kPa)psi
OtherOvercranking timer cranking limit45 to 75seconds
OtherOvercranking timer limit45 to 75seconds
OtherRemote breaker rating7amperes
OtherSwitching regulator (standard setting) nominal switching frequencyapproximately 125Hz
OtherWater temperature gauge range100 to 250F (40 to 121C)F
PressureAir cleaner cleaning air pressure35psi (241 kPa)
PressureAir cleaner rinse water pressure maximum40psi (276 kPa)
PressureLow oil pressure shutdown14psibelow; 97 kPa equivalent; 10 s delay after starter disconnect
PressureLow oil pressure shutdownbelow 14psi (97 kPa)fault time delayed about 10 seconds following starter disconnect and inhibited during cranking
PressureLow oil pressure shutdown (LO OIL PRES)14psi (97 kPa)
PressureLow oil pressure switch closes14psi (97 kPa)
PressureLow oil pressure switch closes14 psi (97 kPa)psi
PressureOil pressure gauge normal range30 to 55psi (207 to 380 kPa)operating temperature
PressureOil pressure gauge range0 to 100psi (0 to 700 kPa)
PressurePre-low oil pressure alarm20psi (138 kPa) or less
PressurePre-low oil pressure switch closes20psi (138 kPa)
PressurePre-low oil pressure switch closes20 psi (138 kPa)psi
PressurePre-low oil pressure warning20psi (138 kPa)
ResistanceActuator coil resistance1 ±10%ohmat 77°F (25°C); leads disconnected
ResistanceCommutating reactor L21 coils 1-20.031 to 0.37ohmsat 77 deg F (25 deg C)
ResistanceCommutating reactor L21 coils 3-40.037 to 0.46ohmsat 77 deg F (25 deg C)
ResistanceCommutating reactor L21/L22 coil 1-2 resistance.031 to 0.37ohmsat 77F (25C)
ResistanceCommutating reactor L21/L22 coil 3-4 resistance0.037 to 0.46ohmsat 77F (25C)
ResistanceCommutating reactor coil to frameinfinityohms
ResistanceControl heater element resistance192ohmsdissipates 75 watts at 120 VAC
ResistanceExciter rotor leads T1-T2, T2-T3, T1-T3 resistance0.6 to 0.7ohmsat 68F (20C)
ResistanceExciter rotor winding between lead pairs T1-T2, T2-T3, T1-T30.6 to 0.7ohmsat 68 deg F (20 deg C)
ResistanceExciter rotor winding resistance0.54ohmsat 77°F (25°C), ±10%
ResistanceExciter rotor winding resistance0.54 ±10%ohmsat 77°F (25°C)
ResistanceExciter rotor winding resistance0.645ohmsat 77°F (25°C), ±10%
ResistanceExciter rotor winding resistance0.645 ±10%ohmsat 77°F (25°C)
ResistanceExciter stator / rotor / generator winding insulation to ground1 megohm (1,000,000 ohms) or greaterohmsminimum
ResistanceExciter stator field leads F1-F2 resistance13.05 to 15.95ohmsat 77F (25C)
ResistanceExciter stator insulation resistance to lamination100,000ohmsminimum; 500 VDC or more
ResistanceExciter stator winding between F1+ and F2-13.05 to 15.95ohmsat 77 deg F (25 deg C)
ResistanceExciter stator winding resistance12.4 ±10%ohmsat 77°F (25°C)
ResistanceExciter stator winding resistance14.5 ±10%ohmsat 77°F (25°C)
ResistanceExciter stator winding resistance, 4A2.3/6A3.4/6AT3.414.5ohmsat 77°F (25°C), ±10%
ResistanceExciter stator winding resistance, DGAB/DGAC/DGAD/DGAE12.4ohmsat 77°F (25°C), ±10%
ResistanceExciter stator winding resistance, DL420.0ohmsat 77°F (25°C)
ResistanceExciter stator winding resistance, DL625.0ohmsat 77°F (25°C)
ResistanceExciter stator winding resistance, DL6T40.0ohmsat 77°F (25°C)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantEthylene glycol anti-freeze (permanent type) with rust/corrosion inhibitor, no stop-leak additiveUse at least 50/50 mixture of anti-freeze and clean, soft water
Engine oil15W-40, 30W, 20, 20W-20, 10W (API CD/SF, CD/SE, or MIL-L-2104C); synthetic 5W-20 or 5W-30 (MIL-L-46167, MIL-L-2104C, MIL-L-46152B)API CD/SF, CD/SE, MIL-L-2104CMineral base 5W-20/5W-30 not recommended under any conditions; select grade for lowest expected temperature
FuelASTM 2-D (No. 2 Diesel) or ASTM 1-D (No. 1 Diesel), Cetane 45 minimumASTM 2-D / ASTM 1-DUse No. 1 diesel below 0C (32F) and during long light-load periods; cloud point at least 10 degrees below lowest expected fuel temperature
GreaseMolyKote grease or equivalentApply thin film to mating surfaces of end bearing and end bell bearing hole
GreaseMolykote grease or equivalentApply a thin film to the mating surfaces of the end bearing and the end bell bearing hole.
OtherApproved water for battery electrolyteAdd approved water to keep battery electrolyte at proper level.
OtherDOT 3Trailer brake system; reservoir should be at least half full
OtherDOT-3 heavy duty hydraulic fluidTrailer brake system bleeding
Otherdistilled waterBattery electrolyte; add distilled water to maintain proper level.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

15
CodeNameMeaningSeverityAction
FAULT 1Fault 1Red lamp for customer-installed auxiliary equipment fault switch; part of timed factory-set 10-second shutdown circuit.Shutdown
FAULT 2Fault 2Red lamp for customer-installed auxiliary equipment fault switch; part of factory-set non-timed delayed shutdown circuit.Shutdown
HI ENG TEMPHigh Engine TemperatureEngine overheated above 220F (104C) or low coolantShutdownCheck coolant level, airflow, fan belt
LO ENG TEMPLow Engine TemperatureEngine block temperature below 70F (21C)InfoWait for block temperature to rise
LO FUELLow fuelYellow lamp indicates fuel supply is marginally low.WarningReplenish fuel supply.
LO OIL PRESLow Oil PressureOil pressure dropped to 14 psi (97 kPa)ShutdownCheck oil level, reset control
LOW ENG TEMPLow engine temperatureYellow lamp indicates engine temperature is marginally low for starting; indicates inoperative coolant heater on gensets with option.WarningCheck coolant heater.
LOW OIL PRESLow oil pressure shutdownRed lamp indicates engine shutdown because of critically low oil pressure.ShutdownCheck oil level and LOP switch; inspect engine.
OVERCRANKOvercrankEngine failed to start after 45-75 seconds crankingShutdownCheck fuel system
OVERSPEEDOverspeedEngine exceeded normal operating speedShutdownContact Onan Dealer or Distributor
PRE HI ENG TEMPPre-High Engine TemperatureEngine temperature approximately 215F (102C)WarningCheck ventilation, reduce load
PRE HIGH ENG TEMPPre-high engine temperatureYellow lamp indicates engine temperature is marginally high.WarningFind and correct cause.
PRE LO OIL PRESPre-Low Oil PressureOil pressure dropped to 20 psi (138 kPa)WarningCheck oil level
RUNRUNGreen lamp comes on when both starter-disconnect circuits are opened after genset start.Info
SWITCH OFFSwitch OffStart/Stop/Remote switch in Stop positionInfoMove switch to Remote for automatic starting

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjust magnetic pickup adjustment

Tools: Compressed air, Jam nut wrench

  1. Rotate engine so ring gear tooth is centered in MPU hole.
  2. Clean mounting hole with compressed air.
  3. Turn MPU in until it contacts flywheel tooth directly below.
  4. Turn out 1/2 turn and lock with jam nut.
  5. Be sure pickup does not rotate when tightening jam nut.
Adjust voltage adjust potentiometer R21 adjustment

⚠ Contact with high voltage can cause severe personal injury or death.

Tools: Insulated screwdriver

  1. Loosen locking nut of R21 and adjust to mid-range.
  2. Start genset and bring temperature to normal.
  3. With no load, turn Phase Selector to read output voltage and current.
  4. Adjust R32 for approximate desired voltage.
  5. Fine-adjust with R21 and tighten locking nut without changing setting.
Adjust voltage regulator adjustment

⚠ Use insulating mat or dry wood platform when control doors are open.

Tools: Insulated screwdriver, Accurate voltmeter

  1. Open control panel doors and set S1, S2, and S3 per table.
  2. Connect accurate voltmeter to TB1-2 and TB1-3 if no AC meter.
  3. Start genset and bring temperature to normal.
  4. Turn R32 to set no-load voltage.
  5. Stop genset and close control panel doors.
Calibrate electronic governor adjustment

⚠ Keep hands and fingers clear while performing tests on operating equipment.

Tools: Tachometer or frequency meter

  1. Check actuator linkage does not bind through full travel.
  2. Attach tachometer or frequency meter.
  3. Set GAIN adjustment to second mark from zero.
  4. Disconnect governor rod from throttle lever.
  5. Start genset and adjust right stop to 72 Hz for 60 Hz gensets.
  6. Adjust left stop to take up slack and tighten locknut.
  7. Stop, attach governor rod, start, and adjust SPEED to 60 or 50 Hz.
  8. Connect load and adjust GAIN clockwise until stable.
Changing Sensitivity Reference adjustment

⚠ Do not mark on printed circuit boards with a pencil; graphite lines are conductive.

Tools: soldering iron

  1. Unsolder W1 on VR21 at hole F for frequency sensitive.
  2. Resolder W1 to hole S for semi-frequency sensitive.
  3. Resolder W1 to hole N for non-frequency sensitive.
Electronic governor adjustment/calibration adjustment

⚠ Contact with rotating machinery can cause severe personal injury or death.

Tools: Tachometer or frequency meter, Screwdriver

  1. Check actuator linkage does not bind through full travel; ensure terminals 7 and 8 are jumpered.
  2. Attach tachometer to engine or frequency meter to generator if control panel lacks one.
  3. Set Controller GAIN adjustment to second mark from zero.
  4. Disconnect governor rod from throttle lever.
  5. Place Run/Stop/Remote switch in Run position to start genset.
  6. Adjust right stop screw on mechanical governor to obtain 72 Hz (2160 r/min) for 60 Hz gensets or 62 Hz (1860 r/min) for 50 Hz gensets.
  7. Adjust left stop screw to just take up slack, then tighten locknut without binding shaft.
  8. Stop genset, attach governor rod to throttle lever, start, and adjust Controller SPEED screw for 60 Hz or 50 Hz.
  9. Connect full rated load; if genset cannot manage load, shorten governor rod one-half turn and repeat; tighten locknuts.
  10. Connect 1/4 rated load; turn GAIN screw clockwise until actuator hunts, then back off until stable.
  11. Stop genset, wait 30 seconds for turbo coast down if equipped, restart, and check for speed overshoot.
  12. Restart genset and check frequency and stability under various loads.
  13. Stop genset and remove tachometer or frequency meter if attached.
Fan Belt Adjustment adjustment

Tools: belt adjustment tool

  1. Loosen alternator bolt through elongated slot in mounting bracket
  2. Slide alternator until fan belt tension of 60 lbs (267 N) is obtained
  3. Tighten alternator mounting bolt to lock in place
  4. Check tension and repeat if necessary
Governor Control Adjustment adjustment

⚠ Hold the throttle linkage so that the set will not overspeed.

Tools: frequency meter

  1. Place Start/Stop/Remote switch in STOP.
  2. Attach frequency meter to generator output leads if none on panel.
  3. Locate governor control in control box.
  4. Adjust GAIN potentiometer fully counterclockwise.
  5. Hold throttle linkage to prevent overspeed; start the set.
  6. Adjust SPEED potentiometer to correct frequency (50 or 60 hertz).
  7. Adjust GAIN clockwise until governor hunts, then counterclockwise until stable.
  8. Test by tapping actuator lever; set should return to speed without hunting.
  9. Stop and restart set to verify it does not overspeed.
Magnetic Pickup Sensor Adjustment adjustment
  1. Place Start/Stop/Remote switch in the STOP position.
  2. Loosen stop-nut on the magnetic sensor on the flywheel housing.
  3. Turn sensor IN until it just contacts flywheel ring gear.
  4. Back sensor OUT 1/2 turn and tighten stop-nut.
Reconnection (Test Q) adjustment
  1. Refer to the generator reconnection possibilities when changing voltage.
  2. Reconnect lead W12 (inside control box) to the proper H terminal (H2, H3, H4, H5, or H6) depending on voltage selected.
  3. Change jumper W12 from TB2-2 to the proper TB2 terminal.
Voltage Adjustment (Standard Regulator) adjustment
  1. Center the panel mounted voltage adjustment knob with pointer vertical.
  2. Start the set and allow it to stabilize at correct frequency and speed.
  3. Turn R18 counterclockwise to decrease voltage or clockwise to increase.
  4. Set voltage with no load connected (e.g., 246 volts for 120/240).
  5. Turn R26 counterclockwise until unstable, then clockwise until voltage stabilizes.
Voltage Adjustment (Test P) adjustment

Tools: voltmeter

  1. Center the panel-mounted voltage adjustment knob vertically.
  2. Start the set and allow it to stabilize at the correct frequency and speed.
  3. Standard regulator: turn R18 counterclockwise to decrease voltage, clockwise to increase; set no-load voltage (e.g. 246 volts for 120/240 connection).
  4. Standard regulator: turn R26 counterclockwise until voltage hunts, then clockwise until stable.
  5. Switching regulator: turn R36 counterclockwise to increase voltage, clockwise to decrease; set no-load voltage.
  6. Switching regulator: turn R5 counterclockwise until voltage hunts, then clockwise until stable.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Connect loose wire W12 from TB2-2 to TB2 (H terminal)H2, H3, H4, H5 or H6 depending on voltage selectedW12 reconnection lead inside control box; must be reconnected to proper H terminal when reconnecting for a different voltage
X1 (red) to VR21-9, X2 (red) to VR21-10X1, X2Reference transformer T21 secondary connections
110/1903Figure 26 generator voltage connections
110/2201Connect lead W12 to H6 (per Figure 26 reconnection table)50 Hz. Figure 26 generator voltage connections. OCR partially garbled.
115/2003Figure 26 generator voltage connections
115/2301Connect lead W12 to H6 (per Figure 26 reconnection table)50 Hz. Figure 26 generator voltage connections. OCR partially garbled.
120/2083Figure 26 generator voltage connections
120/2401Connect lead W12 to H5 (per Figure 26 reconnection table)60 Hz. Figure 26 generator voltage connections. OCR partially garbled.
120/2401Reconnectible generator (code 15/515)W12 (TB2) to H3/H4/H5/H6 on voltage reference transformer12-lead generator reconnection
127/2203Figure 26 generator voltage connections
130/4003Figure 26 generator voltage connections
139/2403Figure 26 generator voltage connections
208 VACSwitch S1 position 1stator T7 and T8Transformer TX1 primary H1-H3
220/3803Figure 26 generator voltage connections
220/3803Non-reconnectible (code 7)H3
240 VACSwitch S1 positions 2 and 3stator T7 and T8Transformer TX1 primary H3-H5
240/4163Figure 26 generator voltage connections
254/4403Figure 26 generator voltage connections
277/4803Figure 26 generator voltage connections
347/6003Non-reconnectible (code 9X)H5
VariousReconnect lead W12 (inside control box) from TB2-2 to the proper H terminal (H2, H3, H4, H5, or H6) depending on voltage selectedW12, H2, H3, H4, H5, H6Figure 25. Single phase generators use leads 1 and 4 (lead 2 not used); three phase generators use leads 4, 7, 8, 9 and 10 for control input and metering.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Cummins/Onan L634D?

The Cummins/Onan L634D engine has an oil capacity of 8.5 liters.

Which generators use the Cummins/Onan L634D engine?

The Cummins/Onan L634D powers 1 generator set(s), including Cummins/Onan DL6.

What is a common problem with the Cummins/Onan L634D engine?

A commonly reported issue on generators using the Cummins/Onan L634D is: Engine does not crank. Cause: Battery dead; start solenoid K1 does not energize; less than 7 volts DC between K1 terminal S and ground; less than 7 volts DC between B1 starter solenoid terminal and ground; K1 fault relay not energized; faulty battery cables or connections; faulty B1 starter solenoid or motor; faulty K1 start solenoid, K2 on/off relay, K3 and K11 start-disconnect relays, S10 switch, or connections. Fix: Check battery per Checkout [A] and recharge or replace; check alternator operation per Checkout [C]; check K1 start solenoid, K2 on/off relay, K3 and K11 start-disconnect relays, S10 switch, and all connections per Checkouts D, E, and G; check wiring and connections between K1 terminal I and the solenoid terminal B1; check for possible fault conditions and, if ok, check K1 fault relay per Checkout E; check battery cables for clean and tight connections per Checkout [B]; check B1 starter solenoid and motor and repair or replace if bad; jumper battery cable B+ connection to B1 starter solenoid terminal and check whether engine cranks.