The Cummins/Onan Cummins DFEB is an engine. It powers generator sets from Cummins/Onan, including the DFE.
Also known as: Cummins Cummins DFEB
How to read your Cummins/Onan engine serial & model number →
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan Cummins DFEB.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Air cleaner | Check | 250 hr | 6 mo | X1; replace as necessary; refer to QSX15 engine manual |
| All hardware (fittings, clamps, fasteners, etc.) | Check | 100 hr | Daily or after 8 hours | |
| Anti-freeze and DCA concentration | Check | 250 hr | 6 mo | X1; refer to QSX15 engine manual |
| Coolant heater(s) | Check | 100 hr | Daily or after 8 hours | |
| Drive belt | Check | 250 hr | 6 mo | X1; refer to Cummins QSX15 Series Engine Operation and Maintenance Manual for interval/procedure |
| Engine oil level | Check | 8 hr | Daily or after 8 hours | |
| Fuel filter(s) | Drain | 250 hr | 6 mo | X1; refer to QSX15 engine manual |
| Genset | Inspect | 8 hr | Daily; check for oil, fuel, cooling and exhaust system leaks | |
| Radiator hoses for wear and cracks | Check | 250 hr | Daily or after 8 hours | |
| Charge Air Piping | Check | 50 hr | Weekly | |
| Coolant heater | Check | 50 hr | Weekly or after 50 hours | |
| Coolant level | Check | 50 hr | Weekly or after 50 hours | |
| Exhaust condensate trap | Drain | 100 hr | Drain water to prevent it flowing back into the engine | |
| Fuel level | Check | 50 hr | Weekly or after 50 hours | |
| Oil level | Check | 50 hr | Weekly or after 50 hours | |
| Air cleaner | Clean | 100 hr | Monthly or after 100 hours; clean if required, perform more often in dusty conditions | |
| Battery charging system | Check | 100 hr | Monthly or after 100 hours | |
| Battery electrolyte level | Check | 200 hr | Monthly or After 100 Hrs | |
| Fuel tank water and sediment | Drain | 100 hr | Monthly or after 100 hours | |
| General set inspection | Inspect | 100 hr | Monthly or after 100 hours (Table 5-1, footnote X2): check for oil, fuel, cooling and exhaust system leaks; check exhaust system audibly and visually with set running | |
| Generator air outlet | Check | 100 hr | Monthly or After 100 Hrs | |
| Radiator hoses | Check | 500 hr | 12 mo | Monthly or After 100 Hrs; check for wear and cracks |
| Starting batteries | Check | 100 hr | Check condition and terminals | |
| Air cleaner | Replace | 250 hr | Check air cleaner; replace as necessary. Refer to QSX15 manual. | |
| Crankcase oil and filter | Change | 250 hr | 12 mo | Prime power: every 6 months or 250 hours; standby: every 12 months or 250 hours, whichever comes first |
| Drive belt tension | Check | 250 hr | 6 mo | Visually check belt for wear or slippage; replace if hard or brittle |
| Engine oil and filter | Replace | 250 hr | 6 mo | X1; 6 Months or After 250 Hrs; refer to QSX15 engine manual |
| Radiator Hoses | Inspect | 250 hr | 6 mo | Check for wear & cracks |
| Water coolant filter | Replace | 250 hr | 6 mo | X1; 6 Months or After 250 Hrs |
| Air cleaner element | Change | 500 hr | 12 mo | Yearly or after 500 hours; clean if required more often |
| Coolant filter | Change | 500 hr | 12 mo | Yearly or after 500 hours; refer to engine operation and maintenance manual |
| Cooling system | Clean | 500 hr | 12 mo | Yearly or after 500 hours; drain and replace coolant mixture |
| Crankcase breather | Clean | 500 hr | 12 mo | Yearly or after 500 hours |
| Engine oil and filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Fuel filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Fuel filters | Change | 500 hr | 12 mo | Yearly or after 500 hours |
| Generator insulation resistance | Test | 500 hr | 12 mo | Follow periodically throughout life of set or if generator has set idle with no heaters; contact authorized service center |
| Water coolant filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Cooling systems | Clean | 500 hr | 12 mo | X1; 1 Year |
| Fuel filter | Replace | 12 mo | X1; 1 Year |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Angular alignment T.I.R. limit | not more than .001 | in per inch of radius | center of shaft to indicator axis |
| Clearance | Angular alignment maximum T.I.R. | 0.001 | inch per inch of radius (center of shaft to indicator axis) | measuring deflection to bolt heads |
| Clearance | Exhaust pipe clearance from combustible wall or partition | 12 | inches (305 mm) | minimum |
| Clearance | Exhaust pipe clearance to combustible wall/partition | 12 | inches (305 mm) | |
| Clearance | Float switch assembly float lift clearance below C-clip stop | 1/8 | inch (3 mm) | use a feeler gauge |
| Clearance | Fuel line clearance from electrical wiring | 1/2 | inch (12.7 mm) | |
| Clearance | Fuel line clearance from hot exhaust parts | 2 | inch (51 mm) | |
| Clearance | Generator mount pre-load steel spacer thickness | 1 3/4 | inch | two spacers under both stator foot brackets |
| Clearance | Generator-to-engine angular alignment (T.I.R.) | .001 in. per inch of radius (center of shaft to indicator axis), maximum | in | 750 kW gensets and larger |
| Clearance | MPU installation gap adjustment | back out 1/4 turn after touching gear tooth | turn | |
| Clearance | Vibration isolator base elevation difference | 0.25 | inch (6 mm) | shimmed or grouted within this of each other |
| Clearance | Vibration isolator clearance | 0.25 | inch (6 mm) | |
| Clearance | Vibration isolator nominal clearance (leveling bolt) | 0.25 | inch (6 mm) | minimum, or greater |
| Gap | Coolant level below radiator cap lower sealing surface | 3/4 inch (18 mm) | inch (mm) | |
| Gap | MPU sensor to flywheel ring gear tooth | back it out one quarter turn | turn | sensor threaded in until it just touches gear tooth |
| Other | AVR Droop setting | 5 | % at full load, 0 PF | |
| Other | AVR voltage regulation (load regulation) | approximately ±0.5 | % RMS | |
| Other | Ambient temperature below which coolant heaters recommended (NFPA 110) | 40 | °F | |
| Other | Angular alignment maximum T.I.R. | .001 inches per inch of radius | in/in | center of shaft to indicator axis |
| Other | Battery CCA (minimum) | 1400 | CCA | Cold Soak @ 0° F (-18° C) |
| Other | Battery charging alternator output | 35 | Amps | |
| Other | Battery specific gravity (fully charged) | 1.26 | specific gravity | at 80 F (27 C) |
| Other | Battery specific gravity (high ambient, above 95F/35C) | 1.225 | recommended to reduce electrolyte loss | |
| Other | Battery specific gravity (recharge threshold) | below 1.260 | ||
| Other | Battery specific gravity charge threshold | 1.215 | corrected | charge battery if reading below |
| Other | Battery specific gravity fully charged | 1.260 | corrected | add 0.004 per 10 F above 80 F (27 C) |
| Other | Battery specific gravity, fully charged | approximately 1.260 | specific gravity | at 80 F (27 C) |
| Other | Battery terminal cleaning solution | 1/4 pound baking soda to 1 quart water | ||
| Other | CAN datalink main trunk maximum length | 40 | meters | no more than 30 devices |
| Other | CAN datalink stub maximum length | 1 | meter | stub from main trunk to each module |
| Other | CAN datalink transmission speed | 250 | KBaud | |
| Other | Charge battery if specific gravity below | 1.215 | specific gravity | |
| Other | Compression ratio | 17.0:1 | ||
| Other | Frequency regulation | Isochronous | ||
| Other | Fuel lift height limit | 6 | feet | (1.8 meters) between fuel lift pump and bottom of dip tube |
| Other | Fully charged battery corrected specific gravity | 1.260 | specific gravity | corrected reading @ 80 F (27 C) |
| Other | GOV GAIN default value for paralleling applications | 70 | % | |
| Other | Maximum cranking voltage drop | 2 | volts | difference between battery and starter terminals while cranking |
| Other | Mounting bolt size | 5/8 | inch or 16 mm | |
| Other | Mounting bolts | 5/8 inch or 16 mm | inch / mm | anchored mounting bolts |
| Other | Optional run/alarm relay contact rating | 10 amps at 28 VDC or 120 VAC, 80%PF; 6 amps at 240 VAC, 80%PF; 3 amps at 480/600 VAC, 80%PF | amps | |
| Other | Output frequency adjustment (PCC) | +/- 5 | % | set running under normal parameters |
| Other | Over current warning threshold | 110 | % of rated | |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal | 55 | Hz | reset 53 Hz |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal | 65 | Hz | reset 63 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal | 45 | Hz | reset 47 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal | 55 | Hz | reset 57 Hz |
| Other | Over/Under Voltage Sensor Module time delay | typically 25 percent, approximately 2.5 | seconds | |
| Other | Overcrank cranking limit | 75 | seconds | three 15-second cranking cycles with two 15-second rest periods |
| Other | Overcurrent shutdown threshold | 110% of rated | % of rated | PCC time/current calculation |
| Other | Overcurrent warning threshold | 110% of rated for 60 seconds | % of rated | generator output current |
| Other | Overload warning threshold | 105% of standby or 115% of prime | % of rating | three-phase power output; load dump after five seconds, warning after 60 seconds |
| Other | Overspeed limit | 2150 ± 50 | rpm | |
| Other | REG VHZ (underfrequency roll-off) adjustable range | 1 through 50; normal range 7 through 21 | ||
| Other | Random frequency variation | ± 0.25 | % | |
| Other | Short circuit shutdown threshold | 175 | % of rated current | |
| Other | Short circuit shutdown threshold | 175% of rated | % of rated | generator output current |
| Other | Specific gravity correction | 0.004 | gravity point per 10 F above 80 F (27 C) | |
| Other | Start delay adjustment range | 0 to 300 | seconds | |
| Other | Start delay adjustment range (PCC) | 0 to 300 | seconds | Auto mode remote starting |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for coolant recommendations/specifications | 58.0 L | Cooling System (Capacity Std. Radiator) printed as 15.3 Gal (58 L); check anti-freeze and DCA concentration | ||
| Coolant | Balanced coolant mixture of water and antifreeze | Refer to Cummins engine Operation and Maintenance Manual | 90.0 L | Capacity with standard radiator 24 Gal (90 L); drain and replace mixture every year or after 500 hours; add until 3/4 inch (18 mm) below radiator cap lower sealing surface | |
| Coolant | soft water / E.G. / DCA mixture | Cooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist). | |||
| Engine oil | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for lubricating oil classification/viscosity | 58.0 L | Oil Cap. w/Filters printed as 26 Gallons (58 L); gense is shipped filled with correct type and quantity of oil | ||
| Fuel | ASTM D975 No. 2-D | Cetane number 40-50, 300-500 ppm Sulfur | Diesel fuel specifications | ||
| Fuel | ASTM No. 2 diesel | Cummins engines normally use ASTM No. 2 diesel fuel. | |||
| Fuel | Diesel | Day tank fuel transfer pump maintains reservoir of diesel fuel in the day tank. | |||
| Fuel | diesel | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for fuel recommendations; do not use zinc coated or copper fuel lines with diesel fuel; keep fuel supply tanks as full as possible | |||
| Grease | Lithium based grease | Mobilux No. 2 or Shell Alvania R3 | 2.74 oz (81 ml) | Generator end bearing. Temperature range -22F to +248F (-30C to +120C). Grease should be equally divided between the bearing, bearing cap cavity, and bearing cartridge cavity. | |
| Grease | Lithium based grease, Mobilux No. 2 or Shell Alvania R3 | -30°C to 120°C | 2.74 oz (81 ml) | End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity. | |
| Other | Donaldsons D1400 solvent | Soak air cleaner filter element at least 15 minutes in water and D1400 solvent to remove soot, carbon and dirt |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 27 | Low AC voltage shutdown | Voltage on any phase has dropped below a preset value; adjustable 50-95% of reference, delay 2-20 seconds; default 85% for 10 seconds | Shutdown | Genset shut down on low AC output voltage |
| 32 | Reverse power shutdown | Adjustment range 5-20% of standby kW rating, delay 1-15 seconds; default 10%, 3 seconds | Shutdown | Genset shut down on reverse power |
| 59 | High AC voltage shutdown | Output voltage on any phase exceeds preset values; adjustable 105-125% of nominal, time delay 0.1-10 seconds; default 110% for 10 seconds | Shutdown | Genset shut down on high AC output voltage |
| 81 o | Over frequency shutdown/warning | Generator set is operating at a potentially damaging frequency level; 2-10 Hz above nominal, 1-20 second delay; default 6 Hz, 20 seconds, disabled | Shutdown | Shutdown/warning on over frequency |
| 81 u | Under frequency shutdown | Generator set output frequency cannot be maintained; 2-10 Hz below reference, 5-20 second delay; default 6 Hz, 10 seconds | Shutdown | Genset shut down on under frequency |
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode (governed at 800 RPM, generator build-up inhibited). | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 111 | Internal ECM error | Category A | Shutdown | |
| 112 | Actuator not responding | Category A | Shutdown | |
| 113 | Actuator sensor fault | Category B | Warning | |
| 115 | No speed signal | Category A | Shutdown | |
| 116 | Time press sensor high | Category A | Shutdown | |
| 117 | Time press sensor low | Category A | Shutdown | |
| 118 | Pump press sensor high | Category B | Warning | |
| 119 | Pump press sensor low | Category B | Warning | |
| 121 | No engine speed signal | Category C | Warning | |
| 122 | Manifold air press sensor | Category B | Warning | |
| 123 | Manifold air press sensor | Category B | Warning | |
| 135 | Oil Pressure Sensor High | Engine oil pressure sensor is shorted high | Warning | Verify fault simulation not enabled (InPower); inspect sensor and engine harness connector pins; use oil pressure sensor simulator to check control response, replace sensor if it responds; check P7-13, 17, 21 for short (>200k ohms OK) and open (10 ohms or less OK) |
| 141 | Oil Pressure Sensor Low | Engine oil pressure sensor is shorted low | Warning | Verify fault simulation not enabled; inspect sensor/harness connector pins; use simulator to check control response; check P7-13, 17, 21 short/open |
| 143 | Pre-Low Oil Pres | Engine oil pressure has dropped below the warning trip point | Warning | If powering critical loads, wait until next shutdown period then follow code 415 procedure |
| 144 | Coolant Temperature Sensor High | Coolant temperature sensor signal is shorted high | Warning | Verify fault simulation not enabled; inspect sensor/harness pins; use resistive sensor simulator, replace sensor if control responds; check P7-30 (IH20) and P7-34 (IH20 COM) for short to ground and pin-to-pin (>200k ohms OK); compare sensor resistance between pins |
| 145 | Coolant Temperature Sensor Low | Coolant temperature sensor signal is shorted low | Warning | Verify fault simulation not enabled; inspect sensor/harness pins; use resistive sensor simulator; check P7-30 and P7-34 for short circuits and compare resistance |
| 146 | Pre-High Coolant Temp | Engine operating near cooling system capacity | Warning | Review 151 correction list |
| 151 | High Coolant Temp | Coolant temperature has risen above the shutdown trip point | Shutdown | Check coolant level/leaks, airflow obstructions, fan belt, blower fan/circulation pumps; reset and restart |
| 152 | Low coolant temp | Category D | Warning | Warning occurs when jacket water coolant temperature is 70 F (21 C) or lower. Check coolant heater power supply (blown fuse or disconnected heater cord); check jacket water coolant level and replenish; look for coolant leakage and repair. In applications where ambient is below 40 F (4 C) Low Coolant Temp may be indicated even though the heaters operate. |
| 153 | Manifold air temp sensor | Category C | Warning | |
| 154 | Manifold air temp sensor | Category C | Warning | |
| 155 | Manifold air temp alarm | Category A | Shutdown | |
| 197 | Low Coolant Level | Coolant level below warning trip point (optional) | Warning | Follow code 235 procedure at next shutdown |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Oil pressure limits are listed in Table 4-3. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Set is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Reduce load if possible by turning off non-critical loads. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 212-SHUTDOWN procedure. |
| 212 | HIGH COOLANT TEMP | Indicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary). | Shutdown | Allow engine to cool down completely. Check for obstructions to cooling airflow; check fan belt; check coolant mixture; check blower fan and circulation pumps on remote radiator installations. Reset control and restart. |
| 213 | COOLANT SENDER | Indicates that the resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender. Resistance should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Look for coolant leakage points and repair if necessary. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Reset control and restart after correcting problem. Shutdown will not occur if genset is in Idle mode (low coolant warning only). |
| 220 | MAG PICKUP | Indicates mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display. |
| 221 | FAIL TO CRANK | Indicates possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery. |
| 222 | OVERCRANK | Indicates possible fuel system problem. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines. Check for dirty fuel filter and replace if necessary. Check for dirty or plugged air filter and replace if necessary. Reset the control and restart after correcting the problem. |
| 223 | OVERSPEED | Engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Check mechanical fuel linkage and actuator; check governor output module (A38) and digital board (A32). |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 228 | Low coolant pressure | Category A | Shutdown | |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check float level on battery charger if applicable (lower float level). Check engine DC alternator; replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Discharged or defective battery. See Warning message 230, LOW DC VOLTAGE. |
| 233 | Coolant pressure warning | Category A | Warning | |
| 234 | Overspeed | Engine speed signal indicates engine speed greater than the shutdown threshold | Shutdown | Cold engine: clear fault and restart; large block load removal: clear and restart; verify fault simulation not enabled; reset threshold via InPower; monitor engine RPM; check electronic governor actuator for binding |
| 235 | Low Coolant Level | Coolant level below shutdown trip point (optional) | Shutdown | Check coolant level and leaks; reset and restart |
| 236 | Position sensor | Category A | Shutdown | |
| 240 | LOW FUEL−DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform initial start setup procedure; replace digital board (A32) if fault repeats. |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform adjustment and calibration procedures; replace digital board (A32) if fault repeats. |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify selected values; repeat save operation; replace digital board (A32) if fault repeats. |
| 253 | Oil level alarm | Category D | Shutdown | |
| 254 | Fuel shutoff valve | Category A | Shutdown | |
| 259 | Fuel shutoff valve | Category C | Warning | |
| 260 | CUSTOMER FAULT 1 | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 261 | GROUND FAULT | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 262 | RUPTURE BASIN | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 263 | HIGH GEN TEMP | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 265 | Fuel temperature sensor | Category C | Warning | |
| 266 | Fuel temperature | Category A | Shutdown | |
| 270 | PHASE ROTATION | The phase relationship between the generator set and the system bus is not matched. | Shutdown | Verify genset phase rotation matches bus; verify control wiring to bus PT module. |
| 272 | FIRST START | PowerCommand control is not receiving a proper signal from the system master first start sensor. | Warning | Verify Master First Start Sensor and interconnection wiring. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds. | Shutdown | Check PCC, alternator, excitation circuit, and PT/CT module wiring. |
| 303 | LOW AC VOLTAGE | One or more phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check PMG/field wiring, rotating rectifier, load and connectors. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated. | Shutdown | Check fuel supply, intake air supply and load. |
| 316 | Fuel supply pump | Category B | Warning | |
| 318 | Fuel supply pump | Category B | Warning | |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 321 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown. | Shutdown | Check load and load lead connections. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 326 | Oil level warning | Category D | Warning | |
| 330 | OVERLOAD | Indicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating. After five seconds, the Load Dump output is activated. After 60 seconds, the OVERLOAD warning is activated. | Warning | Check load and load lead connections. |
| 335 | REVERSE POWER | Indicates improper CT or PT phasing. (Non-parallel units only.) | Shutdown | Check CT / PT wiring. Refer to CT Installation in Section 5. |
Showing the first 80 of 284 codes.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.
Tools: Dial indicator, Shims
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.
Tools: Dial indicator, Wooden shims
⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.
⚠ Do not bar engine over by prying on fan blade.
Tools: dial indicator
Tools: Dial indicator with holding device (magnetic base or clamp)
Tools: dial indicator
⚠ Contacting hazardous voltage components can cause electrocution, resulting in severe personal injury or death.
⚠ Improper calibration or adjustment of the PowerCommand control can cause equipment malfunction or damage.
Tools: Calibrated RMS multimeter (Fluke models 87 or 8060A)
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Disconnect the negative (-) battery cable(s) before beginning.
Tools: Two 1 3/4" T x 2" W x 6" L steel spacers, Adequate lifting device
⚠ Contacting hazardous voltage components can cause electrocution, resulting in severe personal injury or death.
⚠ Improper calibration or adjustment of the PowerCommand control can cause equipment malfunction or damage.
Tools: Calibrated RMS multimeter (Fluke models 87 or 8060A)
⚠ Contacting hazardous voltage components can cause electrocution, resulting in severe personal injury or death.
⚠ Improper calibration or adjustment of the PowerCommand control can cause equipment malfunction or damage.
Tools: Calibrated RMS multimeter (Fluke models 87 or 8060A)
Tools: Frequency meter or tachometer, Jumper wire
Tools: Dial indicator with magnetic base or clamp
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12 lead generator sets | Load wires are routed through the CTs | Reconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage). | ||
| 6 lead generator sets | Generator output leads are routed through the CTs | Non-reconnectable gensets (6 leads) have single secondary CTs (2 pins). | ||
| Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F) | Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100). | |||
| A | CT21 – U load leads | A phase | CT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground. | |
| A (U) | Bus PT module TB1 A | bus A phase | Bus PT module A39. | |
| A (U) | CT21 | U load leads (A phase) | CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground. | |
| B | CT22 – V load leads | B phase | CT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground. | |
| B (V) | Bus PT module TB1 B | bus B phase | Bus PT module A39. | |
| B (V) | CT22 | V load leads (B phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| C | CT23 – W load leads | C phase | CT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground. | |
| C (W) | Bus PT module TB1 C | bus C phase | Bus PT module A39. | |
| C (W) | CT23 | W load leads (C phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| N | Bus PT module TB1 N | bus neutral | Bus PT module A39. | |
| 110/190 | 3 | 12 | Full load current at Standby rating: 1901 A | |
| 110/220 | 3 | 12 | Full load current at Standby rating: 1642 A | |
| 115/230 | 3 | 12 | Full load current at Standby rating: 1571 A | |
| 120/208 | 3 | 12 | Full load current at Standby rating: 1737 A | |
| 139/240 | 3 | 12 | Full load current at Standby rating: 1505 A | |
| 220/380 | 3 | 12 | Full load current at Standby rating: 951 A | |
| 230/400 | 3 | 12 | Full load current at Standby rating: 903 A | |
| 240/416 | 3 | 12 | Full load current at Standby rating: 868 A | |
| 255/440 | 3 | 12 | Full load current at Standby rating: 821 A | |
| 277/480 | 3 | Wye, 4 Wire | 12 | Full load current at Standby rating: 753 A |
| 277/480 | 3 | Wye, 4 wire | 12 | Alternator 60 Hz, 12 lead, limited range, 125 °C; single phase power may be taken at up to 40% of nameplate kW at unity power factor |
| 347/600 | 3 | 12 | Full load current at Standby rating: 602 A | |
| high voltage genset | 12-lead CT secondary wire marked 2/3 to pin 2 | 2/3 | For high voltage gensets. | |
| low voltage genset | 12-lead CT secondary wire marked 2/3 to pin 3 | 2/3 | For low voltage gensets. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Cummins/Onan Cummins DFEB powers 1 generator set(s), including Cummins/Onan DFE.
A commonly reported issue on generators using the Cummins/Onan Cummins DFEB is: Over Current.