| Fails to crank | Bad battery connection | Clean and tighten all battery and cable connections. |
| Fails to crank | Low battery | Check specific gravity. Recharge or replace if necessary. |
| Fails to crank | Faulty start solenoid (K1) | Check for battery voltage at K1 "I" terminal. Push start switch. Check start solenoid "S1" terminal voltage to ground. When battery voltage at start solenoid "B-" terminal is present, battery voltage should also appear at "S1" terminal. If not, check K3. |
| Fails to crank | Faulty start switch | Jumper switch (#3 terminal) to ground. If solenoid energizes, replace switch. |
| Cranks slowly | Bad battery connection | See 1 above (FAILS TO CRANK): Clean and tighten all battery and cable connections. |
| Cranks slowly | Low battery | See 2 above (FAILS TO CRANK): Check specific gravity. Recharge or replace if necessary. |
| Cranks but won't start | Faulty fuel solenoid or fuel pump | Fuel solenoid must open during cranking and running. Check by removing steel line from carburetor and crank engine. If fuel solenoid is open, fuel will pulsate out of this line. If it does not, the fuel solenoid and fuel pump must be checked separately to determine defective part. |
| Cranks but won't start | Faulty ignition | Check to see if points open and close during cranking. If they do not open and close, adjust and set points. Plug and plug wires must be in good condition. Voltage at ignition coil negative terminal (-) must alternate from +12 volts to zero volts as points open and close during engine cranking. |
| Cranks but won't start | Inoperative choke | With engine not running, check choke vane movement by pushing choke lever arm. Choke must be in closed position with cold engine and must be free to move against bimetal spring. As engine warms up, bimetal spring relaxes and allows choke vane to open fully. The lever will pulsate as engine warms up. See ADJUSTMENT section. |
| Unit starts, but stops immediately after releasing start switch S1 | Low oil level | Check oil level. If low or empty, refill to proper level. |
| Unit runs then stops | Low oil level | Check oil level. If low or empty, refill to proper level. |
| Unit runs then stops | Stuck choke | See 3 above (CRANKS BUT WON'T START): With engine not running, check choke vane movement by pushing choke lever arm. Choke must be in closed position with cold engine and must be free to move against bimetal spring. As engine warms up, bimetal spring relaxes and allows choke vane to open fully. The lever will pulsate as engine warms up. See ADJUSTMENT section. |
| Unit runs but surges | Governor not adjusted properly | Readjust governor. |
| Unit stops | Faulty ignition | See 4 above (CRANKS BUT WON'T START): Check to see if points open and close during cranking. If they do not open and close, adjust and set points. Plug and plug wires must be in good condition. Voltage at ignition coil negative terminal (-) must alternate from +12 volts to zero volts as points open and close during engine cranking. |
| Unit stops | Out of fuel | Refill fuel tank. |
| Unit stops | Low oil level | Check oil level. If low or empty, refill to proper level. |
| Remote running time meter or generator lamp inoperative | Blown fuse (F1) | Replace F1 fuse on control. |
| Engine does not crank | Engine cranks at set but not at remote start panel; remote start control wires not continuous between generator set and remote start panel; control wires not sized large enough to avoid excessive voltage drop | Replace control wires with correct wire gauge |
| Engine does not crank | Battery not fully charged or terminal connections not clean and tight | Recharge battery and clean and tighten all terminal connections |
| Engine does not crank | No battery voltage present between control terminals 3 and 5 when switch S1 is pushed to START (or when remote start switch is pushed to START); fuse F1 open | Replace start-stop switch S1 or remote start switch as required |
| Engine does not crank | No battery voltage present between K1 start solenoid terminal S1 and ground when start-stop switch S1 is pushed to START | Replace K1 start solenoid |
| Engine does not crank | Generator brushes, commutator, DC armature windings, or field windings faulty | Check generator brushes, commutator, DC armature windings, and field windings. See Generator Service Procedures section |
| Engine cranks but does not start | No battery voltage present between control terminal 6 and ground when start-stop switch S1 is pushed to START | Check all solenoid terminal connections. If OK, replace K1 start solenoid on BF (Spec A) or K2 ignition relay on BF (Spec B) and NH (Spec J) |
| Engine cranks but does not start | Fuse F2 open | Replace fuse F2 |
| Engine cranks but does not start | Low engine oil level; low oil pressure switch operation | Check engine oil level and add if necessary. If oil level is OK, remove wire lead from low oil pressure switch and push start-stop switch S1 to START. Check low oil pressure switch operation. Switch should open when oil pressure builds up and close when oil pressure drops. Replace if necessary |
| Engine cranks but does not start | Low oil pressure lead wire grounded | Check low oil pressure lead wire for grounding and repair or replace as necessary |
| Engine cranks but does not start | High air temperature switch operation | Remove wire lead from high air temperature switch and push start-stop switch S1 to START (do not let lead ground while disconnected). Check high air temperature switch operation. Switch should be open unless engine overheats. Replace if necessary |
| Engine cranks but does not start | High air temperature lead wire grounded | Check high air temperature lead wire for grounding and repair or replace as necessary |
| Engine cranks but does not start | Fuel pump does not operate or fuel solenoid does not open during cranking; fuel pump lead wire connections | Check the fuel pump lead wire connections and repair or replace as necessary. Refer to the Fuel System section for testing and service procedures |
| Engine cranks but does not start | Choke not closed | Refer to the Ignition System section for testing and service procedures |
| Engine starts but stops when start switch is released | No DC voltage output from the generator between control terminal 6 and ground while cranking | Check R1 resistor and connections. If OK, check brushes, commutator, armature windings, and field windings. Refer to Generator Service Procedures section |
| Engine is running - then stops | Low fuel level or low oil level | Check for low fuel level or low oil level. Refill with fuel or oil as required |
| Engine is running - then stops | Low oil pressure, low oil pressure switch malfunction, overheating, or high air temperature switch malfunction | See sections B5 through B11 for the troubleshooting procedures |
| Engine is running - then stops | No battery voltage present between control terminal 6 and ground when start-stop switch S1 is pushed to START | Check for an open R1 resistor or for open connections between R1 and fuse F2. If OK, check generator brushes, commutator, DC armature windings, and field windings. See Generator Service Procedures section |
| Engine is running - then stops | Fuse F2 open | Replace fuse F2 |
| Low battery - no charge rate | Battery charger does not show a normal charge rate of 1 to 1-1/2 amps | Check condition of battery. Generator set charger will not recharge a battery that is in a very low state of charge. Use a separate battery charger to bring battery up to full charge |
| Low battery - no charge rate | Wire connection between CR1 diode, K1 start solenoid, R2 resistor, and battery | Check wire connection between CR1 diode, K1 start solenoid, R2 resistor, and battery |
| Low battery - no charge rate | CR1 diode shorted or open | Replace defective CR1 diode |
| Low battery - no charge rate | Defective R2 resistor | Replace R2 resistor |
| Running time meter inoperative | Wires between control terminal 6 and battery positive terminal for running time meter, or ground wire and connection to meter | Check wires between control terminal 6 and battery positive terminal for running time meter, and ground wire and connection to meter |
| Running time meter inoperative | Defective running time meter | Replace defective running time meter |
| Battery condition meter inoperative | Fuse F1 open | Replace fuse F1 |
| Battery condition meter inoperative | Wire connections between remote connector plug terminal 5 (or TB1-5 where applicable) and the battery condition meter and between the battery condition meter and ground | Check wire connections between remote connector plug terminal 5 (or TB1-5 where applicable) and the battery condition meter and between the battery condition meter and ground |
| Battery condition meter inoperative | Voltmeter does not read battery voltage minus 10 volts between battery charge meter positive terminal and ground; defective zener diode | Replace defective zener diode |
| Battery condition meter inoperative | Defective battery condition meter | Replace defective battery condition meter |
| Engine does not crank | No battery voltage present between remote connector plug terminals 3 and 5 (between terminals TB1-3 and TB1-5 where applicable) when switch S1 is pushed to START (or when remote start switch is pushed to START); fuse F1 open | Replace start-stop switch S1 or remote start switch as required |
| Engine does not crank | No battery voltage present between ground and K3 relay terminal 87A; fuse F2 open; run ignition relay K3 contacts 87A-30 not closed | Replace run ignition relay K3. Replace fuse F2 |
| Engine does not crank | Generator brushes, commutator, DC armature windings, or DC field windings faulty | Check generator brushes, commutator, DC armature windings, and DC field windings. See Generator Service Procedures section |
| Engine cranks but does not start | No battery voltage present between remote connector plug terminal 6 and ground when start-stop switch is pushed to START; terminal connections on K2 crank ignition relay | Check all terminal connections on K2 crank ignition relay. If OK, replace K2 relay |
| Engine cranks but does not start | Fuel pump does not operate during cranking; fuel pump lead wire connections | Check the fuel pump lead wire connections and repair or replace as necessary. Refer to the Fuel System section for testing and service procedures |
| Engine starts but stops when start switch is released | Incorrect oil level | Add oil as required |
| Engine starts but stops when start switch is released | Low oil pressure switch operation | Disconnect the low oil pressure switch lead wire, ground the end connected to the control, and push the start-stop switch to START. Check low oil pressure switch operation. Switch should close when oil pressure builds up and open when oil pressure drops. Replace if necessary |
| Engine starts but stops when start switch is released | Low oil pressure lead wire open circuit | Check low oil pressure lead wire for an open circuit and repair or replace as necessary. Reconnect oil pressure lead wire and push start-stop switch to START |
| Engine starts but stops when start switch is released | Wire connections between R1 resistor and K3 run ignition relay and between R1 resistor and K1 start solenoid; R1 resistor resistance not OK | Check wire connections and resistance of R1 resistor (see Parts Catalog for resistance value). Replace R1 resistor |
| Engine starts but stops when start switch is released | No voltage at remote connector plug terminal 6 and ground (or TB1-6 and ground where applicable) when start-stop switch S1 is pushed to START; fuse F1 open | Connect a jumper wire between remote connector plug terminals 5 and 6 (or TB1-5 and TB1-6 where applicable) and push start-stop switch S1 to START. Replace K3 run relay |
| Engine starts but stops when start switch is released | Generator brushes, commutator, DC armature, or field windings faulty | Check generator brushes, commutator, DC armature, and field windings. Refer to Generator Service Procedures section |
| Engine is running - then stops | Low oil pressure or low oil pressure switch malfunction | See sections C3, C4, and C5 for troubleshooting procedures |
| Engine is running - then stops | No battery voltage present between remote connector plug terminal 6 and ground (or TB1-6 and ground if applicable) when start-stop switch S1 is pushed to START; fuse F2 open | Replace fuse F2 |
| Engine is running - then stops | Open R1 resistor, open connection between K3 run ignition relay and R1 resistor, or defective K3 run ignition relay | See sections C6 through C11 for troubleshooting procedures |
| No AC output voltage | Blown fuse or circuit breaker (if used) | Look for cause and repair. Then replace fuse or reset circuit breaker |
| No AC output voltage | Disconnected wire or lead on brushes | Reconnect wire or wires |
| No AC output voltage | Brushes not making contact with slip rings | Check brush springs for free movement or brushes which may be excessively worn |
| No AC output voltage | Open, grounded or short circuit in field or armature winding | Test for open, grounded, or shorted windings. Repair or replace as necessary |
| Low AC output voltage | External short circuit on line | Locate and eliminate short circuit problem |
| Low AC output voltage | Generator overloaded | Remove part of load |
| Low AC output voltage | Shorted or grounded circuit in field or armature winding | Test for open, grounded, or shorted windings. Repair or replace as necessary |
| Low AC output voltage | Engine not running properly causing generator to slow down | Refer to Engine Troubleshooting Guide |
| Noisy generator | Defective bearing in end bell | Replace bearing |
| Noisy generator | Brush rig loose | Retorque |
| Noisy generator | Armature and field frame rubbing together | Check for generator misalignment and for varnish lumps between armature and field. Repair as necessary |
| Noisy generator | Raised commutator bar or high mica condition | Turn commutator on lathe; undercut mica insulation |
| Generator overheats | Generator overloaded | Remove part of load |
| Generator overheats | Windings and parts covered with oil or dirt | Clean generator. Take necessary steps to allow for proper cooling |
| Generator overheats | Air intake restricted or incoming air too hot | |