The Cummins/Onan 6CTAA8.3-G3 is a 8.3 L 6-cylinder turbocharged and cac engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the DGFC. It holds 23.8 L (6.3 gal) of oil and 25.7 L (6.8 gal) of coolant.
Also known as: Cummins 6CTAA8.3-G3
Part of the Cummins/Onan 6CTAA8.3 engine family — 4 variants share parts & fitment.
| Oil capacity | 23.8 L |
|---|---|
| Coolant capacity | 25.7 L |
| Displacement | 8.3 L |
| Cylinders | 6 |
| Aspiration | Turbocharged and CAC |
| Rated speed | 1800 rpm |
How to read your Cummins/Onan engine serial & model number →
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan 6CTAA8.3-G3.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Charge air piping | Check | 50 hr | Daily or after 8 hours | |
| Coolant level | Check | 8 hr | Daily or after 8 hours | |
| Engine oil level | Check | 8 hr | Daily or after 8 hours | |
| Fuel Filter(s) | Drain | 8 hr | Drain 1 cup or more of fuel to remove water and sediment. Refer to engine operation and maintenance manual for procedure. | |
| Fuel Tanks (water and sediment) | Drain | 8 hr | Drain 1 cup or more of fuel to remove water and sediment. | |
| Fuel level | Check | 8 hr | Daily or after 8 hours | |
| General genset inspection | Inspect | 8 hr | Daily or after 8 hours. Check for oil, fuel, cooling and exhaust system leaks; check exhaust audibly and visually with set running. | |
| Inspect Genset | Check | 8 hr | Check for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running and repair any leaks immediately. | |
| Oil Level | Check | 8 hr | Keep oil level near the dipstick high mark without overfilling. | |
| Air Cleaner | Clean | 50 hr | Clean if required. Perform more often in dusty conditions. | |
| Air cleaner (clean if required) | Clean | 50 hr | Weekly or after 50 hours; perform more often in dusty conditions | |
| Battery charging system | Check | 50 hr | Weekly or after 50 hours | |
| Coolant heater | Check | 50 hr | Weekly or after 50 hours | |
| Crankcase Oil | Drain | 50 hr | First service — Break-in: drain and replace the crankcase oil after the first 50 hours of operation on new generator sets. | |
| Exhaust condensate trap | Drain | 50 hr | Weekly or after 50 hours | |
| Water and sediment from fuel tank | Drain | 50 hr | Weekly or after 50 hours; drain 1 cup or more of fuel to remove water and sediment | |
| Radiator hoses for wear and cracks | Inspect | 100 hr | Monthly or after 100 hours | |
| Starting batteries | Check | 100 hr | Monthly or after 100 hours | |
| Battery electrolyte level | Check | 200 hr | Check at least every 200 hours of operation | |
| Anti-freeze and DCA Concentration | Check | 250 hr | 3 mo | Refer to engine operation and maintenance manual. |
| Crankcase oil and filter | Change | 250 hr | 12 mo | Refer to Cummins Engine Operation and Maintenance Manual. Standby applications: change every 12 months or 250 hours, whichever comes first. |
| Drive Belt Tension | Check | 250 hr | 3 mo | Visually check belt for evidence of wear or slippage. Replace if hard or brittle. Refer to engine operation and maintenance manual. |
| Fuel Filters | Change | 250 hr | 3 mo | Refer to engine operation and maintenance manual. |
| Governor Adjustment | Check | 250 hr | 3 mo | |
| Radiator Hoses for Wear & Cracks | Check | 250 hr | 3 mo | |
| Air Cleaner Element | Change | 500 hr | Perform more often in dusty conditions. Replace yearly or sooner if service indicator button pops up. | |
| Coolant Filter | Change | 500 hr | 6 mo | Refer to engine operation and maintenance manual. |
| Cooling System | Clean | 500 hr | 6 mo | Refer to engine operation and maintenance manual. |
| Crankcase Breather | Clean | 500 hr | 6 mo | Refer to engine operation and maintenance manual. |
| Valve Lash | Adjust | 1000 hr | After 1000 hours; contact an authorized service center for service | |
| Alternator Bearings | Inspect | 4000 hr | 24 mo | Inspect all sealed bearings every 4000 to 4500 hours (10000 hr/2 years) |
| Alternator Bearings | Replace | 30000 hr | 60 mo | Replace all sealed bearings every 30000 hr/5 years (or if necessary after 10000 hr/2 years) |
| Air cleaner element | Replace | 12 mo | Replace yearly or sooner if service indicator pops up; more often in dusty conditions | |
| Generator set exercise | Test | 1 mo | Exercise at least once a month for a minimum of 30 minutes at not less than 30 percent of nameplate rating |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Float switch lift below C-clip stop | 1/8 | inch (3 mm) | |
| Clearance | Overspeed switch magnet-to-fly arm air gap (minimum) | 0.005 | inches (0.13 mm) | |
| Other | Battery electrolyte corrected specific gravity (fully charged) | 1.260 | electrolyte temperature corrected | |
| Other | Battery electrolyte specific gravity, fully charged (corrected) | 1.260 | corrected to 80 °F (27 °C) | |
| Other | Battery recharge threshold specific gravity | 1.215 | ||
| Other | Battery specific gravity temperature correction | four gravity points (0.004) for every ten degrees above 80 F (27 C) | ||
| Other | Battery specific gravity, fully charged | approximately 1.260 | at 80°F (27°C) | |
| Other | Cycle crank crank and rest time | 7 to 20 | seconds | |
| Other | Cycle crank number of cycles | 3, 4, or 5 | ||
| Other | ECM fuse F1 (starter solenoid circuit) | 20 | amps | |
| Other | ECM fuse F2 (fuel solenoid circuit) | 20 | amps | |
| Other | ECM fuse F3 (continuous B+ to remote circuits) | 15 | amps | |
| Other | ECM fuse F4 (ECM circuits) | 5 | amps | |
| Other | ECM fuse F5 (engine gauge circuits) | 5 | amps | |
| Other | Frequency adjustment range | ±5% | % | genset running |
| Other | Fuse A31-F1 (control B+) | 5 | Amp | Engine Interface board |
| Other | Fuse A31-F3 (auxiliary B+) | 5 | Amp | Engine Interface board; panel lights, run and start relays |
| Other | Fuse A38-F1 (Network B+) | 10 | Amp | Governor Output Module |
| Other | Fuse A38-F2 (Switched B+) | 10 | Amp | Governor Output Module |
| Other | Fuse A38-F3 (Governor B+) | 10 | Amp | Governor Output Module |
| Other | Fuse TB-Bat F1 (Customer B+) | 20 | Amp | Engine Harness Assembly |
| Other | GOV RAMP adjustment range | 0 through 10 | seconds | |
| Other | Governor droop adjustment range | within 5 | percent of nominal frequency (3 Hz for 60Hz sets, 2.5 Hz for 50Hz sets) | |
| Other | Low oil pressure / high engine temperature fault time delay | about 10 | seconds | following starter disconnect and inhibited during cranking |
| Other | Overcrank limit (Sentinel) | 60 | seconds | |
| Other | Overcrank option limit (Detector) | 75 | seconds | |
| Other | REG VHZ adjustment range | 1 through 50 (normal range 7 through 21) | ||
| Other | Setup/calibration menu access code | 574 | ||
| Other | Standard cycle cranking (Detector) | three 15-second cranking cycles with two 15-second rest periods | ||
| Other | Start delay adjustment range | 0 to 300 | seconds | remote starting in Auto mode |
| Other | Stop delay adjustment range | 0 to 600 | seconds | remote stopping in Auto mode |
| Other | Voltage adjustment range | ±5% | % | genset running |
| Pressure | Engine oil pressure (normal) | 30 to 65 | psi (207 to 449 kPa) | at normal operating temperature |
| Pressure | Engine oil pressure range (low oil pressure troubleshooting) | 25 to 65 | psi (172 to 449 kPa) | |
| Pressure | Fuel shutoff valve rating (TB1-8 and TB1-5) | not more than 0.5 | amps | 120 or 240 VAC |
| Pressure | Idle oil pressure | 10 - 30 | psi (69 - 207 kPa) | idle |
| Pressure | Idle oil pressure | 10-30 | psi (69-207 kPa) | idle |
| Pressure | Idle oil pressure | 69-207 | kPa | idle |
| Pressure | Idle oil pressure (normal) | 10-30 | psi (69-207 kPa) | Engine model 6C, idle |
| Pressure | Idle oil pressure shutdown limit | 55 | kPa | idle |
| Pressure | Idle oil pressure shutdown limit | 8 | psi (55 kPa) | idle |
| Pressure | Idle oil pressure warning limit | 12 | psi (83 kPa) | idle |
| Pressure | Idle oil pressure warning limit | 83 | kPa | idle |
| Pressure | Low Oil Pressure shutdown threshold | 14 | psi (97 kPa) | |
| Pressure | Low oil pressure shutdown limit | 14 | psi (97 kPa) | |
| Pressure | Max. Allowable Exhaust Back Pressure | 41 | in. H2O | |
| Pressure | Max. Fuel Inlet Restriction | 4 | in. Hg (13.5 kPa) | |
| Pressure | Max. Fuel Return Restriction | 10 | in. Hg (33.8 kPa) | |
| Pressure | Max. Fuel Return Restriction | 20 | in. Hg (67.6 kPa) | |
| Pressure | Normal Oil Pressure | 40-70 | psi | normal |
| Pressure | Normal oil pressure | 276-483 | kPa | |
| Pressure | Normal oil pressure | 40 - 70 | psi (276 - 483 kPa) | normal operating speed |
| Pressure | Oil pressure shutdown limit | 103 | kPa | |
| Pressure | Oil pressure shutdown limit | 15 | psi (103 kPa) | normal operating speed |
| Pressure | Oil pressure warning limit | 138 | kPa | |
| Pressure | Oil pressure warning limit | 20 | psi (138 kPa) | normal operating speed |
| Pressure | Pre-Low Oil Pressure warning threshold (Detector control) | 20 | psi (138 kPa) | |
| Pressure | Pre-low oil pressure alarm | 20 | psi (137 kPa) | |
| Pressure | Radiator cleaning maximum air/water pressure | 35 | psi (242 kPa) | |
| Resistance | A31 J1-2 to J4-10 / J1-1 to J4-11 continuity | 270 | ohms |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | soft water/E.G./DCA mixture | Installation review checklist item: cooling system must be filled with soft water/E.G./DCA mixture. | |||
| Coolant | 50/50 mix of water and antifreeze | Balanced coolant mixture of water, antifreeze and coolant additives | Drain and replace the mixture every 6 months or after 500 hours of operation. Do not add cold coolant to a hot engine; allow engine to cool below 120 F (50 C) before adding coolant. | ||
| Engine oil | Refer to Cummins engine Operation and Maintenance Manual for lubricating oil classification | Gensets are shipped with oil added. | |||
| Fuel | Diesel | Do not use zinc coated or copper fuel lines with diesel fuel. | |||
| Fuel | diesel | Do not use zinc coated or copper fuel lines with diesel fuel. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode; generator build-up is inhibited and engine governed at 800 RPM. | Warning | Remove ground from the engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Pull the button out; move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can only be reset at the PCC front panel. |
| 1122 | Rated/Idle Trans | Info | ||
| 1123 | Shutdown After Battle Short | A shutdown fault occurred while Battle Short was enabled and transitioned from enabled to disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | Delayed Shutdown | A shutdown fault became active while the Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | Battle Sh Active | Control is in Battle Short mode (bypasses several critical fault shutdowns). | Warning | None; used for genset operation during emergencies. |
| 121 | Speed Signal Lost | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on digital display; inspect MPU wires/connector pins; check for 3.5 to 15 VAC at MPU while cranking. |
| 1311 | Customer Input #1 | Warning | Optional customer selection (e.g., Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure). Programmable: enable/disable, status/warning/shutdown, active closed or open, and display name. | |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection. | |
| 1312 | Customer Input #2 | Warning | Optional customer selection; programmable (enable/disable, status/warning/shutdown, active open/closed, display name). Default #2 thru #4 - Warning. | |
| 1317 | Customer Input #3 | Warning | Optional customer selection; programmable (default #3 - Low Fuel). | |
| 1318 | Customer Input #4 | Warning | Optional customer selection; programmable (default #4 - Rupture Basin Fault). | |
| 1334 | Crit Scaler Out Of Range | Incorrect feature or calibration was entered into control. | Shutdown | Reload correct feature/calibration file. |
| 1335 | Noncrit Scaler Out Of Range | Incorrect feature or calibration was entered into control. | Warning | Reload correct feature/calibration file. |
| 1337 | No Message | Info | ||
| 135 | Oil Pressure Sensor H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM). |
| 141 | Oil Pressure Sensor L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21. |
| 1416 | Fail To Shutdown | Genset continues to run after receiving shutdown command (Battle Short feature enabled). | Warning | Check Battle Short feature setting. |
| 1417 | Powr Down Error | Controller cannot power down because of an unknown condition. | Warning | Indicates controller cannot power down because of unknown condition. Possible drain on battery. Contact an authorized service center for service. |
| 143 | Pre-Low Oil Pres | Engine oil pressure dropped to an unacceptable level. | Warning | Indicates engine oil pressure has dropped below the warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure. |
| 1433 | Emergency Stop | Local Emergency Stop. | Shutdown | Pull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | Remote E-Stop | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | Low Coolant Temp | Engine coolant heater is not operating or not circulating coolant (coolant <=70 F [21 C]). | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply for blown fuse or disconnected cord; check for low coolant level and replenish; look for coolant leaks and repair. |
| 1438 | Fail To Crank | Engine failed to crank after the PCC received a start signal. | Shutdown | Test for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121. |
| 144 | Coolant Sensor High | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM). |
| 1442 | Weak Battery | During cranking battery voltage at or below weak battery trip point. | Warning | Recharge or replace battery; check electrolyte level and connections; check harness. |
| 1443 | Battery Failed | Dead battery - engine will not start. | Shutdown | See code 1438 instructions. |
| 1444 | KW Overload | Generator output power exceeded 105% of genset rating (3 sec at 110% of rated). | Warning | Check load and load lead connections; check CTs and CT connections. |
| 1445 | Short Circuit | Generator output current exceeded 175% of rated. | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 1446 | High AC Voltage | Phase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds. | Shutdown | Check fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure. |
| 1447 | Low AC Voltage | Phase voltage dropped below 85% of nominal for 10 seconds. | Shutdown | Check load; reconnect per reconnection diagram; check PMG/field wiring; check P8-21/P8-22 shunt connections. |
| 1448 | Under Frequency | Engine speed dropped below 90% of nominal for 10 seconds. | Shutdown | Check fuel supply, intake air supply and load; check P8 connections. |
| 1449 | Over Frequency | Frequency is 10% above base frequency for 20 seconds. | Warning | Check fuel or air delivery problem; repair P7/P8 connections. |
| 145 | Coolant Sensor Low | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts at P7-30 and P7-34. |
| 1452 | Gen CB Not Close | Genset circuit breaker (S2) failed to close when PTC enabled. | Warning | Refer to Section 5. |
| 1453 | Gen CB Not Open | Genset circuit breaker (S2) failed to open when PTC enabled. | Warning | Refer to Section 5. |
| 1459 | Reverse Power | Improper CT phasing. | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 146 | Pre-High Coolant Temp | Engine has begun to overheat (coolant temperature risen to an unacceptable level). | Warning | Reduce load; check air inlets/outlets and remove obstructions to airflow; if engine can be stopped follow code 151. |
| 1461 | Loss Of Field | Loss of field (electric) due to reverse kVAR. | Shutdown | Check field circuit. |
| 1466 | Modem Failure | Control cannot communicate with the modem. | Warning | Check for open, short circuit to ground, and loose connections to the modem. |
| 1468 | Network Error | Momentary loss of communication from the LonWorks Network. | Warning | Refer to the LonWorks Network publications. |
| 1469 | Speed/Hz Match | Measured speed and measured AC output frequency do not agree. | Shutdown | Check calibration file. |
| 1471 | Over Current | Generator output current exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 1472 | Over Current | Generator output current exceeded 110% of rated; time/current calculation initiated shutdown. | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 151 | High Coolant Temp | Engine has overheated (coolant temperature above the shutdown trip point). | Shutdown | Engine has overheated. Allow engine to cool completely, then: check coolant level and replenish and repair leaks; check for obstructions to cooling airflow; check fan belt and repair or tighten; check blower fan and circulation pumps on remote radiator installations; reset control and restart. |
| 197 | Low Coolant Level | Engine coolant level has fallen below the warning trip point. | Warning | Indicates engine coolant level has fallen below warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. If engine can be stopped, follow code 235 procedure. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If powering critical loads, wait until next shutdown period and follow 201-SHUTDOWN procedure; check oil pressure via menu prior to clearing fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. Oil pressure limits in Table 4-3. |
| 204 | OIL PRESS SENDER | The control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower, indicating the engine coolant heater is not operating or is not circulating coolant. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant; check coolant heater power supply/fuse, low coolant level, and open heater element. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215°F (102°C) standby or 207°F (97°C) prime. | Warning | Reduce load if possible; check air inlets/outlets; follow 212-SHUTDOWN procedure if engine can be stopped. |
| 212 | Oil Temp Sensor H | Indicates engine has overheated (coolant temperature above the shutdown trip point: 223°F (106°C) standby or 215°F (102°C) prime). | Warning | Check sender/connectors/wires; check resistance between P7-22 (OIL TEMP) and P7-26 (OIL TEMP COM). |
| 213 | Oil Temp Sensor L | Resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender; should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Check coolant level in radiator and coolant recovery bottle; look for leakage; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. LOW COOLANT LVL Shutdown will not occur if genset is in Idle mode (low coolant warning only). | Shutdown | Check coolant level in radiator and recovery bottle and replenish if low; check defective coolant bottle hose or radiator cap; reset control and restart after correcting problem. Will not occur in Idle mode. |
| 220 | MAG PICKUP | Mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display; isolate per troubleshooting table 4-18. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system; engine will not crank. | Shutdown | Check fuse F3 on the Engine Interface board; clean battery cable connections; recharge or replace battery. |
| 222 | OVERCRANK | Possible fuel system problem; engine stops cranking. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; check/replace dirty fuel filter and air filter; reset and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Inspect the mechanical fuel linkage and repair or replace; check the EFC for binding or damage; monitor the PCC duty cycle display and replace A32 or A38 as indicated. |
| 224 | FAIL TO SYNCHRONIZE | The generator set has not synchronized to the system bus within the allowable time frame. | Check governor system stability and adjust governing/synchronizer parameters; check for fuel system problems causing engine instability; widen synchronizing window and reduce acceptance time delay. | |
| 226 | FAIL TO CLOSE | Indicates that the paralleling breaker has been given a signal to close, but has not closed properly. | Verify charging mechanism of paralleling breaker; check the close signal to the breaker; verify auxiliary contact signals from the breaker to the control are operational. | |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace battery; clean/tighten connections; check engine DC alternator; check battery charger float level. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check voltage float level on battery charger if applicable (lower float level); check engine DC alternator and replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Recharge or replace the battery; see 230 LOW DC VOLTAGE. |
| 2327 | PTC Fault | PTC module or communication link not working properly when PTC enabled. | Warning | Check blinking light on PTC module; check B+ TB3-3 to TB3-4; check PTC status voltage TB3-5 to TB3-6 (~0.2 VDC); repower control. |
| 2329 | Low S1 Frequency | Low utility (S1) frequency. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check sensor set points. |
| 2331 | Low S1 Voltage | Low utility (S1) voltage. | Warning | Repower PCC 2100 control to clear; check S1 AC inputs at TB5; check S1 pickup/dropout set points. |
| 2335 | Excitation Fault | Loss of all three voltage sense leads or failure in excitation circuit. | Shutdown | Check field wiring (X1 and X2) for shorts or opens. |
| 2336 | Memory Error | Control memory error; data corruption of critical operating parameters. | Shutdown | Try reloading calibration file. |
| 2337 | Pwr Tran Disabled | PTC module available but PTC feature not enabled. | Warning | Use InPower to enable PTC feature; cycle power off for 5 seconds then repower. |
| 2338 | Pwr Tran Failure | PTC module trim enabled but control could not communicate with PTC module. | Warning | Check blinking light and B+ TB3-3 to TB3-4; check connections between TB2 and TB3; cycle power. |
| 2339 | Pwr Down Enabled | Power Down (sleep) function enabled but PTC module or network board is active. | Warning | None required. |
| 234 | Overspeed | Engine has exceeded normal operating speed. | Shutdown | Clear fault and restart genset; check fault threshold; monitor RPM; check electronic governor actuator. |
| 2341 | High Control Temp | Control temperature above normal (158 F [70 C]) for time greater than set time. | Warning | Check genset room air flow. |
| 2342 | Too Long In Idle (10 min.) | Genset has been in Idle mode too long. | Warning | Indicates genset has been in Idle mode too long (10 minutes maximum). |
| 235 | Low Coolant Level | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Coolant level has fallen below the shutdown trip point. Allow engine to cool completely, then check coolant level and replenish, look for possible coolant leakage points and repair; reset control and restart. |
| 2358 | High S1 Voltage | Utility (S1) voltage increased above over voltage threshold. | Warning | Measure S1 AC inputs at PTC module; check utility nominal voltage; check sensor set points. |
| 2396 | S1 CB Not Close | Utility contact (S1) failed to close with PTC enabled. | Warning | Refer to Section 5. |
| 2397 | S1 CB Not Open | Utility contact (S1) failed to open with PTC enabled. | Warning | Refer to Section 5. |
| 240 | LOW FUEL-DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ If Home button or Previous Main Menu button is pressed before pressing save symbol, changes are not saved.
⚠ Selecting this menu resets all operating parameters to default values; perform only by technically qualified personnel.
⚠ This test involves unregulated excitation; disconnect all loads.
⚠ HAZARDOUS VOLTAGE.
Tools: Voltmeter, 12 volt battery, Jumpers
⚠ Touching uninsulated high voltage parts can result in severe personal injury or death.
Tools: Wheatstone bridge, digital ohmmeter
⚠ HAZARDOUS VOLTAGE. Touching uninsulated high voltage parts inside the control and power output boxes can result in severe personal injury or death.
Tools: Wheatstone bridge or digital ohmmeter
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| CT1 - U load leads (A phase); CT2 - V load leads (B phase); CT3 - W load leads (C phase) | 6 lead gensets: generator output leads routed through CTs; 12 lead gensets: load wires routed through CTs | 12-lead sets have dual secondary CTs (3 pins); 6-lead sets have single secondary CTs (2 pins) | ||
| Fault relay K8/K9 (Dry Contact Module) | K8=Over Crank, Low Oil Pressure, High Engine Temperature, Low Coolant Level, Low Fuel Level; K9=Low Fuel Level, Rupture Basin | Contact ratings: 40A max carry/break N.O. 12V coil, 30A N.C. 12V coil, 20A N.O./10A N.C. 24V coil | ||
| TB3 (ECM alternative RUN/STOP/REMOTE connection) | TB3-1=REMOTE, TB3-2=RUN, TB3-3=STOP | Provides alternative direct connection to ECM for troubleshooting or customer connection | ||
| 110V - 120V L-N | Single phase, 2-wire | Jumper locations for single phase, 2-wire | PTC Module AC wiring (0300-5382-01, -02) | |
| 190, 200, 208, 220, 230, 240, 380, 416, 440, 460, 600 (L-L) | 3 (three phase) | 3 or 4 wires | Voltage Configuration submenu; default = 3Ph 208V 4W | |
| 190V - 240V L-L | Three phase | Jumper locations for three phase, 190V-240V L-L | Use 0300-5382-01 for 190V-240V L-L, 50/60 Hz | |
| 200, 220, 230, 240 (L-L) | 1 (single phase) | 3 wires | Voltage Configuration submenu (Governor/Regulator Setup) | |
| 200V - 240V L-L | Single phase, 3-wire | Jumper locations for single phase, 3-wire | PTC Module AC wiring | |
| 380V - 600V L-L | Three phase | Jumper locations for three phase, 380V-600V L-L | Use 0300-5382-02 for 380V-600V L-L, 50/60 Hz |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Part # | Description | Category |
|---|---|---|
| 503-1134 | Clamp, Hose | clamp |
| 155-3164-05 | Muffler, Critical | muffler |
| 800-2072 | Screw, Cap - Hex Head (M8 x 1.25 x 100) | screw |
| A028Z105 | Sender, Low Coolant | sensor |
Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.
The Cummins/Onan 6CTAA8.3-G3 engine has an oil capacity of 23.8 liters.
The Cummins/Onan 6CTAA8.3-G3 has a displacement of 8.3 liters with 6 cylinders.
The Cummins/Onan 6CTAA8.3-G3 powers 1 generator set(s), including Cummins/Onan DGFC.
A commonly reported issue on generators using the Cummins/Onan 6CTAA8.3-G3 is: Over Current.