| AC Sens Loss Low Shutdwn | AC Sensing Loss (Shutdown) | Loss of AC voltage shutdown occurs when the controller does not detect the nominal generator AC output voltage for more than 3 seconds after crank disconnect. | Shutdown | Contact an authorized distributor/dealer for service. |
| AC Sens Loss Warning | AC Sensing Loss Warning | Loss of AC voltage warning occurs when the controller does not detect the nominal generator set AC output voltage after crank disconnect. | Warning | Contact an authorized distributor/dealer for service. |
| Aux Input Shutdwn | Auxiliary Input Shutdown | Auxiliary fault input shutdown; input from a customer-supplied switch that closes when the fault is active. | Shutdown | Check the cause of the auxiliary fault. |
| Backup Pars Status | Backup Parameters Loaded | Backup parameter firmware is now loaded on the controller. | Info | |
| Battery High Warning | High Battery Voltage Warning | High battery voltage warning; the fault condition clears when the battery voltage returns within limits (above 125% of nominal 12 V). | Warning | Check the battery rating and condition. |
| Battery Low Warning | Low Battery Voltage Warning | Low battery voltage warning; the fault condition clears when the battery voltage returns within limits (at or below 100% of nominal 12 V). | Warning | Check the battery rating and condition. Charge or replace the battery. |
| Coolnt Temp High Shutdwn | High Coolant Temperature Shutdown | Occurs if the engine coolant temperature exceeds the default setting (at or above 110 °C / 230 °F). | Shutdown | Check for a low engine coolant level. Check seawater pump impeller, strainers, and seacock. |
| Coolnt Temp High Warning | High Coolant Temperature Warning | High coolant temperature warning (at or above 105 °C / 221 °F). | Warning | Check for a low engine coolant level. Check seawater system for reduced flow. Allow the generator set to cool down before checking. |
| Eng Speed High Shutdwn | Engine Over Speed Shutdown | Occurs if the engine speed exceeds the default setting (above 115% of rated speed). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Eng Speed Low Shutdwn | Engine Under Speed Shutdown | Occurs if the engine speed falls below the default setting (below 85% of rated speed). | Shutdown | Contact an authorized distributor/dealer for service. |
| Engine Start Status | Engine Started | Generator set start circuit is closed allowing the engine to crank and run. | Info | |
| Engine Stop Status | Engine Stopped | Generator set start circuit is open causing the engine to shut down. | Info | |
| Exh Temp High Shutdwn | High Exhaust Temperature Shutdown | Occurs if the engine exhaust temperature exceeds the default setting. | Shutdown | Check the wiring to the sensor. Check for a clogged seawater intake or sea strainer. Check for a damaged seawater pump impeller. Check the exhaust system. |
| Frequency High Shutdwn | Overfrequency Shutdown | Occurs when the governed frequency exceeds the default setting of the system's frequency setpoint (above 110% of nominal). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Frequency Low Shutdwn | Underfrequency Shutdown | Occurs when the governed frequency falls below the default setting of the system's frequency setpoint (below 90% of nominal). | Shutdown | Reduce the load and restart the generator set. Contact an authorized distributor/dealer if problem continues. |
| Gen Running Notice | Generator Running | Generator set has started and is running. | Info | |
| Lo Crank Vlt Warning | Low Cranking Voltage Warning | Low cranking voltage warning (battery voltage drops below 60% of nominal 12 V). | Warning | Check the battery rating and condition. Charge or replace the battery. |
| Locked Rotor Shutdwn | Locked Rotor (Overcrank) Shutdown | Overcrank (locked rotor) shutdown; engine speed below 10 rpm and oil pressure below crank oil pressure (69 kPa). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Oil Pres Low Shutdwn | Low Oil Pressure Shutdown | Occurs if a low oil pressure condition exists (at or below 117 kPa). Note: does not protect against low oil level. | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. |
| Oil Pres Low Warning | Low Oil Pressure Warning | Low engine oil pressure warning (at or below 138 kPa). | Warning | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. |
| Over Crank Shutdwn | Overcrank Shutdown | Occurs after 3 unsuccessful starting attempts. | Shutdown | Check the fuel supply and battery. Also check for loose connections. Contact an authorized distributor/dealer if problem continues. |
| Preheat | Engine Start Aid Active | Start aid is active and will energize an engine equipped preheat or ether system during the crank cycle. | Info | |
| Remote Start Status | Remote Start | Generator set start circuit was closed from a remote location allowing the engine to crank and run. | Info | |
| RunRelCoil Shutdwn | Run Relay Coil Shutdown | Overload or perceived overload on the DC circuits provided through the controller (70 Run, 71 Crank, FP/FN Flash). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Sea Pressure Low Shutdwn | Low Seawater Pressure Shutdown | Occurs after a loss of seawater pressure is detected (5 seconds after detection). | Shutdown | Check for a clogged seawater intake or sea strainer. Check for a damaged seawater pump impeller. |
| Start Delay Notice | Engine Start Delay Active | The delay for engine start is active; the unit will start cranking after the time delay times out. | Info | |
| System Ready Status | System Ready | Generator set is in the AUTO mode and available to start if the start circuit is closed. | Info | |
| Timer Error Notice | System Timer Failed | Controller timer logic has failed to time out a designated function. | Info | |
| Volts xx-xx High Shutdwn | Overvoltage Shutdown | Occurs if the voltage exceeds the default setting of the voltage regulator setpoint (exceeds 120% of the AC system voltage). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Volts xx-xx Low Shutdwn | Undervoltage Shutdown | Occurs if the voltage falls below the default setting of the voltage regulator setpoint (below 80% of the AC system voltage). | Shutdown | Reduce the load and restart the generator set. Check the F1 fuse. Contact an authorized distributor/dealer if problem continues. |