| Clearance | Air shutoff damper plunger distance A (minimum) | 18.3 | mm | 0.72 inch; replace plunger if less |
| Clearance | Coolant level below bottom of filler pipe | 13 | mm | no sight gauge |
| Gap | Air shutoff damper plunger distance A (replace if less) | 18.3 | mm | |
| Other | Air cleaner element cleaning limit | six times | | replace at least once per year regardless |
| Other | Altitude capability without derate | 1525 | m | |
| Other | Altitude capability without derate | 800 | m | |
| Other | Coolant Sample (Level 1) interval for Cat DEAC | 250 | hours | |
| Other | Cooling system cleaner amount (heavy deposits) | 0.5 | L per 3.8 to 7.6 L capacity | 1 pint per 1 to 2 US gal |
| Other | Cooling system cleaner amount (normal deposits) | 0.5 | L per 15 L capacity | 1 pint per 4 US gal |
| Other | Cooling system cleaning duration (heavy deposits) | 90 | minutes | minimum, coolant at least 82 C (180 F) |
| Other | Cooling system cleaning duration (normal deposits) | 30 | minutes | minimum, coolant at least 82 C (180 F) |
| Other | Cooling system fill rate maximum | 19 | L/min | |
| Other | Damper fluid viscosity degradation limit | 20 | percent | majority of applications |
| Other | Damper fluid viscosity degradation limit (Hasse & Wrede) | 20 | percent | majority of applications |
| Other | Damper operating hours before rebuild/replace (damper without sampling port) | 20000 | hours | |
| Other | Damper without sampling port - rebuild/replace interval | 20000 | hours | or at major overhaul |
| Other | Fast Acting Cooling System Cleaner amount | 0.5 L per 15 L | L | cooling system capacity, normal deposits |
| Other | Fast Acting Cooling System Cleaner amount | 0.5 L per 3.8 to 7.6 L | L | cooling system capacity, heavy deposits |
| Other | Hydrosolv cleaner concentration | 2 to 5 | percent | temperatures up to 93 C (200 F) |
| Other | Maximum air pressure at nozzle for cleaning purposes | 205 | kPa | 30 psi |
| Other | New drive belt tension recheck after operation | 30 | minutes | rated rpm |
| Other | Rating condition (diesel 7 L and higher) | 99 kPa (29.31 in Hg) dry barometer, 25°C (77°F) | | SAE J1995 inlet air standard |
| Other | Rating condition (diesel up to 6.6 L) | 100 kPa (29.5 in Hg) total barometric pressure, 1 kPa (.295 in Hg) vapor pressure, 25°C (77°F) | | ISO/TR14396 inlet air standard |
| Other | Rating condition (gas) | 100 kPa (29.61 in Hg) and 25°C (77°F) | | SAE J1349 standard |
| Other | Starting motor cool-down between cranking periods | 2 | minutes | |
| Other | Supplemental coolant additive concentration maximum (conventional coolant) | 6 | percent | |
| Other | Supplemental coolant additive concentration maximum (water and SCA) | 8 | percent | |
| Other | Thread lock cure time minimum before air shutoff use | 1 | hour | |
| Pressure | Air cleaner service indicator restriction (clean/replace) | 6 | kPa | 25 inches of H2O |
| Pressure | Engine air cleaner differential pressure (nominal) | 3 | kPa | normal engine operation |
| Pressure | Engine air cleaner maximum differential pressure (replace element) | 6.2 | kPa | |
| Pressure | Engine oil filter differential pressure (nominal) | 60 | kPa | normal engine operation |
| Pressure | Engine oil filter differential pressure (normal) | 60 | kPa | normal engine operation |
| Pressure | Engine oil filter differential pressure (replace elements) | 103 | kPa | oil filter elements to be replaced |
| Pressure | Engine oil pressure during cranking | 70 | kPa | cranking with fuel off |
| Pressure | Fuel filter differential pressure (nominal) | 60 | kPa | normal engine operation |
| Pressure | Fuel filter differential pressure (normal) | 60 | kPa | normal engine operation |
| Pressure | Fuel filter differential pressure (replace secondary elements) | 103 | kPa | fuel filter elements to be replaced |
| Pressure | Maximum air pressure at nozzle for cleaning | 205 | kPa | |
| Pressure | Maximum air pressure for cleaning (aftercooler core) | 205 | kPa | 30 psi; at nozzle |
| Pressure | Maximum air pressure for cleaning (radiator) | 205 | kPa | 30 psi; deadheaded nozzle |
| Pressure | Maximum air pressure for cleaning air cleaner element | 207 | kPa | 30 psi |
| Pressure | Maximum water pressure for cleaning (aftercooler core) | 275 | kPa | 40 psi |
| Pressure | Oil pressure required before starting after oil change | 70 | kPa | 10 psi; crank with fuel off, max 30 seconds |
| Pressure | Unit injector fuel injection pressure | 1240 | bar (18 000 psi) | |
| Resistance | Exciter field L1 resistance - 1400 Frame | 11 | ohms | approximation, winding at room temperature |
| Resistance | Exciter field L1 resistance - 1600 Frame | 10 | ohms | approximation, winding at room temperature |
| Resistance | Exciter field L1 resistance - 1800 Frame | 10.9 | ohms | approximation, winding at room temperature |
| Resistance | Exciter rotor L2 resistance - 1600 Frame | 0.06 | ohms | approximation, use milliohmmeter |
| Resistance | Exciter rotor L2 resistance - 1800 Frame | 0.05 | ohms | approximation, use milliohmmeter |
| Resistance | Main field (rotor) L3 resistance - 1400 Frame | 0.35 | ohms | approximation |
| Resistance | Main field (rotor) L3 resistance - 1600 Frame | 0.5 | ohms | approximation |
| Resistance | Main field (rotor) L3 resistance - 1800 Frame | 0.9 | ohms | approximation |
| Resistance | Main field (rotor) L3 resistance range | 0.35 to 1.2 | ohms | measured with multimeter |
| Resistance | Main stator L4 resistance | less than 0.1 | ohm | use milliohmmeter |
| Resistance | Pilot exciter stator L5 resistance | less than 0.1 | ohm | use milliohmmeter |
| Resistance | Resistance Temperature Detector (RTD) resistance | 100 | ohm | generator bearings / stator windings |
| Resistance | Space heaters required when insulation test result below | 3 | megohms | or humidity above 75 percent |
| Speed | Full load speed | 1800 | rpm | full load |
| Speed | Low idle (electric sets, 50 Hz units) | 80 | % of full speed | approximately |