| 1123 | Shutdown After BS | Category A fault | Shutdown | |
| 1124 | Delayed Shutdown | Category E fault | Warning | |
| 1131 | Battle Sh Active | Category E fault | Warning | |
| 121 | Speed Signal Lost | Category A fault | Shutdown | |
| 1311 | Customer Input #1 | Category E fault; optional customer selection | | The nature of the fault is an optional customer selection (example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault). Programmable via the InPower service tool. |
| 1312 | Customer Input #2 | Category E fault; optional customer selection | | The nature of the fault is an optional customer selection. Programmable via the InPower service tool (default: Warning). |
| 1313-1316 | Network Fault 1 through 4 | Category E fault | | |
| 1317 | Customer Input #3 | Category E fault; optional customer selection | | The nature of the fault is an optional customer selection. Programmable via the InPower service tool (default: Warning). |
| 1318 | Service Engine | Category B fault | Warning | Indicates that emissions criteria might not be met due to one of the following: engine running in open loop, lean mixture, rich mixture, or failed fuel system component. |
| 1334 | Crit Scaler OR | Category A fault | Shutdown | |
| 1335 | Noncrit Scaler OR | Category B fault | Warning | |
| 135 | Oil Pressure Sensor H | Category C fault | Warning | |
| 141 | Oil Pressure Sensor L | Category C fault | Warning | |
| 1416 | Failt to Shutdown | Category C fault | Warning | |
| 1417 | Pwr Down Error | Category D fault | Warning | Indicates that the control cannot power down due to some unknown condition. Possible drain on battery. Contact an authorized service center for service. |
| 143 | Pre-Low Oil Pres | Category D fault | Warning | Indicates the engine oil pressure has dropped to an unacceptable level. If the generator is powering critical loads and cannot be shut down, wait until the next shutdown period and then follow code 415 procedure. |
| 1433 | Emergency Stop | Category D fault; indicates local Emergency Stop | Shutdown | To reset the local/remote Emergency Stop button: Pull the button out. Move the O/Manual/Auto switch to O. Press the front panel Fault Acknowledge/Reset button. Select Manual or Auto, as required. |
| 1434 | Remote E-stop | Category D fault; indicates remote Emergency Stop | Shutdown | See code 1433 to reset. |
| 1435 | Low Coolant Temp | Category D fault; warning occurs when the engine coolant temperature is 70 deg F (21 deg C) or lower | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check that coolant heater is connected to power supply and for blown fuse or disconnected heater cord. Check for low coolant level and replenish; look for possible coolant leakage points and repair. |
| 1438 | Fail to Crank | Category D fault; possible fault with control, speed sensing or starting system | Shutdown | See code 441 for corrective action. |
| 144 | Coolant Sensor High | Category C fault | Warning | |
| 1442 | Weak Battery | Category D fault; during cranking the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time | Warning | See code 441 for corrective action. |
| 1443 | Battery Failed | Category D fault; dead battery - engine will not start | Shutdown | See code 441 for corrective action. |
| 1444 | kW Overload | Category B fault | Warning | |
| 1445 | Short Circuit | Category A fault | Shutdown | |
| 1446 | High AC Voltage | Category A fault | Shutdown | |
| 1447 | Low AC Voltage | Category A fault | Shutdown | |
| 1448 | Under Frequency | Category D fault; possible fuel system problem or overload condition | Shutdown | Check for dirty or plugged air filter and replace if necessary. Check operation by disconnecting load and restarting generator set. Fuel system requires adjustment or fuel delivery is inadequate - contact an authorized service center. Reset the control and restart. |
| 1449 | Over Frequency | Category A fault | Warning | |
| 145 | Coolant Sensor Low | Category C fault | Warning | |
| 1452 | Gen CB Not Close | Category A fault | Warning | |
| 1453 | Gen CB Not Open | Category A fault | Warning | |
| 1459 | Reverse Power | Category A fault | Shutdown | |
| 146 | Pre-High Coolant Temp | Category D fault | Warning | Indicates the engine has begun to overheat (coolant temperature has risen to an unacceptable level). Reduce the load if possible by turning off non-critical loads. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow code 151 procedure. |
| 1461 | Loss of Field | Category A fault | Shutdown | |
| 1466 | Modem Failure | Category C fault | Warning | |
| 1468 | Network Error | Category C fault | Warning | |
| 1469 | Speed/Hz Match | Category A fault | Shutdown | |
| 1471 | Over Current | Category B fault | Warning | |
| 1472 | Over Current | Category A fault | Shutdown | |
| 151 | High Coolant Temp | Category D fault | Shutdown | Indicates the engine has overheated (coolant temperature has risen above the shutdown trip point). Allow the engine to cool completely. Check the coolant level and replenish if low; look for coolant leaks. Check for obstructions to cooling airflow. Check fan belt and repair or tighten if necessary. Check the blower fan and circulation pumps on remote radiator installations. Reset the control and restart. |
| 197 | Low Coolant Level | Category D fault | Warning | Indicates engine coolant level has fallen to an unacceptable level. If the generator is powering critical loads and cannot be shut down, wait until the next shutdown period, and then follow 235 Coolant Level Alarm procedure. |
| 2323-2326 | Network Fault 5 through 8 | Category E fault | | |
| 2327 | PTC Fault | Category B fault | Warning | |
| 2329 | Low S1 Frequency | Category E fault | Warning | |
| 2331 | Low S1 Voltage | Category E fault | Warning | |
| 2335 | Excitation Fault | Category A fault | Shutdown | |
| 2336 | Memory Error | Category A fault | Shutdown | |
| 2337 | Pwr Tran Disabled | Category C fault | Warning | |
| 2338 | Pwr Tran Failure | Category C fault | Warning | |
| 2339 | Pwr Down Enabled | Category E fault | Warning | |
| 234 | Overspeed | Category A fault | Shutdown | |
| 2341 | High Control Temp | Category B fault | Warning | |
| 2342 | Too Long in Idle | Category E fault; generator set has been in Idle mode too long (10 minutes maximum) | Warning | Indicates the generator set has been in Idle mode too long (10 minutes maximum). |
| 235 | Low Coolant Level | Category D fault | Shutdown | Indicates engine coolant level has fallen below the alarm trip point. Allow the engine to cool down completely. Check the coolant level sight glass at LTA top tank and replenish if low. Look for possible coolant leakage points and repair if necessary. Reset the control and restart. |
| 2358 | High S1 Voltage | Category E fault | Warning | |
| 2396 | S1 CB Not Close | Category E fault | Warning | |
| 2397 | S1 CB Not Open | Category E fault | Warning | |
| 2966 | PTC Timeout | Category C fault | Warning | |
| 2967 | Governor Fault | Category C fault | Warning | |
| 2968 | AVR Fault | Category C fault | Warning | |
| 2969 | LON Failure | Category C fault | Warning | |
| 2972 | Field Overload | Category A fault | Shutdown | |
| 359 | Fail To Start | Category D fault | Shutdown | Indicates a possible fuel system problem (engine cranks but fails to start). Open any closed fuel shutoff valve. Check for dirty or plugged air filter and replace if necessary. Fuel delivery to the set is inadequate - contact an authorized service center. Reset the control and restart. |
| 415 | Low Oil Pressure | Category D fault | Shutdown | Indicates engine oil pressure has dropped below the shutdown trip point. Check oil level, lines and filters. If the oil system is OK but oil level is low, replenish. Reset the control and restart. |
| 441 | Low Bat Voltage | Category D fault | Warning | Indicates battery voltage supply to the control is approaching a low level. Discharged or defective battery - check the battery charger fuse and recharge or replace the battery. Clean the battery cable terminals and tighten all connections. Check battery charge voltage float level if applicable (raise float level). |
| 442 | High Bat Voltage | Category D fault | Warning | Indicates battery voltage supply to the control is approaching a high level at which damage to the control can occur. Check the float level on the battery charger if applicable (lower float level). |