Home›Engines›Kohler CH740 (14 kW models); CH1000 (20 kW models)

Kohler CH740 (14 kW models); CH1000 (20 kW models) Engine

The Kohler CH740 (14 kW models); CH1000 (20 kW models) is a 2-cylinder engine rated at 3600 rpm. It powers generator sets from Kohler, including the 14RCA, 20RCA and RCA.

Also known as: Kohler CH740 (14 kW models); CH1000 (20 kW models)

2
Cylinders
3600 rpm
Rated speed

Engine specifications

Cylinders2
Rated speed3600 rpm

Common problems

15
  • The generator shuts down due to a main power overload. Main Power Overload Shutdown
    Fix: Check the circuit breaker and ensure it is not tripped. If necessary, replace the circuit breaker.
  • Paralleling issues occur, such as incorrect synchronization or failure to maintain parallel operation. Faults Related to Paralleling
    Fix: Verify that all paralleling settings are correct in the controller parameters. Check the paralleling cables and connections for any faults.
  • Low battery voltage warnings are displayed on the controller display. Battery Low Warnings
    Fix: Check the battery connections and ensure they are secure. Replace the battery if it is low on charge.
  • This generator has absorbed more than 25% reactive power (magnetic excitation current) for 20 seconds. LossOfField
    Cause: Generator voltage on this generator is not calibrated correctly. Generator voltage on other generator is not calibrated correctly. Bus voltage on this generator is not calibrated correctly. Bus voltage on the other generator is not calibrated correctly.
  • This generator does not know if the metering is connected or the orientation of the connection. This means that the generators can’t share load accurately until this information is known. MeterUnknown
    Cause: System commissioning and startup not yet complete. See the APM instructions.
  • The two generators that are intended to be paralleled have incompatible model numbers. CfgModelNum
    Cause: Incorrect configuration of one of the generators. Different generator types. The paralleled generator sets must be the same kW model. (i.e. two 14 kW or two 20 kWor 26 kW models).
  • The system voltage of the two generators intended to be paralleled is not the same. CfgSysVolt
    Cause: One of the two generators is incorrectly configured. Intermittent connections on RBUS network wiring.
  • The primary controller has lost communication with the secondary controller. (A secondary controller was detected, then communication was lost.) LossOfComm2
    Cause: RBUS disconnected, secondary controller battery disconnected, updating firmware in secondary controller, or intermittent RBUS connections.
  • The power metering on this controller gives a signal that is not consistent with the system configuration. Reversing the power direction does not resolve the problem. ErraticSig
    Cause: Bad wiring to the CT. Too much tension on wires from the CT to the controller.
  • The generator set cranks but does not start, starts hard, lacks power, or operates erratically.
    Cause: Air cleaner clogged
    Fix: Clean and/or replace the air cleaner.
  • The generator has verified that the metering is connected correctly and that the direction is consistent with expected power direction. MeteringOk
    Cause: Status message indicates that the CT is connected to the generator correctly.
  • The generator has been attempting to synchronize for over 2 minutes without success. SyncFailure
    Cause: Generator is hunting. Advanced speed control settings need adjustment. Load is changing frequently to disturb the online generator.
  • The generator has applied load (using the other generator) and has observed no current on the power sensing inputs. NoCurrent
    Cause: The CT is not connected to the controller. The output leads from the generator do not go through the CT in the correct direction. See the APM instructions.
  • The controller displays fault messages TP-7092
  • The bus is measured to be live when no generators are connected to it (both contactors open). BusLiveDead
    Cause: Bus metering V9A and V9B connections to V9 of paralleling protection harness are connected incorrectly.

Compiled from service & troubleshooting documentation across every generator set that uses the Kohler CH740 (14 kW models); CH1000 (20 kW models).

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterReplace air cleaner element at intervals specified in the service schedule. Replace more often under extremely dusty or dirty conditions.—100 hr
Fuel filterChange fuel flexible lines and connections quarterly. Check main tank supply level weekly. Change fuel piping yearly.—52 hr
Oil filterReplace oil filter yearly or 200 hours.—200 hr
BatteryCheck the electrolyte level of batteries with filler caps monthly. Remove filler caps and verify that electrolyte level reaches bottom of filler holes. Refill as necessary with distilled water.—30 hr
BeltCheck control and power wiring connections yearly. Check remote control system monthly if equipped. Check visible wear or damage quarterly.—12 hr
CoolantCheck air ducts, louvers yearly. Check exhaust system leakage weekly. Check insulation, fire hazards yearly.—52 hr
OilChange oil every 8 hours of engine operation or yearly. Replace filter yearly or 200 hours.—100 hr
Spark plug—

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Oil levelCheck8 hrEvery 8 hours of engine operation
Oil level (14 kW)Check8 hrEvery 8 hours of engine operation
Oil level (20 kW)Check8 hrEvery 8 hours of operation
Oil level, 14 kW modelsCheck8 hrEvery 8 hours of engine operation
Oil level, 18/20 kW modelsCheck8 hrEvery 8 hours of engine operation
Oil level, 20 kW modelsCheck8 hr
Oil level (26 kW)Check24 hrEvery 24 hours of operation
Oil level, 26 kW modelsCheck24 hr
Change oilChange100 hrYearly or 100 hours
Change oil (14 kW models)Change100 hr12 moYearly or 100 hours
Change oil (14 kW)Change100 hr12 moYearly or 100 hours
Oil coolerClean100 hr20 kW models; Yearly or 100 hours
Oil cooler (20/26 kW)Clean100 hr12 moYearly or 100 hours; inspect and clean
Replace filter (20/26 kW)Replace100 hr12 moYearly or 100 hours
Air cleaner serviceClean300 hr12 moYearly or hours shown
Change oil (20 kW models)Change150 hr12 moYearly or 150 hours
Oil change (20/26 kW)Change150 hr12 moYearly or 150 hours
Oil cooler (20RCA/RCAL only)Clean150 hr12 moYearly or 150 hours; inspect and clean, must be kept free of debris
Replace oil filter (20 kW models)Replace150 hr12 moYearly or 150 hours
Replace filter (oil)Replace200 hr14 kW: Yearly or 200 hours; 20 kW: Yearly or 100 hours
Replace oil filter (14 kW models)Replace200 hr12 moYearly or 200 hours
Replace oil filter (14 kW)Replace200 hr12 moYearly or 200 hours
Air cleaner serviceReplace300 hr12 moYearly or hours shown; service more frequently under dusty/dirty conditions
Brushes and collector ringInspect300 hr12 moYearly or 300 hours; authorized distributor/dealer only
Optional 300 hour extended life oil change kit (26 kW)Change300 hr24 mo2 years or 300 hours
Spark plugsReplace300 hr14 kW: 300; 20 kW: 150 and 300 hours
Spark plugs (14 kW)Replace300 hrHours shown
Spark plugs (20/26 kW)Replace300 hr150/300 hours shown
Crankcase breather hoseCheck500 hrYearly or 500 hours
Crankcase breather hoseInspect500 hr12 moYearly or 500 hours
Crankcase breather hoseReplace500 hr12 moYearly or 500 hours
Replace stepper motor coupling and bushingReplace500 hrAuthorized distributor/dealer only
Wire-cable insulation conditionInspect500 hr36 mo3 years or 500 hours
Wire-cable insulation conditionTest500 hr36 mo3 years or 500 hours
AC electrical system visible wear or damageInspect3 moQuarterly
Air ducts, louversClean12 moYearly; visually inspect and clean
Battery and rack corrosionClean12 moYearly
Battery charger operation, charge rateCheck1 moMonthly
Battery electrolyte level and specific gravityCheck12 moYearly; not necessary for maintenance-free batteries
Battery terminals and bootsClean12 moYearly

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapSpark plug gap0.76mm (0.030 in.)
OtherBattery wrap length1067 (42)mm (in.)
OtherBattery wrap length864 (34)mm (in.)
OtherEngine cooldown time delay5minutes
OtherEngine start crank cycle3 attempts, 15 sec crank / 15 sec off
OtherGoverned frequency high shutdown110% of frequency setpoint for >10 sec10 sec inhibit after engine start
OtherGoverned frequency low shutdown90% of frequency setpoint for >10 sec, or 1 Hz below setpoint for >60 sec10 sec inhibit after engine start
OtherHeater wrap rating50Watts
OtherHeater wrap rating65Watts
OtherPlug cord length75 (3)mm (in.)
OtherPower cord length1677 (66)mm (in.)
OtherPower cord length1830 (72)mm (in.)
OtherPower cord length483 (19)mm (in.)
OtherSpecific gravity, battery fully charged1.260electrolyte temperature 80 F (26.7 C)
OtherSpecific gravity, battery needs charging (below)1.215electrolyte temperature 80 F (26.7 C)
PressureEngine oil pressure172-241kPa (25-35 psi)
PressureFuel pressure required, LPG1.7-2.7kPa (7-11 in. H2O)
PressureFuel pressure required, Natural Gas0.9-2.7kPa (3.5-11 in. H2O)
PressureLPG fuel supply1.7-2.7kPa
PressureNatural gas fuel supply0.9-2.7kPa
ResistanceResistance through brushes0.1-0.2ohmswithout meter lead resistance
ResistanceResistance through the brushes0.1-0.2ohmswithout meter lead resistance
ResistanceRotor insulation (megohmmeter)500kOhms minimum500 VDC applied
ResistanceRotor resistance, cold (14 kW)5.2ohmscold
ResistanceRotor resistance, cold (14RCA/L 2F5/2G5)5.2ohmscold
ResistanceRotor resistance, cold (20 kW)5.6ohmscold
ResistanceRotor resistance, cold (20RCA/L 2F7/2G7)5.6ohmscold
ResistanceRotor resistance, cold (26 kW)6.4ohmscold
ResistanceStator insulation (megohmmeter)500kOhms minimum500 VDC applied
ResistanceStepper motor coil resistance (per half coil)38.5ohms
ResistanceStepper motor coil resistance per half coil38.5ohms
ResistanceTemperature sensor (OTS) resistance at 100 C (212 F)180-200ohms100 C (212 F)
ResistanceTemperature sensor (OTS) resistance at 100C (212F)180-200ohms100 C (212 F)
ResistanceTemperature sensor (OTS) resistance at 30 C (86 F)2100-2400ohms30 C (86 F)
ResistanceTemperature sensor (OTS) resistance at 30C (86F)2100-2400ohms30 C (86 F)
SpeedCrank disconnect speed750RPM (12.5 Hz)
SpeedEngine crank disconnect speed750RPM
SpeedEngine overspeed shutdown115% of normal running speed for >0.3 sec
SpeedEngine run speed (60 Hz)3600RPM
SpeedEngine run speed 60 Hz / 50 Hz3600 / 3000RPM
SpeedEngine speed high shutdown115% of normal running speed for >0.3 sec
SpeedEngine speed low shutdown85% of normal running speed for >3 sec
SpeedEngine underspeed shutdown85% of normal running speed for >3 sec
SpeedOverspeed shutdown test115% of rated speed (69 Hz @60 Hz, 58 Hz @50 Hz)
TemperatureCarburetor heater thermostat OFF16 ± 3C (60 ± 5F)
TemperatureCarburetor heater thermostat ON4 ± 4C (40 ± 7F)
TemperatureController operating temperature-30 to 70C
TemperatureController storage temperature-40 to 85C
TemperatureHigh lube oil temperature shutdown325F (163 C)
TemperatureHigh lube oil temperature warning300F (149 C)
TemperatureThermostat off temperature27C (80 F)
TemperatureThermostat on temperature16C (60 F)
TorqueAlternator adapter bolts69Nm (51 ft. lb.)
TorqueAlternator adapter bolts (14/20 kW)69Nm (51 ft. lb.)
TorqueAlternator adapter bolts (26 kW)69Nm (51 ft. lb.)
TorqueAlternator mounting bolts14.9Nm (11 ft. lb.)
TorqueAlternator mounting bolts (14/20 kW)14.9Nm (11 ft. lb.)
TorqueAlternator mounting bolts (26 kW)14.9Nm (11 ft. lb.)
TorqueAlternator thrubolt85Nm (63 ft. lb.)
TorqueAlternator thrubolt (14/20 kW)85Nm (63 ft. lb.)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilService class SJ or higher1.8 L (1.9 qt.)Oil capacity 14 kW
Engine oil10W-30 syntheticService class SJ or higherAdd 5W-30 or 10W-30 synthetic oil when oil level is low
Engine oil10W-50 extended-life synthetic1.9 L (qt.)Premium oil option, 26 kW models, requires fewer oil changes
Engine oil5W-30 or 10W-30API Service Class SG, SH, or SJ synthetic oil1.8 L14 kW models; capacity 1.8 L (1.9 qt.)
Engine oil5W-30 or 10W-30 API Service Class SG, SH, or SJ syntheticAPI SG/SH/SJ1.8 L (qt.)14 kW models
Engine oil5W-30 syntheticService class SJ or higherRefer to Oil Matrix chart for oil recommendation based on air temperature
Engine oilKOHLER PRO 10W-50Service class SJ or higherAll season Kohler PRO 10W-50 is ideal; extends oil/filter change to 300 hours (2 years) with KOHLER PRO extended life oil filter
Engine oilSynthetic, API Service Class SG or higherAPI SG or higherCheck oil level at or near, not over, full mark on dipstick before operation
FuelLP gas or natural gasMinimum fuel supply pressure NG: 1.2-2.7 kPa (5-11 in. H2O); LP: 1.7-2.7 kPa (7-11 in. H2O)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

62
CodeNameMeaningSeverityAction
AC Sens LossAC Sensing LossATS sensing lost. In Auto mode, generator output AC sensing is lost. Detection begins 10 seconds after start.WarningContact an authorized distributor/dealer for service
AC Sens Loss ShutdownLoss of AC sensing shutdownLess than 5% of rated voltage measured on Phase A for 3 seconds in AUTOShutdownCheck loose wiring and connections; check all AC leads; troubleshoot alternator
AC Sens Loss ShutdwnLoss of AC sensing shutdownController shut down the generator because there was less than 5% of rated voltage measured on Phase A for 3 seconds, only in AUTO.ShutdownCheck for loose wiring and connections. Check all AC leads. Troubleshoot alternator.
AC Sens Loss WarningLoss of AC sensing warningLess than 5% of rated voltage on Phase A for 1 second, 10 seconds after crank disconnectWarningCheck loose wiring and connections; check all AC leads; troubleshoot alternator
ATS ComErrorATS Communication ErrorATS communication error; interface connection lostWarningCheck communication wiring between transfer switch interface board and generator set.
ATS ComError WarningATS communication errorController lost communication with the RXT ATSWarningCheck connection to ATS module
ATS PhaseRotATS PhaseRotATS phase rotation mismatch; ATS will not transferWarningCorrect the ATS connection. Refer to the ATS Installation manual, wiring diagrams, and labels on the transfer switch.
Accy PwrOver WarningAccy PwrOver WarningAn over current fault (short circuit) on the accessory controller power output.WarningContact an authorized distributor/dealer for service
AccyPwrOver WarningAccessory Power OverloadOvercurrent fault (short circuit) on the accessory controller power outputWarningCheck wiring to RBUS accessories; troubleshoot RBUS accessories
Advanced DiagnosticAdvanced DiagnosticShutdown during the reduced speed portion of an exercise. Event history shows Advanced Diagnostic Active. Engine restarts, runs at full speed for 2 minutes, and stops. Controller returns to AUTO mode.ShutdownIf the generator set does not restart and return to AUTO, check for other faults that prevent generator set operation.
Aux InputAuxiliary InputOptional customer-connected input (from PIM) is closedShutdownCheck customer-supplied equipment.
Aux Input ShutdwnAuxiliary input shutdownDigital input for a custom shutdown (AuxiliaryInputShutdown - PIM) was activated (low).ShutdownCheck customer equipment connected to the PIM module.
Batt Chg FltBattery Charger FaultInput to PIM from an external battery charger (not the built-in battery charger).WarningCheck external battery charger.
Battery CRLow WarningBattery cranking low warningBattery voltage dropped to 11 VDC or less for 30 seconds or more.WarningCheck engine starting battery; check battery charger DC output from RDC2
Battery CrLo WarningLow Cranking Battery Voltage WarningEngine starting battery voltage falls below 11 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when battery voltage returns to acceptable level.WarningCheck the battery rating and condition. Check the battery charger operation. Charge or replace the battery.
Battery HighBattery HighEngine starting battery voltage rises above 16 VDC for more than 10 seconds (inhibited during crank)WarningCheck battery rating/condition and charger operation
Battery High WarningBattery high warningBattery voltage above the high warning setting for 10 seconds or more.WarningCheck engine starting battery.
Battery Low WarningBattery low warningController measured battery voltage below low warning setting for 90 seconds or moreWarningCheck engine starting battery; check battery charger DC output from RDC2
Battery Voltage HighBattery Voltage HighEngine starting battery voltage rises above 16 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when voltage returns to acceptable level.WarningCheck the battery rating and condition. Check the battery charger operation.
Battery Voltage LowBattery Voltage LowEngine starting battery voltage falls below 12.5 VDC for more than 90 seconds when engine not running. Not operative during crank cycle. Clears when voltage returns to acceptable level.WarningCheck the battery rating and condition. Check the battery charger operation. Charge or replace the battery.
Chk DateTime WarningCheck Date and Time WarningDC power to controller interrupted and date/time may not be correctWarningVerify time and date settings
Default Pars WarningDefault Parameters WarningController has been loaded with default parametersWarningConfigure settings as required for desired operation
Emerg Stop ShutdwnEmergency stop shutdownOptional emergency stop button pressed or emergency stop leads ESS and/or ESN not connectedShutdownReset the emergency stop button and clear the fault; check ESS and ESN connections; if no E-stop, connect ESS and ESN together.
Eng Speed HighEng Speed HighEngine speed exceeds 115% of normal running speed for more than 0.3 secondsShutdownContact an authorized distributor/dealer for service
Eng Speed LowEng Speed LowEngine speed drops below 85% of normal running speed for more than 3 secondsShutdownReduce the load; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists
Engine M/N Invalid ShutdwnEngine model number invalid shutdownGenerator model number has not been entered.ShutdownEnter the generator set model number from the RDC2 keypad, or use SiteTech to select the genset model number.
Engine Speed HighEngine Speed HighEngine speed exceeds 115% of the normal running speed for more than 0.3 seconds.ShutdownContact an authorized dealer for service.
Engine Speed High ShutdwnEngine speed high shutdownEngine speed, calculated from AC frequency, was above the high speed setting for 0.3 seconds or more.ShutdownTroubleshoot engine operation per the engine service manual.
Engine Speed LowEngine Speed LowEngine speed drops below 85% of the normal running speed for more than 3 seconds.ShutdownReduce the load. Check enclosure thermostat and reset if tripped. Contact an authorized dealer for service.
Engine Speed Low ShutdwnEngine speed low shutdownEngine speed below the low speed setting for 3 seconds or more after crank disconnect; enclosure thermostat may have tripped.ShutdownTroubleshoot engine; check enclosure thermostat and reset if tripped
Exer Not SchExercise Not ScheduledNo exercise is scheduled on the controller.WarningSet the exerciser per Section 3.6
Frequency HighFrequency HighGoverned frequency exceeds 110% of the system's frequency setpoint for more than 10 seconds. Active 10 seconds after engine start.ShutdownContact an authorized distributor/dealer for service
Frequency High ShutdwnFrequency high shutdownFrequency on Phase A exceeded high frequency setting for 10 secondsShutdownTroubleshoot engine operation per the engine service manual.
Frequency LowFrequency LowGoverned frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds. Active 10 seconds after engine start.ShutdownReduce the load and restart; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists
Frequency Low ShutdwnFrequency low shutdownFrequency on Phase A was less than the low limit for 10 seconds, or 10 Hz or more less than rated for 60 seconds or more.ShutdownTroubleshoot engine; check and reset enclosure thermostat
Fuel Leak ShutdwnFuel Leak ShutdownDigital input for Fuel Tank Leak Shutdown (PIM) activated (low)ShutdownCheck customer equipment connected to the PIM module
Fuel Level Low ShutdwnFuel Level Low ShutdownDigital input for Low Fuel Level Shutdown (PIM) activated (low)ShutdownCheck customer equipment connected to the PIM module
GenBrkerOpen WarningGenerator Circuit Breaker OpenVoltage at generator set but none measured on emergency side of ATS (RXT required)WarningCheck line circuit breaker; correct short circuits or overloading before resetting
Ground Fault WarningGround Fault WarningDigital input for Ground Fault Warning (PIM) active (low)WarningCheck customer equipment connected to the PIM module
High Lube Oil Temperature ShutdownHigh lube oil temperature shutdownOil temperature higher than 325 F (163 C).ShutdownSee Overheats troubleshooting; check cooling
High Lube Oil Temperature WarningHigh lube oil temperature warningOil temperature higher than 300 F (149 C).WarningSee Overheats troubleshooting
Lo Crank VltLow Cranking VoltageBattery voltage dropped below 3.5 VDC during engine cranking.WarningCharge or replace the battery.
Lo Crank Vlt WarningLow cranking voltage warningDuring cranking, battery voltage measured less than 60% (7.2V or 14.4V) for 6 seconds or more.WarningCheck cranking battery.
Locked RotorLocked RotorNo engine rotation sensed during cranking; shuts down 3 seconds after detectionShutdownCheck the battery. Check for loose connections. Contact an authorized dealer for service.
Locked Rotor ShutdwnLocked rotor shutdownNo rotation of the engine or alternator was detected for 3 seconds or more during cranking.ShutdownCheck cranking circuit; troubleshoot engine and alternator; check aux winding circuit breaker
Low Oil Level or Oil PressureLow Oil Level or Oil PressureOil level switch on the 26 kW indicates low oil level. LOP switch indicates low oil pressure for more than 5 seconds. Active 30 seconds after crank disconnect. Does not protect against low oil level.ShutdownCheck for leaks in the lubrication system. Check the oil level and add oil if low. Check the oil level or oil pressure switch and wiring. If fault persists, do not run the generator set; contact an authorized dealer.
MainPwrOverLMainPwrOverLMain power overload; an over current fault on the controller output (short circuit).ShutdownContact an authorized distributor/dealer for service
MainPwrOverL ShutdwnMain power overload shutdownInternal current limit circuit tripped, indicating an overcurrent condition on the DC power supply circuit.ShutdownCheck crank, run, and flash relay circuits for short circuits.
Not In Auto WarningNot in auto warningThe RDC2 controller is not in AUTO; generator will not start from an ATS or remote device.WarningPress the Auto button to ensure automatic system operation.
Not in AutoNot in AutoThe generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored.WarningPress AUTO to place the generator set in Automatic mode, when appropriate.
Oil Press LowOil Pressure LowThe LOP switch indicates low oil pressure for more than 5 seconds. Function becomes active 30 seconds after crank disconnect (30 second inhibit). The low oil pressure shutdown does not protect against low oil level.ShutdownCheck for leaks in the lubrication system. Check the oil level and add oil if the level is low. Check the oil pressure switch and wiring. If the fault persists, do not run the generator set. Contact an authorized dealer for service.
Oil Pressure Low ShutdwnOil Pressure Low ShutdownThe low oil pressure switch was closed for 5 seconds or more; inhibited until 30 seconds after crank disconnect.ShutdownCheck for oil leaks; check oil level and add oil; check oil pressure sensor
Oil Pressure OpenCR WarningOil pressure open circuit warningOil pressure switch closure has not been detected after shutdown.WarningCheck the oil pressure switch connection. Test the LOP switch.
Over CrankOver CrankThree unsuccessful starting attempts.ShutdownCheck the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized dealer for service.
Over Crank ShutdwnOvercrank shutdownThe engine did not start during the crank cycle (15 second time delay).ShutdownCheck the alternator, fuel supply, cranking circuit, cranking battery; troubleshoot engine.
RBUS ComError WarningRBUS communication error warningThe controller has lost communication with an RBUS device that had previously been communicating properly.WarningCheck connection to the RBUS device.
Spd Sens FltSpeed Sensor FaultEngine speed sensor has failed or engine stalled.ShutdownContact an authorized distributor/dealer for service
Spd Sens Flt ShutdwnSpeed sensor fault shutdownThe speed signal was lost; also occurs if the engine stalls.ShutdownCheck leads 55, 66, F+, and F- between the alternator and the controller; check the engine.
Volts L1-L2 (AB) High ShutdwnVolts L1-L2 High ShutdownVoltage from Phase A to Phase B exceeded the high limit for longer than the 2 second delay setting.ShutdownTroubleshoot alternator.
Volts L1-L2 (AB) Low ShutdwnVolts L1-L2 Low ShutdownVoltage from Phase A to Phase B was greater than 5% of rated but less than the low voltage setting for longer than the 10 second delay; enclosure thermostat may have tripped.ShutdownTroubleshoot alternator; check and reset enclosure thermostat
Volts L1-L2 HighVolts L1-L2 HighOutput voltage exceeds 120% of the system nominal voltage for more than 2 seconds.ShutdownContact an authorized distributor/dealer for service
Volts L1-L2 LowVolts L1-L2 LowOutput voltage falls below 80% of the nominal system voltage for more than 10 seconds.ShutdownReduce the load and restart; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
RDC2 Voltage Calibration Using SiteTech adjustment

Tools: digital voltmeter, personal computer, SiteTech software

  1. Connect PC to controller via USB
  2. With generator off, connect multimeter across L1/L2 (AC volts)
  3. Start generator set
  4. Compare voltmeter reading to controller display
  5. Calculate new Genset Calibration Factor Voltage using (Vmeter / Vcontrol) x Fold = Fnew
  6. Enter new value into SiteTech and click Apply Changes
  7. Verify voltmeter matches controller display
  8. Repeat for L2-L3 and L3-L1 if three-phase
  9. Press OFF to stop generator set
RDC2 Voltage Calibration Using the Controller Keypad adjustment

Tools: digital voltmeter

  1. With generator off, connect digital multimeter across L1 and L2, set to AC volts
  2. Start generator set with RUN button
  3. Navigate to Generator Metering menu, press Select; Volts L1-L2 displayed
  4. Press Select; voltage number flashes
  5. Use up/down arrows to match voltmeter reading
  6. Press Select to confirm
  7. Step to Return screen
  8. Press OFF to stop generator set
VSC Current (Load) Calibration Using the Controller Keypad adjustment

Tools: clamp-on DC current probe or DC current meter

  1. Connect DC current probe/clamp meter to measure generator current
  2. Start generator with RUN button
  3. Adjust system voltage to obtain rated current output with battery bank attached (or use load bank)
  4. Trip output breaker
  5. Navigate to Generator Metering menu, select Generator Load
  6. Press and hold Select for No-Load Calibration; verify breaker open, confirm Yes
  7. Close output breaker; verify rated output current, confirm Yes
  8. Verify displayed load is correct; recalibrate if necessary
  9. Press OFF to stop generator set
Voltage Calibration Using RDC2 Keypad adjustment

Tools: Digital voltmeter

  1. With set off, connect DVM to measure output voltage L1-L2 (AC volts).
  2. Press RUN to start generator set.
  3. Press Select, navigate to Generator Metering menu.
  4. Press Select to display Volts L1-L2; compare with voltmeter.
  5. If incorrect, press Select (flashes), adjust with arrows, press Select to save.
  6. Wait 30-60 seconds for voltmeter reading to stabilize.
  7. For three-phase, repeat for L2-L3 and L3-L1.
  8. Press OFF to stop generator set.
Governor System Operation Test diagnostic

⚠ Hazardous voltage. Moving parts.

Tools: Ohmmeter

  1. Verify carburetor throttle linkage is connected to stepper motor.
  2. Check for broken or loose wiring or plug connections.
  3. Check stepper motor operation at startup (open then closed position).
  4. Open circuit breaker, disconnect starting battery, shut off fuel supply.
  5. Disconnect stepper motor plug P6 to access terminals.
  6. Check coil resistance across pins 2-3 and pins 1-4.
  7. Inspect linkage and bushings; replace as necessary.
  8. Disconnect linkage; verify free full range of motion.
Resetting the Controller After a Fault Shutdown diagnostic

⚠ Always identify and correct cause of fault before resetting

  1. Press Select to go to Overview menu while fault message is displayed
  2. Press Select again to show active fault message
  3. Press Select; 'Confirm Clear Fault: NO' displayed
  4. Press UP arrow; 'Confirm Clear Fault: YES' displayed
  5. Press Select to clear fault
  6. Press Select to return to overview menu; controller changes to OFF mode
  7. Press AUTO to place generator set in automatic mode
Separate Excitation diagnostic

⚠ Hazardous voltage. Moving parts.

Tools: DC ammeter, 10-amp fuse, 12-volt automotive battery

  1. Disconnect black FN and FP leads at brush holder terminals.
  2. Connect DC ammeter, 10-amp fuse, and 12-volt battery to FP/FN brush leads.
  3. Start engine; verify ammeter reading remains stable.
  4. Check AC output across stator leads; compare to specifications.
  5. If rotor and stator good, check wiring, fuses, controller settings.
Separate Excitation Procedure diagnostic

⚠ Hazardous voltage. Operate the generator set only when all guards and electrical enclosures are in place.

Tools: DC ammeter, 10-amp fuse, 12-volt automotive battery

  1. Disconnect the black FN and FP leads from the alternator at the brush holder terminals.
  2. Connect a DC ammeter, 10-amp fuse, and a 12-volt automotive battery to the FP and FN brush leads.
  3. Note and record the ammeter reading.
  4. Start the engine and check that the ammeter reading remains stable.
  5. An increasing reading indicates a shorted rotor; a decreasing reading suggests a running open.
  6. Check for AC output across the stator leads and compare to Section 1 specifications.
  7. If rotor and stator are good, check the wiring, fuses, and controller settings and connections.
Test Low Oil Pressure (LOP) Switch diagnostic

Tools: Ohmmeter or continuity tester, Oil pressure gauge

  1. Press OFF to stop engine.
  2. Disconnect lead 13 from the switch.
  3. Use ohmmeter/continuity tester to verify switch is closed (grounded).
  4. Start engine and verify switch opens after a few seconds.
  5. If not operating, remove LOP switch, install oil pressure gauge.
  6. Start and run generator set.
  7. Verify oil pressure within specified range before replacing LOP switch.
12-Lead Generator Reconnection Procedure installation

⚠ Hazardous voltage. Disconnect all power sources before opening the enclosure.

Tools: digital multimeter, voltmeter

  1. Press the OFF button on the RDC2 controller.
  2. Disconnect the engine starting battery, negative lead first.
  3. Disconnect utility power to the generator set.
  4. Remove the circuit breaker cover and the controller panel to access the alternator leads and CTs.
  5. Replace the circuit breaker with the correct part for the new voltage rating.
  6. Select the desired voltage connection and connect the leads per the diagram.
  7. Reconnect the engine starting battery, negative lead last.
  8. Check system voltage, frequency, and phase settings and change them if necessary.
  9. Connect a digital multimeter (DVM) to the generator set output.
  10. Press RUN to start the generator set.
  11. Use a voltmeter to check for the correct voltage output; calibrate the RDC2 voltage if necessary.
  12. Press OFF to stop the generator set.
  13. Reconnect utility power to the generator set.
  14. Press AUTO to place the generator set in automatic mode.
Access the Air Intake Area installation
  1. Unlock and raise the enclosure roof.
  2. Pull the air intake panel up and off its four bushings.
  3. Remove the cover panel over the terminal block to make electrical connections.
  4. After connections complete and battery installed, reinstall panels.
Battery Installation Procedure installation

⚠ Battery acid can cause severe injury or death

⚠ Explosion hazard from battery gases

  1. Ensure starting battery is fully charged before placing in service.
  2. Clean battery posts and/or adapters if necessary.
  3. Install battery post adapters, if needed.
  4. Place battery in the housing.
  5. Connect positive (+) lead to engine starting battery.
  6. Connect negative (-) lead to engine starting battery.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12-volt engine electrical system, single starter motor, negative groundBattery negative to ground terminal on or near starter motor; battery positive to positive terminal on starter solenoidAll generator set models use a negative ground with a 12-volt engine electrical system
Engine start connection for non-RXT transfer switch or remote start/stop switchTerminals 3 and 4 on generator set terminal blockRoute engine start leads through separate conduit from AC power and load leads
RXT transfer switch to generator set terminal block A, B, PWR, COMP10-1 through P10-4 (transfer switch) to A, B, PWR, COM (generator set)Terminal block connections 3 and 4 not used with Model RXT ATS
1Single-phase leads 1-2, 3-41, 2, 3, 44-lead generator sets are not reconnectable
3Three-phase leads 1-4, 2-5, 3-6, 7-10, 8-11, 9-121-1212-lead generator sets are reconnectable to voltages shown on the generator set specification sheet
Single Phase12-volt engine electrical system, single starter motorPositive to starter solenoid; negative to ground on or near starter motorNegative ground; follow polarity markings
Single Phase4-lead/12-lead reconnection per 12-Lead Generator Reconnection diagram (Figure 27)Single-phase leads 1-2, 3-4; sensing leads 11-444-lead generators are not reconnectable; 12-lead three-phase reconnectable to voltages shown on spec sheet
Three Phase12-lead reconnection per Figure 27Leads 1-4, 2-5, 3-6, 7-10, 8-11, 9-12; sensing leads V7, V8, V9Also route leads through current transformers (CTs) and change controller voltage setting; replace line circuit breaker for new voltage
100/2001Single
100/2003Delta
110/2201Single
110/2203Delta
115/2301Single
12 VDCSingle starter motor, negative ground engine electrical systemPositive (+) to starter solenoid terminal; negative (-) to ground terminal on or near starter motorRemove negative lead first when disconnecting, reconnect negative lead last
1201SingleGenset System Voltage/Frequency/Phase table for controller setup
120/2083WyeVoltage configuration (Figure 4-12)
120/208, 120/240, 277/48033-phase 2G712
120/2401SingleVoltage configuration (Figure 4-12)
120/2401Single phase 2F74
120/2403DeltaVoltage configuration (Figure 4-12)
127/2203Wye
2201Single
220/3803Wye
2301Single
230/4003Wye
2401Single
240/4163Wye
277/4803WyeVoltage configuration (Figure 4-12)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

Which generators use the Kohler CH740 (14 kW models); CH1000 (20 kW models) engine?

The Kohler CH740 (14 kW models); CH1000 (20 kW models) powers 3 generator set(s), including Kohler 14RCA, Kohler 20RCA, Kohler RCA.

How often should you change the oil in the Kohler CH740 (14 kW models); CH1000 (20 kW models)?

The Kohler CH740 (14 kW models); CH1000 (20 kW models) oil change interval is every 100 hours.

What is a common problem with the Kohler CH740 (14 kW models); CH1000 (20 kW models) engine?

A commonly reported issue on generators using the Kohler CH740 (14 kW models); CH1000 (20 kW models) is: The generator shuts down due to a main power overload.. Fix: Check the circuit breaker and ensure it is not tripped. If necessary, replace the circuit breaker..