| Other | Engine derating - ambient temperature | about 1% | per 10ºF (5.6ºC) over 72ºF (22ºC) | above 72ºF (22ºC) |
| Other | Engine derating - elevation | 2% to 4% | per 1000 ft (305 m) of elevation | |
| Other | Low-pressure compressed air for cleaning cabinet interior | less than 40 | PSI (276 kPa) | |
| Other | Voltage regulation | +/-1% | % | |
| Pressure | Engine oil pressure, normal operating | 35-80 | psi (241-552 kPa) | engine running |
| Pressure | Maximum tire pressure | 50 | psi | |
| Speed | Engine operating speed | 1800 | rpm | |
| Speed | Frequency reading on controller LCD window | 60 | Hz | all loads disconnected, unit restarted |
| Speed | Maximum recommended highway towing speed | 45 | mph (72 km/h) | |
| Speed | Recommended off-road towing speed | 10 mph (16 km/h) or less | mph (16 km/h) | depending on terrain |
| Temperature | Engine coolant temperature, normal operating | 100-230 | °F (38-110°C) | engine running |
| Temperature | High Coolant Temperature Shutdown Threshold | 210 | °F | 99°C |
| Temperature | Maximum ambient air temperature for engine operation | 120 | °F (49°C) | |
| Temperature | Maximum ambient operating temperature | 120 | °F | shut down if above; 49°C |
| Temperature | Stop engine immediately if coolant temperature reaches | 210 | °F (99°C) | |
| Torque | Wheel lug nuts - first pass | 20-25 | ft-lbs (27-33 Nm) | start all lug nuts by hand first |
| Torque | Wheel lug nuts - second pass | 50-60 | ft-lbs (67-81 Nm) | |
| Torque | Wheel lug nuts - third pass | 90-120 | ft-lbs (122-162 Nm) | re-torque in sequence after first road use |
| Torque | Wheel lug nuts, first pass | 20-25 | ft-lbs | first pass |
| Torque | Wheel lug nuts, second pass | 50-60 | ft-lbs | second pass |
| Torque | Wheel lug nuts, third pass | 90-120 | ft-lbs | third pass |
| Voltage | Engine/DC battery voltage (VBAT) | 13.5-15 | V | 12-volt system, engine running |
| Voltage | GFCI Outlet / Ballast Supply Voltage | 120 ±5 | V | |
| Voltage | Incoming voltage to ballast | 120 | V | +/- 5V |
| Voltage | Incoming voltage to ballast | 120V +/- 5V | VAC | |
| Voltage | Transformer Stabilized Voltage | 240-260 | VAC | after strike, drops then rises and stabilizes |
| Voltage | Transformer Strike Voltage | approximately 400 | VAC | when bulb strikes/induces an arc |
| Voltage | Transformer output at light strike | approximately 400 | VAC | as light strikes |
| Voltage | Transformer output stabilized | 240-260 | VAC | stabilized |
| Voltage | Transformer voltage after strike, stabilizes at | 240-260 | VAC | stabilized |
| Voltage | Transformer voltage as light strikes (induces an arc) | approximately 400 | VAC | strikes |