| Clearance | Air shutoff damper plunger distance A (minimum) | 18.3 | mm | 0.72 inch; replace plunger if less |
| Clearance | Coolant level below bottom of filler pipe | 13 | mm | no sight gauge |
| Clearance | Crankshaft end play | .178 to .635 | mm (0.0070 to 0.0250 inch) | measured with dial indicator |
| Clearance | Crankshaft end play after assembly | 0.178 to 0.635 | mm (0.0070 to 0.0250 inch) | after assembly |
| Clearance | End play at heat sink after assembly | 0.076 to 0.635 | mm (0.0030 to 0.0250 inch) | after assembly |
| Clearance | Gap at 3, 6, 9, 12 o'clock positions | 0.03 to 0.13 | mm (0.001 to 0.005 inch) | between |
| Clearance | Gap between generator and flywheel housing at locations (E), (F), (G), (H) | >0.03 and <0.13 | mm (0.001 inch to 0.005 inch) | more than 0.03 mm and less than 0.13 mm |
| Clearance | Generator forward offset from midpoint of end play | + 0.50 | mm (+ 0.0200 inch) | while generator supported by crane |
| Clearance | Rotor end play | 3.81 to 7.62 | mm (.150 to .300 inch) | approximately |
| Clearance | Shim thickness divisor for number of shims | 0.8 | mm (0.03 inch) | divide Letter L by this value |
| Clearance | Support deflection during bolt tightening | 0.13 | mm (0.005 inch) | maximum allowed movement |
| Gap | Air shutoff damper plunger distance A (replace if less) | 18.3 | mm | |
| Other | Air cleaner element cleaning limit | six times | | replace at least once per year regardless |
| Other | Altitude capability without derate | 1525 | m | |
| Other | Altitude capability without derate | 800 | m | |
| Other | Coolant Sample (Level 1) interval for Cat DEAC | 250 | hours | |
| Other | Cooling system cleaner amount (heavy deposits) | 0.5 | L per 3.8 to 7.6 L capacity | 1 pint per 1 to 2 US gal |
| Other | Cooling system cleaner amount (normal deposits) | 0.5 | L per 15 L capacity | 1 pint per 4 US gal |
| Other | Cooling system cleaning duration (heavy deposits) | 90 | minutes | minimum, coolant at least 82 C (180 F) |
| Other | Cooling system cleaning duration (normal deposits) | 30 | minutes | minimum, coolant at least 82 C (180 F) |
| Other | Cooling system fill rate maximum | 19 | L/min | |
| Other | Damper fluid viscosity degradation limit | 20 | percent | majority of applications |
| Other | Damper fluid viscosity degradation limit (Hasse & Wrede) | 20 | percent | majority of applications |
| Other | Damper operating hours before rebuild/replace (damper without sampling port) | 20000 | hours | |
| Other | Damper without sampling port - rebuild/replace interval | 20000 | hours | or at major overhaul |
| Other | Exercise under full load | 1 | hour | ToCI quarterly |
| Other | Fast Acting Cooling System Cleaner amount | 0.5 L per 15 L | L | cooling system capacity, normal deposits |
| Other | Fast Acting Cooling System Cleaner amount | 0.5 L per 3.8 to 7.6 L | L | cooling system capacity, heavy deposits |
| Other | Full load test duration | 4 | hours | Once per year |
| Other | Gross Input Torque (TH55-E70) | 12 667 | N•m (9350 lb-ft) | |
| Other | Gross Input Torque (TH55-E90) | 12 677 | N•m (9350 lb-ft) | |
| Other | Hydrosolv cleaner concentration | 2 to 5 | percent | temperatures up to 93 C (200 F) |
| Other | Load bank data recording interval | 15 | minutes | During load bank test |
| Other | Load bank test load level | 80 | % of generator nameplate capacity | 4-hour resistive load bank test |
| Other | Load bank test profile | 2 hours at 50%, 1 hour at 75%, 1 hour at 100% | | Annual four (4) hour load bank test |
| Other | Maximum air pressure at nozzle for cleaning purposes | 205 | kPa | 30 psi |
| Other | New drive belt tension recheck after operation | 30 | minutes | rated rpm |
| Other | Rating condition (diesel 7 L and higher) | 99 kPa (29.31 in Hg) dry barometer, 25°C (77°F) | | SAE J1995 inlet air standard |
| Other | Rating condition (diesel up to 6.6 L) | 100 kPa (29.5 in Hg) total barometric pressure, 1 kPa (.295 in Hg) vapor pressure, 25°C (77°F) | | ISO/TR14396 inlet air standard |
| Other | Rating condition (gas) | 100 kPa (29.61 in Hg) and 25°C (77°F) | | SAE J1349 standard |
| Other | Stall Torque Ratio (TH55-E70) | 2.23 | | |
| Other | Stall Torque Ratio (TH55-E90) | 2.23 | | |
| Other | Starting motor cool-down between cranking periods | 2 | minutes | |
| Other | Supplemental coolant additive concentration maximum (conventional coolant) | 6 | percent | |
| Other | Supplemental coolant additive concentration maximum (water and SCA) | 8 | percent | |
| Other | Thread lock cure time minimum before air shutoff use | 1 | hour | |
| Pressure | Air cleaner service indicator restriction (clean/replace) | 6 | kPa | 25 inches of H2O |
| Pressure | Engine air cleaner differential pressure (nominal) | 3 | kPa | normal engine operation |
| Pressure | Engine air cleaner maximum differential pressure (replace element) | 6.2 | kPa | |
| Pressure | Engine oil filter differential pressure (nominal) | 60 | kPa | normal engine operation |
| Pressure | Engine oil filter differential pressure (normal) | 60 | kPa | normal engine operation |
| Pressure | Engine oil filter differential pressure (replace elements) | 103 | kPa | oil filter elements to be replaced |
| Pressure | Engine oil pressure during cranking | 70 | kPa | cranking with fuel off |
| Pressure | Fuel filter differential pressure (nominal) | 60 | kPa | normal engine operation |
| Pressure | Fuel filter differential pressure (normal) | 60 | kPa | normal engine operation |
| Pressure | Fuel filter differential pressure (replace secondary elements) | 103 | kPa | fuel filter elements to be replaced |
| Pressure | Maximum air pressure at nozzle for cleaning | 205 | kPa | |
| Pressure | Maximum air pressure for cleaning (aftercooler core) | 205 | kPa | 30 psi; at nozzle |
| Pressure | Maximum air pressure for cleaning (radiator) | 205 | kPa | 30 psi; deadheaded nozzle |
| Pressure | Maximum air pressure for cleaning air cleaner element | 207 | kPa | 30 psi |