3.0L L4 Engine
The 3.0L L4 is a 1.81 L engine, producing up to 5200 kW. It powers generator sets from General Motors, including the 3.0 L. It holds 5 L (1.3 gal) of oil and 7.3 L (1.9 gal) of coolant.
Also known as: 3.0L L4
Engine specifications
| Oil capacity | 5.0 L |
|---|
| Coolant capacity | 7.3 L |
|---|
| Displacement | 1.81 L |
|---|
| Gross power | 5200 kW |
|---|
Generator sets powered by this engine
1
Common problems
15- Unit Not In Auto LED 12
Fix: Move the AUTO/OFF/MANUAL switch to the AUTO position for automatic starting. - Low Fuel LED 11
Fix: Check fuel supply and replenish as required. - UNIT WILL START THEN FAIL — Overspeed light lit
Cause: Lost governor control; Defective overspeed switch - UNIT WILL START THEN FAIL — Overcrank light lit
Cause: Lost signal on Mag Pickup Crank Disconnect Terminal or lost signal on Auxiliary Crank Disconnect terminal after unit started - UNIT WILL START THEN FAIL — Low Oil light lit
Cause: Low oil in crankcase; Oil pump failed; Defective pressure switch - UNIT WILL START THEN FAIL — Loss of Fuel
Cause: Empty fuel tank; Restricted fuel filter; Restricted, broken or loose fuel line - UNIT WILL START THEN FAIL — Loose or Open Connections
Cause: May have lost power to control or ignition system - UNIT WILL START THEN FAIL — High Water Temperature light lit
Cause: Low water level in radiator; Thermostat closed; Broken fan belt; Restricted flow through radiator; Ambient temperature too high; Defective temperature switch - UNIT STARTS BUT STARTER DOES NOT DISENGAGE — Voltage on Terminal #3 After Unit Running
Cause: Signal must be present at either Terminal #5, 6, 7, or 12 after unit starts to operate crank disconnect of control - UNIT STARTS BUT STARTER DOES NOT DISENGAGE — No Voltage on Terminal 49 After Unit is Running
Cause: Starter drive could be hanging up or the solenoid on starter is not disengaging - UNIT NOT IN AUTO LED — Indicates AUTO/OFF/MANUAL switch is in the OFF position which will prevent automatic starting if an automatic transfer switch is used. *7
Fix: Move the AUTO/OFF/MANUAL switch to the AUTO position for automatic starting - UNIT DOES NOT START — Voltage on Terminal #2 While Cranking
Cause: If present may have defective fuel valve, defective ignition system or loose connection - UNIT DOES NOT START — Fuel Supply
Cause: Empty fuel tank; Air in fuel lines; Wrong pressure on Natural Gas or LPG - PRE-HI ENGINE TEMP LED. Engine continues to operate — Indicates engine has begun to overheat and engine temperature has risen to approximately 215°F (105°C). If generator is powering non critical and critical loads and cannot be shut down. Use the following: #14
Fix: Reduce load if possible by turning off non-critical loads; Check air inlets and outlets and remove any obstructions to airflow; Open doors or windows in generator area to increase ventilation; If engine can be stopped, follow procedure in Step 2 - PRE LOW OIL PRESSURE LED. Engine continues to operate — Indicates engine oil pressure has dropped to 20 psi (138kPa). If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow Step 4 procedure. If engine can be stopped, follow procedures in Step 4. *3
Compiled from service & troubleshooting documentation across every generator set that uses the 3.0L L4.
Common questions
What is the oil capacity of the 3.0L L4?
The 3.0L L4 engine has an oil capacity of 5.0 liters.
What is the displacement of the 3.0L L4?
The 3.0L L4 has a displacement of 1.81 liters.
Which generators use the 3.0L L4 engine?
The 3.0L L4 powers 1 generator set(s), including General Motors 3.0 L.
What is a common problem with the 3.0L L4 engine?
A commonly reported issue on generators using the 3.0L L4 is: Unit Not In Auto LED. Fix: Move the AUTO/OFF/MANUAL switch to the AUTO position for automatic starting..