| Other | 10 in. weld flange bolt circle diameter B | 361.95 | mm (14.25 in.) | |
| Other | 10 in. weld flange outside diameter C | 406.4 | mm (16.0 in.) | |
| Other | 10 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 12 in. weld flange bolt circle diameter B | 431.80 | mm (17.00 in.) | |
| Other | 12 in. weld flange outside diameter C | 482.6 | mm (19.0 in.) | |
| Other | 12 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 14 in. weld flange bolt circle diameter B | 476.25 | mm (18.75 in.) | |
| Other | 14 in. weld flange outside diameter C | 533.4 | mm (21.0 in.) | |
| Other | 14 in. weld flange quantity of bolts / bolt hole diameter D | 12, 28.58 | mm (1.13 in.) | |
| Other | 16 in. weld flange bolt circle diameter B | 539.75 | mm (21.25 in.) | |
| Other | 16 in. weld flange outside diameter C | 596.9 | mm (23.5 in.) | |
| Other | 16 in. weld flange quantity of bolts / bolt hole diameter D | 16, 28.58 | mm (1.13 in.) | |
| Other | 18 in. weld flange bolt circle diameter B | 577.85 | mm (22.75 in.) | |
| Other | 18 in. weld flange outside diameter C | 635.0 | mm (25.0 in.) | |
| Other | 18 in. weld flange quantity of bolts / bolt hole diameter D | 16, 31.75 | mm (1.25 in.) | |
| Other | 20 in. weld flange bolt circle diameter B | 635.00 | mm (25.00 in.) | |
| Other | 20 in. weld flange outside diameter C | 698.5 | mm (27.5 in.) | |
| Other | 20 in. weld flange quantity of bolts / bolt hole diameter D | 20, 31.75 | mm (1.25 in.) | |
| Other | 5 in. weld flange bolt circle diameter B | 215.90 | mm (8.50 in.) | |
| Other | 5 in. weld flange outside diameter C | 241.30 | mm (9.50 in.) | |
| Other | 5 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 6 in. weld flange bolt circle diameter B | 254.0 | mm (10.0 in.) | |
| Other | 6 in. weld flange outside diameter C | 279.4 | mm (11.0 in.) | |
| Other | 6 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 8 in. weld flange bolt circle diameter B | 298.45 | mm (11.75 in.) | |
| Other | 8 in. weld flange outside diameter C | 342.9 | mm (13.5 in.) | |
| Other | 8 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | Alternator protection current/time limits | 200%: 40 seconds; 300%: 10 seconds; 425%: 5 seconds; 950%: 1 second | | rated current percentage |
| Other | Battery specific gravity (charge threshold) | 1.215 | specific gravity | at 26.7 C (80 F); charge if below |
| Other | Battery specific gravity (fully charged) | 1.260 | specific gravity | at 26.7 C (80 F) electrolyte temperature |
| Other | Controller operating temperature range | --40 to 70 C (--40 to 158 F) | | |
| Other | Controller power drain | 400 milliamps at 12V; 200 milliamps at 24V | | |
| Other | Engine speed adjustment | 50 | | default setting; settings between 40 and 60 acceptable; 52 increases speed by 2 RPM, 49 decreases by 1 RPM |
| Other | Frequency regulation steady state | 0.5 | % | Electronic isochronous governor |
| Other | Gaseous fuel tank maximum safe fill level | 80 | % of total fuel tank volume | |
| Other | Generator to bus phase angle | -10 to 10 | degrees | verify with contactor closed |
| Other | LP gas fuel system leak test pressure | 6--8 ounces per square inch (10--14 inches water column) | oz/in2 (in. water column) | test pressurized |
| Other | Reactive droop | 1 | % | default setting; range 0.5 - 2% |
| Other | Voltage regulation no-load to full-load | ±0.5 | % | Alternator |
| Other | Weld flange angle A (10, 12, 14 in. nominal pipe size) | 30 | deg. | |
| Other | Weld flange angle A (16, 18, 20 in. nominal pipe size) | 22.5 | deg. | |
| Other | Weld flange angle A (5, 6, 8 in. nominal pipe size) | 45 | deg. | |
| Other | Wheel stud size | 1/2-20 | | |
| Pressure | Fuel tank pressure relief valve (close) | 1937--2130 | kPa (281--309 psi) | |
| Pressure | Fuel tank pressure relief valve (open) | 2151 | kPa (312 psi) min | |
| Pressure | LPG vapor withdrawal fuel supply pressure | 1.24--2.74 | kPa | Normal operation |
| Pressure | Natural gas fuel supply pressure | 1.74--2.74 | kPa | Normal operation |
| Pressure | Tire inflation pressure @ rated load | 552 (80 psi) | kPa (psi) | |
| Speed | Overfrequency default setting | 110% of nominal | % | |
| Speed | Overfrequency setting range | 102%--140% of nominal | % | |
| Speed | Overfrequency time delay | 10 | sec | |
| Speed | Underfrequency default setting | 90% of nominal | % | |
| Speed | Underfrequency setting range | 80%--95% of nominal | % | |
| Speed | Underfrequency time delay | 10 (short term), 60 (long term) | sec | |
| Temperature | Ambient temperature | 45 | °C | Maximum for radiator-cooled system |
| Temperature | Exhaust temperature at rated kW, dry exhaust | 649 | °C | At rated kW |
| Temperature | Maximum allowable exhaust back pressure | 10.2 | kPa | At rated kW |
| Torque | 1-12 fastener | 283.0 (209) | Nm (ft. lb.) | Assembled into cast iron or steel, Grade 2 or 5 |
| Torque | 1-8 fastener | 259.0 (191) | Nm (ft. lb.) | Assembled into cast iron or steel, Grade 2 or 5 |
| Torque | 1/2-13 fastener | 60.0 (44) | Nm (ft. lb.) | Assembled into cast iron or steel, Grade 2 or 5 |