Maintenance schedule
| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | paper element | — |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
The John Deere RG6135HF485 is a 13.5 L turbocharged engine rated at 1800 rpm. It powers generator sets from Generac and Magnum, including the MMG405, MMG465, MMG405 and MMG405 Super Start. It holds 90.4 L (23.9 gal) of coolant.
Also known as: John Deere RG6135HF485
| Coolant capacity | 90.4 L |
|---|---|
| Displacement | 13.5 L |
| Aspiration | turbocharged |
| Rated speed | 1800 rpm |
Shared across brands: Generac, Magnum
Compiled from service & troubleshooting documentation across every generator set that uses the John Deere RG6135HF485.
| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | paper element | — |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Engine oil and oil filter | Change | 250 hr | First service — Change after first 100 hours, then every 250 hours. If John Deere PLUS-50 or equivalent is used, every 500 hours. | |
| Oil vapor recirculation system/non-return valve | Check | 250 hr | ||
| Air intake hoses, connections, and system | Check | 500 hr | 12 mo | |
| Battery | Inspect | 500 hr | 12 mo | Service battery |
| Belt tensioner and belt wear | Check | 500 hr | 12 mo | At 500 hour/12 month interval, remove belt and check for wear; inspect pulleys and bearings |
| Coolant pump weep hole foam filter | Check | 500 hr | 12 mo | |
| Cooling system | Check | 500 hr | 12 mo | |
| Engine ground connection | Check | 500 hr | 12 mo | |
| Engine mounts | Check | 500 hr | 12 mo | |
| Fuel filters/water separator | Replace | 500 hr | 12 mo | Replace fuel filters/clean water separator |
| Generator drive plate torque | Check | 500 hr | 12 mo | See page 45 |
| Leveling jack(s) | Lubricate | 500 hr | 12 mo | |
| Oil vapor recirculation filter | Replace | 500 hr | 12 mo | |
| Thermostats | Test | 500 hr | 12 mo | |
| Air cleaner elements | Replace | 2000 hr | 24 mo | |
| Alternator and fan belts | Replace | 2000 hr | 24 mo | |
| Coolant | Check | 2000 hr | 24 mo | Add coolant |
| Electrical wiring and connections | Check | 2000 hr | 24 mo | |
| Fuel system | Drain | 2000 hr | 24 mo | Bleed fuel system |
| Fuses | Check | 2000 hr | 24 mo |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Fine voltage adjustment window (V Detect) | 45 | seconds | |
| Other | Fuel level low fuel shutdown setpoint | 5 | % | |
| Other | Fuel level low fuel warning setpoint | 15 | % | |
| Pressure | Air filter restriction indicator - replace element | 20 | in. H2O | |
| Pressure | Air filter restriction indicator - replace primary air cleaner | 25 | in. H2O | |
| Pressure | Engine oil pressure, low oil pressure shut down | less than 20 | psi (138 kPa) | |
| Pressure | Engine oil pressure, normal operating | 35-80 | psi (241-552 kPa) | engine running |
| Pressure | Engine oil pressure, verify within 5 seconds of start | 5 | psi (34 kPa) | within 5 seconds of start |
| Speed | Generator frequency, no load | 60.0 | Hz | no load |
| Speed | Operating speed | 1800 | rpm | |
| Temperature | Coolant temperature minimum display | 100 | °F (38°C) | |
| Temperature | Maximum water/coolant temperature shut down | 230 | °F (110°C) | |
| Temperature | Viscous fan clutch temperature range | 170-200 | °F (77-93°C) | |
| Torque | Generator drive plate bolts | 33 | ft-lb (45 Nm) | |
| Torque | Shorting (link) board hardware | 25 | ft-lbs | |
| Torque | Trailer wheel lug nuts, first pass | 20-25 | ft-lbs (27-33 Nm) | |
| Torque | Trailer wheel lug nuts, second pass | 50-60 | ft-lbs (67-81 Nm) | |
| Torque | Trailer wheel lug nuts, third pass | 90-120 | ft-lbs (122-162 Nm) | |
| Voltage | Battery voltage, normal reading on 12 volt systems | 13-14 | V | engine running |
| Voltage | Battery voltage, normal reading on 24 volt systems | 24-26 | V | engine running |
| Voltage | Voltage regulation | +/- 1 | % |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | John Deere PLUS-50 or equivalent | Consult the engine operation and maintenance manual for the proper grade of oil, including special operating conditions. If John Deere PLUS-50 or equivalent is used, oil can be changed every 500 hours. | |||
| Grease | High quality grease made specifically for lubrication of wheel bearings | Trailer wheel bearings; minimum lubrication every 12 months or 12,000 miles (19,312 km) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| AnInIOM Sd | AnInIOM Sd | Shutdown alarm configurable on the input of IG-IOM/IGS-PTM. | Shutdown | |
| AnInIOM Wrn | AnInIOM Wrn | Warning alarm configurable on the input of IG-IOM/IGS-PTM. | Warning | |
| Battery Flat | Battery Flat (low battery) | If the controller switches off during starting sequence due to bad battery condition, it doesn't try to start again and activates this protection. | Shutdown | |
| Binary Input | Binary Input | Configurable warning/shutdown alarms on the inputs of IL-NT. | ||
| ChrgAlternFail | ChrgAlternFail | Failure of the alternator to charge the battery. | Warning | |
| EmergencyStop | EmergencyStop | If the input Emergency Stop is opened or the red E-Stop button is pushed, shutdown is immediately activated. | Shutdown | |
| Engine Temp Sd | Engine Temp Sd | Water temperature is greater than Sd Water Temp setpoint. | Shutdown | |
| Engine Temp Wrn | Engine Temp Wrn | Water temperature is greater than Wrn Water Temp setpoint. | Warning | |
| Fgen<, > | Fgen<, > | The generator frequency is out of limits given by Gen >f and Gen <f setpoints. | Shutdown | |
| Fuel Level Sd | Fuel Level Sd | Fuel level is smaller than Sd Fuel Level setpoint (5%). | Shutdown | |
| Fuel Level Wrn | Fuel Level Wrn | Fuel level is smaller than Wrn Fuel Level setpoint (15%). | Warning | |
| GCB fail | GCB fail | Failure of the generator circuit breaker. | Shutdown | |
| Igen unbl | Igen unbl | The generator current is unbalanced. | Shutdown | |
| Low BackupBatt | Low BackupBatt | RTC backup battery is flat (low). | Warning | |
| Oil Press Sd | Oil Press Sd | Oil pressure is smaller than Oil Press Sd setpoint. | Shutdown | |
| Oil Press Wrn | Oil Press Wrn | Oil pressure is smaller than Oil Press Wrn setpoint. | Warning | |
| Overload | Overload | The load is greater than the value given by Overload setpoint. | Shutdown | |
| Overspeed | Overspeed | The protection comes active if the speed is greater than Overspeed setpoint. | Shutdown | |
| ParamFail | ParamFail | Wrong checksum of parameters. Happens typically after downloading new firmware or changing of the parameter. The controller stays in INIT mode. | Check all parameters, write at least one new parameter. | |
| PickupFault | PickupFault | Failure of the magnetic pick-up sensor for speed measurement. | Shutdown | |
| Sd IOM fail | Sd IOM fail | IOM/IGS-PTM module. | Shutdown | |
| SprinkIActive | SprinkIActive | The protection is active if the output Sprinkler is closed. | Warning | |
| Start failed | Start failed | Unit did not start. | Shutdown | |
| Stop fail | Stop fail | Unit did not stop. | Shutdown | |
| Ubat | Ubat | Battery voltage is out of limits given by Batt Undervolt setpoints. | Warning | |
| Underspeed | Underspeed | During starting, when the RPM reaches Starting RPM setpoint the starter switches off and speed can drop under Start RPM again; underspeed protection becomes active. Evaluation starts 5 seconds after start up. | Shutdown | |
| Vgen unbal | Vgen unbal | The generator voltage is unbalanced more than the value of Volt unbal setpoint. | Shutdown | |
| Vgen<, > | Vgen<, > | The generator voltage is out of limits given by Gen <V and Gen >V setpoints. | Shutdown | |
| Wrn ECU Alarm | Wrn ECU Alarm | ECU alarm list is not empty. | Warning | |
| Wrn RA15 fail | Wrn RA15 fail | Warning alarm in case of lost connection to IGL=RA15 module. | Warning | |
| WrnMaintenance | WrnMaintenance | The period for servicing is set by the WrnMaintenance setpoint. The protection comes active if the running hours of the engine reach this value (250 hours). | Warning |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ NEVER ATTEMPT TO CHANGE THE VOLTAGE WHILE THE ENGINE IS RUNNING. LETHAL VOLTAGE MAY BE PRESENT AT THE CONNECTION LUGS ON THE SHORTING (LINK) BOARD.
Tools: Wrench, Torque wrench
Tools: Torque wrench
Tools: Grease gun
⚠ The controller must be in AUTO mode to run at the programmed time.
⚠ CARBON MONOXIDE: USING A GENERATOR INDOORS CAN KILL YOU IN MINUTES!
⚠ If the unit does not shut down within 15 seconds, a Stop Fail alarm is displayed.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| Cam lock connections | L1 - Black, L2 - Red, L3 - Blue, N (Neutral) - White, G (Ground) - Green | Series 16 taper nose 400A, 600V cam locks; make all connections to one side only | ||
| 120 | 3 | Low Delta | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 208/120 | 3 | Link board attached in 208 VOLT 3Ø position (upper position) | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Shorting (link) board upper position |
| 208/120 | 3 | Low Wye | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 240/120 | 1 | Low Zig Zag | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 240/120 | 3 | High Delta | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 480/240 | 1 | High Zig Zag | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 480/277 | 3 | High Wye | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Dedicated 12 lead generators option |
| 480/277 | 3 | Link board attached in 480 VOLT 3Ø position (lower position) | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Shorting (link) board lower position |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Parts listed by aftermarket suppliers as fitting this engine — leads compiled from supplier catalogs; verify the exact part for your serial number.
The John Deere RG6135HF485 has a displacement of 13.5 liters.
The John Deere RG6135HF485 powers 5 generator set(s), including Generac MMG405, Generac MMG465, Magnum MMG405, Magnum MMG405 Super Start, Magnum MMG465.
A commonly reported issue on generators using the John Deere RG6135HF485 is: OVERSPEED OR UNDERSPEED SHUT DOWN. Cause: Engine speed is above or below 60.0 Hz.. Fix: Disconnect loads and check frequency. Adjust engine speed as needed..