| Other | AC waveform THD (THDV) | < 5 | % | no load to full linear load |
| Other | BMEP at set rated load (prime) | 1885 | kPa | prime rating |
| Other | BMEP at set rated load (standby) | 2109 | kPa | standby rating |
| Other | Breaker fail to synchronize default time delay | 120 | s | adjustable 10–900 s |
| Other | Compression ratio | 16:1 | | |
| Other | Derate above 1402 m (4600 ft) / 40 °C | 4.5% per 305 m (1000 ft) and 11.0% per 10 °C (18 °F) | | standby and prime |
| Other | High AC voltage shutdown default | 110% | % of nominal voltage | for 10 s; adjustable 105–125%, 0.1–10 s |
| Other | Instantaneous pickup (Ii) range (Micrologic 3.0 and 5.0) | 1.5–12 x In | x In | |
| Other | Long-time delay tr | 0.5–24 | s | at 6 x Ir |
| Other | Long-time pickup (Ir) adjustment range | 0.4–1.0 x In | x In | sensor plug rating In |
| Other | Low AC voltage shutdown default | 85% | % of reference voltage | for 10 s; adjustable 50–95%, 2–20 s |
| Other | Over frequency shutdown/warning default | 6 | Hz above nominal | for 20 s, disabled; adjustable 2–10 Hz above set point, 1–20 s |
| Other | Over load (kW) warning default | 105% | % of rated kW | adjustment range 80–140%, 0–120 s delay; default 60 s |
| Other | Piston speed | 11.4 | m/s | |
| Other | Reverse Var shutdown default | 20% | % of rated Var | for 10 s; adjustable 15–50%, 10–60 s |
| Other | Reverse power shutdown default | 10% | % of standby kW | for 3 s; adjustable 5–20%, 1–15 s |
| Other | Short circuit protection threshold | 175% | % of rating | output current on any phase |
| Other | Telephone Harmonic Factor (THF) | < 3 | | |
| Other | Telephone Influence Factor (TIF) | < 50 | per NEMA MG1-22.43 | |
| Other | Under frequency shutdown default | 6 | Hz below reference | for 10 s; adjustable 2–10 Hz below set point, 5–20 s |
| Other | Wire stripping length | 1.38 In (35 mm) | in | |
| Pressure | BMEP at set rated load | 2214 | kPa | prime rating |
| Pressure | BMEP at set rated load | 2435 | kPa | standby rating |
| Pressure | Maximum air cleaner restriction | 6.2 | kPa | |
| Pressure | Maximum back pressure | 10.1 | kPa | |
| Pressure | Maximum back pressure | 6.8 | kPa | exhaust |
| Pressure | Maximum cooling air flow static restriction | 0.12 | kPa | |
| Pressure | Maximum fuel inlet restriction | 13.44 | kPa | |
| Pressure | Maximum fuel inlet restriction | 30 | kPa | |
| Pressure | Maximum fuel return line restriction | 34 | kPa | |
| Speed | Droop electronic speed governing | 0 to 10 | % | no load to full load |
| Speed | Frequency drift | +/-0.5 | % | 33 °C (60 °F) change in ambient temperature over an 8 hour period |
| Speed | Frequency regulation | Isochronous | | |
| Speed | Isochronous governing steady state accuracy | +/-0.25 | % | any steady state load from no load to full load |
| Speed | Over frequency shutdown/warning (81 o) default | 6 | Hz | 20 seconds, disabled |
| Speed | Overspeed limit | 2100 | rpm | |
| Speed | Overspeed limit | 2100 ±50 | rpm | |
| Speed | Random frequency variation | ± 0.25 | % | |
| Speed | Random frequency variation | ± 0.25% | % | |
| Speed | Rated speed | 1800 | rpm | 60 Hz |
| Speed | Under frequency shutdown (81 u) default | 6 | Hz | 10 seconds |
| Temperature | Ambient design (standard set-mounted radiator cooling) | 50 | °C | |
| Temperature | Ambient design (standard set-mounted radiator) | 50 | °C | |
| Temperature | Control operating ambient temperature | -40 to +70 | °C | |
| Temperature | Exhaust temperature | 458 | °C | prime rating, at set rated load |
| Temperature | Exhaust temperature | 476 | °C | standby rating, at set rated load |
| Temperature | Exhaust temperature at set rated load (prime) | 463 | °C | prime |
| Temperature | Exhaust temperature at set rated load (standby) | 469 | °C | standby |
| Temperature | HMI operating ambient temperature | -20 to +70 | °C | |
| Temperature | Maximum aftercooler inlet temp | 49 | °C | |
| Temperature | Maximum fuel inlet temperature | 71 | °C | |
| Temperature | Maximum jacket water outlet temp (remote radiator) | 104 | °C | standby |
| Torque | Circuit breaker terminal tightening torque (AWG 1/0...750 kcmil) | 548.75 Lbf.In (62 N.m) | Lbf.In | 0.08…0.62 in² (50…400 mm²) |
| Voltage | Digital output voltage regulation | +/-1.0 | % | any loads between no load and full load |
| Voltage | Droop voltage regulation | 0-10 | % | no load to full load |
| Voltage | High AC voltage shutdown (59) default | 110 | % | 10 seconds |
| Voltage | Low AC voltage shutdown (27) default | 85 | % | 10 seconds |
| Voltage | Random voltage variation | ± 0.5 | % | |
| Voltage | Random voltage variation | ± 0.5% | % | |
| Voltage | Standard temperature rise | 150 | °C | Standby at 40 °C ambient |