| Clearance | Fan belt tension (deflection) | 0.4-0.6 (10-5) | in. (mm) | |
| Gap | Magnetic pick-up air gap | 0.030 in. (0.76 mm) +/-0.010 in. (0.25 mm) | in. (mm) | |
| Gap | Speed Sensor to actuator air gap | 0.030 in. (0.76 mm) +/-0.010 in. (0.25 mm) | in. (mm) | |
| Injection timing | Timing (B.T.D.C.) | 16 +/- 1 | degrees | B.T.D.C. |
| Other | Fuel solenoid current, pull-in / hold | 50 Amps pull-in; 1.0 Amp hold | Amps | |
| Other | Overcrank shutdown, 5-Light controller | 45 seconds continuous cranking or 75 seconds cyclic cranking; 15 seconds if locked rotor | seconds | |
| Other | Overcrank shutdown, relay controller | 30-60 seconds continuous cranking | seconds | |
| Pressure | Anticipatory Low Oil Pressure switch closes | below 8 | psi (55 kPa) | |
| Pressure | Engine oil pressure | 43-57 | psi (294-392 kPa) | |
| Pressure | Fuel injection pressure | 2844 | psi (19609 kPa) | |
| Pressure | Low Oil Pressure shutdown | 7.1 | psi (49 kPa) | |
| Resistance | Fuel solenoid hold coil (black-red leads) | 11-13 | ohms | solenoid disconnected from engine harness |
| Resistance | Fuel solenoid pull-in coil (black-white 14P leads) | 0.12-0.26 | ohms | solenoid disconnected from engine harness |
| Resistance | K1, K2, K3, K4 relay coil (controller circuit board) | approx. 400 | ohms | R x 10 scale |
| Resistance | K20 relay coil (starter solenoid) | 3-4 | ohms | |
| Resistance | Oil pressure sender resistance at 0 psi/kPa | 227-257 | ohms | |
| Resistance | Oil pressure sender resistance at 100 psi (690 kPa) | 21-50 | ohms | |
| Resistance | Rotor resistance | 2.5-3.1 | ohms | room temperature |
| Resistance | Rotor resistance | 3.5-4.3 | ohms | room temperature |
| Resistance | Rotor resistance | 5.1 | ohms | room temperature |
| Resistance | Stator resistance leads 1-2, 3-4 | 0.07 | ohms | cold, room temperature |
| Resistance | Stator resistance leads 1-2, 3-4 | 0.13 | ohms | cold, room temperature |
| Resistance | Stator resistance leads 1-2, 3-4 | 0.17 | ohms | cold, room temperature |
| Resistance | Stator resistance leads 33-44 | 0.17 | ohms | cold, room temperature |
| Resistance | Stator resistance leads 55-33 | 1.1 | ohms | cold, room temperature |
| Resistance | Stator resistance leads 55-33 | 1.3 | ohms | cold, room temperature |
| Resistance | Stator resistance leads 55-33 | 2.2 | ohms | cold, room temperature |
| Resistance | Water temperature sender resistance at 100 degrees F (38 degrees C) | 450 +/-10% | ohms | |
| Resistance | Water temperature sender resistance at 160 degrees F (71 degrees C) | 130 +/-10% | ohms | |
| Resistance | Water temperature sender resistance at 220 degrees F (104 degrees C) | 47 +/-10% | ohms | |
| Speed | Governor speed, 50 Hz models | 1500 rpm full load; 53 Hz (1590 rpm) no load | rpm | |
| Speed | Governor speed, 60 Hz models | 1800 rpm full load; 63 Hz (1890 rpm) no load | rpm | |
| Speed | Overspeed shutdown | 70 Hz (2100 rpm) | Hz/rpm | 50 and 60 Hz models |
| Speed | Volts/Hz knee frequency (PowerBoost IIIE factory setting) | 57.5 Hz (60 Hz models); 47.5 Hz (50 Hz models) | Hz | |
| Temperature | Anticipatory High Engine Temperature switch closes | above 218 +/-7 | degrees F (103 +/-4 degrees C) | |
| Temperature | Anticipatory Low Water Temperature switch closes | below 60 +/-5 | degrees F (16 +/-8 degrees C) | |
| Temperature | Anticipatory Low Water Temperature switch opens | above 80 +/-5 | degrees F | |
| Temperature | High Engine Temperature shutdown | 230 | degrees F (110 degrees C) | |
| Torque | Cylinder head tightening torque Step 1 | 24-26 | ft. lbs (3.4-3.6 Nm) | |
| Torque | Cylinder head tightening torque Step 1 | 25-31 | ft. lbs (3.5-4.3 Nm) | |
| Torque | Cylinder head tightening torque Step 2 | 49-52 | ft. lbs (6.8-7.2 Nm) | |
| Torque | Cylinder head tightening torque Step 2 | 54-61.5 | ft. lbs (7.5-8.5 Nm) | |
| Torque | Drive disc to flywheel bolt torque | 168 | in. lbs (19 Nm) | |
| Torque | Drive disc to flywheel nut torque | 168 | in. lbs (19 Nm) | |
| Torque | Drive disc to rotor bolt torque | 540 | in. lbs (61 Nm) | |
| Torque | Fan to rotor bolt torque | 260 | in. lbs (29 Nm) | |
| Torque | Generator adapter to flywheel housing bolt torque | 300 | in. lbs (34 Nm) | |
| Torque | Generator adapter to flywheel housing bolt torque | 324 | in. lbs (37 Nm) | |
| Torque | Magnetic pickup actuator to rotor bolt torque | 96 | in. lbs (11 Nm) | |
| Torque | Overbolt torque | 216 | in. lbs (24 Nm) | |
| Valve clearance | Valve clearance, exhaust | 0.008 | in. (0.2 mm) | |
| Valve clearance | Valve clearance, intake | 0.008 | in. (0.2 mm) | |
| Voltage | Controller TB1 test point voltage | slightly less than 12 Volts DC | Volts DC | FASTCHECK toggle in prescribed position |
| Voltage | Megohmmeter insulation test voltage (rotor and stator) | 500 Volts DC; reading of approx. 500K ohms (1/2 megohm) and higher indicates good | Volts DC / ohms | |
| Voltage | Speed Sensor supply voltage at sensor (wire 24 to wire 2) | 9-5 Volts DC (as printed); approx. 7 Volts DC with set running | Volts DC | master switch OFF/OFF-RESET; running |