Home›Engines›Cummins/Onan VTA28-G3

Cummins/Onan VTA28-G3 Engine

The Cummins/Onan VTA28-G3 is a 28 L turbocharged engine. It powers generator sets from Cummins/Onan, including the DFGC and VTA-28-G3. It holds 84 L (22.2 gal) of oil and 167 L (44.1 gal) of coolant.

Also known as: Cummins VTA28-G3

Part of the Cummins/Onan VTA28 engine family — 8 variants share parts & fitment.

28.0 L
Displacement
84.0 L
Oil capacity

Engine specifications

Oil capacity84.0 L
Coolant capacity167.0 L
Displacement28.0 L
Aspirationturbocharged

Generator sets powered by this engine

2
Cummins/Onan DFGCCummins/Onan VTA-28-G3

How to read your Cummins/Onan engine serial & model number →

Common problems

15
  • STOPPING SET AT CONTROL PANEL SC-1609
  • Set-mounted circuit breaker tripped.
    Fix: The optional line circuit breaker mounts on the generator conduit box. If the load exceeds the circuit breaker current rating, the circuit breaker will trip.
  • REMOTE STOP lamp lights.
    Fix: This fault function is programmed to shut down the set immediately, as in the case of an Emergency Stop pushbutton. The nature and location of the fault is an optional selection that is determined when the set installation is designed. Refer to specifics of on-site equipment.
  • PRE LO OIL PRES lamp lights. Engine continues to operate.
    Fix: If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure. If engine can be stopped, follow procedure in step 5.
  • PRE Hi ENGINE COOLANT TEMP lamp lights. Engine continues to operate.
    Fix: If generator is powering non-critical and critical loads, and cannot be shut down, use the following: a. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. c. Open doors or windows in generator area to increase ventilation. If engine can be stopped, follow procedure in step 6.
  • PERMISSIVE AUTOMATIC START SWITCH SC-1610
  • LOW BATTERY VOLTAGE lamp lights.
    Cause: Poor battery cable connections: Clean the battery cable terminals and tighten all connections.
  • LO OIL PRES lamp lights. Engine shuts down.
    Cause: Indicates engine oil pressure has dropped to 12 psi (88 kPa).
    Fix: Check oil level, lines and filters. If oil system is okay but oil level is low, replenish. Reset control and restart. Contact your distributor if oil pressure is not in the range of 50 to 90 psi (345 to 620 kPa).
  • LO FUEL lamp lights.
    Cause: Indicates diesel fuel supply is running low.
    Fix: Check fuel supply and replenish as required.
  • LO ENG TEMP lamp lights.
    Cause: Indicates engine coolant heater is not operating (Lamp lights when engine coolant temperature is 70°F (21°C) or lower.).
    Fix: Since the lamp goes out after the engine warms up, there should be no cause for alarm if it remains lighted during initial generator set operation.
  • HI ENG COOLANT TEMP lamp lights. Engine shuts down.
    Cause: Indicates engine has overheated (engine coolant temperature has risen above 223°F/106°C) or coolant level is low (sets with coolant level sensor).
    Fix: Allow engine to cool down completely before proceeding with the following checks: a. Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check for a slipping fan belt, tighten if loose. d. Reset control and restart after locating and correcting problem. Contact your distributor if none of the above applies.
  • GEN SET UNDER LOAD lamp lights, when attempting to start generator set, EXCITER SWITCH trips to OFF position.
    Fix: Remove all loads from generator set. Reset Exciter Switch to ON position.
  • Engine will not crank.
    Cause: Also refer to LOW BATTERY VOLTAGE, step 15.
  • Engine starts from Manual Start controls but will not start automatically or from a remote panel.
    Cause: The Automatic Start switch must be in the Auto position for automatic or remote starting.
  • Engine runs and then shuts down, OVERSPEED lamp lights.
    Cause: Indicates engine has exceeded normal operating speed.
    Fix: Contact your distributor for service.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan VTA28-G3.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter—
Fuel filter—
Oil filter—
Battery—
Belt—
Coolant—
Oil—
Spark plug—

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

2
ItemActionHoursMonthsNotes
crankcase oilChange50 hrFirst service — Drain and replace the crankcase oil after the first 50 hours of operation on new generator sets (break-in)
Rupture basin leak detect switchTest12 moCheck once a year; in some areas weekly inspections may be required by safety code regulations

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceAngular alignment maximum T.I.R.0.001inch per inch of radius (center of shaft to indicator axis)measuring deflection to bolt heads
ClearanceClearance between exhaust pipes and combustible materials12inches (305 mm)minimum
ClearanceExhaust thimble diameter12inches (305 mm)larger than diameter of exhaust pipe
ClearanceFloat switch assembly float lift clearance below C-clip stop1/8inch (3 mm)use a feeler gauge
ClearanceGenerator-to-engine angular alignment (T.I.R.).001 in. per inch of radius (center of shaft to indicator axis), maximumin750 kW gensets and larger
ClearanceMounting base above floor6inches (152 mm)minimum for maintenance access
GapMPU sensor to flywheel ring gear toothback it out one quarter turnturnsensor threaded in until it just touches gear tooth
OtherAVR Droop setting5% at full load, 0 PF
OtherAVR voltage regulation (load regulation)approximately ±0.5% RMS
OtherAngular alignment maximum T.I.R..001 inches per inch of radiusin/incenter of shaft to indicator axis
OtherBattery specific gravity (high ambient, above 95F/35C)1.225recommended to reduce electrolyte loss
OtherBattery specific gravity (recharge threshold)below 1.260
OtherBattery specific gravity, fully chargedapproximately 1.260specific gravityat 80 F (27 C)
OtherFuel lift height limit6feet(1.8 meters) between fuel lift pump and bottom of dip tube
OtherGOV GAIN default value for paralleling applications70%
OtherGenerator frequency50 or 60Hzas nameplate rating
OtherMaximum cranking voltage drop2voltsdifference between battery and starter terminals while cranking
OtherOver/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal55Hzreset 53 Hz
OtherOver/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal65Hzreset 63 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal45Hzreset 47 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal55Hzreset 57 Hz
OtherOver/Under Voltage Sensor Module time delaytypically 25 percent, approximately 2.5seconds
OtherOvercrank cranking limit75secondsthree 15-second cranking cycles with two 15-second rest periods
OtherREG VHZ (underfrequency roll-off) adjustable range1 through 50; normal range 7 through 21
OtherStart delay adjustment range0 to 300seconds
OtherStop delay adjustment range0 to 600seconds
OtherUnder Frequency Roll Off (UFRO) knee point, 50 Hz units48 to 49Hz
OtherUnder Frequency Roll Off (UFRO) knee point, 60 Hz units58 to 59Hz
OtherUnder-frequency roll-off threshold (UFRO)typically 59 Hz for 60 Hz applications and 49 Hz for 50 Hz applicationsHzAVR UFRO pot preset
PressureEngine oil pressure - K19 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - K38 normal45-65psi (310-448 kPa)run mode
PressureEngine oil pressure - K50 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - L10/M11 normal30-50psi (207-345 kPa)run mode
PressureEngine oil pressure - NTA 855 normal35-50psi (241-345 kPa)run mode
PressureEngine oil pressure - V28 normal50-90psi (345-620 kPa)run mode
PressureEngine oil pressure shutdown limit - L10/M1120psi (138 kPa)run mode value
PressureEngine oil pressure shutdown limit - L10/M118psi (55 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1112psi (83 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1125psi (172 kPa)run mode value
PressureK19 engine idle oil pressure20psi (138 kPa)idle
PressureK19 engine normal oil pressure50-70psi (345-482 kPa)normal run
PressureK19 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureK38 engine idle oil pressure20psi (138 kPa)idle
PressureK38 engine normal oil pressure45-65psi (310-448 kPa)normal run
PressureK38 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureK50 engine idle oil pressure20psi (138 kPa)idle
PressureK50 engine normal oil pressure50-70psi (345-482 kPa)normal run
PressureK50 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureL10/M11 engine idle oil pressure15psi (103 kPa)idle
PressureL10/M11 engine normal oil pressure30-50psi (207-345 kPa)normal run
PressureL10/M11 oil pressure shutdown limit20psi (138 kPa)run mode value
PressureL10/M11 oil pressure shutdown limit8psi (55 kPa)idle mode value
PressureL10/M11 oil pressure warning limit12psi (83 kPa)idle mode value
PressureL10/M11 oil pressure warning limit25psi (172 kPa)run mode value
PressureLow oil pressure service limit while cranking10psiservice lubricating system if below
PressureLow oil pressure shutdownbelow 14psi (97 kPa)time delayed ~10 seconds following starter disconnect
PressureLow oil pressure shutdown threshold14psiless than this value shuts down
PressureLubrication priming pressure30psi (207 kPa)during system priming
PressureMaximum allowable exhaust back pressure41in H2O (10.2 kPa)maximum
PressureNTA 855 engine normal oil pressure35-50psi (241-345 kPa)normal run

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolantsoft water / E.G. / DCA mixtureCooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist).
FuelASTM No. 2 DieselCheck the engine manual for fuel specifications to determine acceptability. Never use galvanized or copper fuel lines, fittings or fuel tanks with diesel fuel systems.
FuelDieselDay tank fuel transfer pump maintains reservoir of diesel fuel in the day tank.
GreaseLithium based greaseMobilux No. 2 or Shell Alvania R32.74 oz (81 ml)Generator end bearing. Temperature range -22F to +248F (-30C to +120C). Grease should be equally divided between the bearing, bearing cap cavity, and bearing cartridge cavity.
GreaseLithium based grease, Mobilux No. 2 or Shell Alvania R3-30°C to 120°C2.74 oz (81 ml)End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

77
CodeNameMeaningSeverityAction
1FAULT 2 - INPUT NON-TIMEDEngine monitor TB2 terminal assignment
10PRE-HIGH ENGINE TEMPERATUREEngine monitor TB2 terminal assignment
101IDLE MODEIndicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.WarningRemove ground from engine idle input to return to normal speed and voltage.
102EMERGENCY STOPIndicates local or remote Emergency Stop.ShutdownTurn the switch clockwise and allow it to pop out (local only); move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can be reset only at the PCC front panel.
11PRE-LOW OIL PRESSUREEngine monitor TB2 terminal assignment
12SWITCH OFFEngine monitor TB2 terminal assignment
13LOW ENGINE TEMPERATUREEngine monitor TB2 terminal assignment
14LOW FUEL - INPUTEngine monitor TB2 terminal assignment
15LOW FUEL - OUTPUTEngine monitor TB2 terminal assignment
16SHUT-DOWNEngine monitor TB2 terminal assignment
2FAULT 2 - OUTPUT SHUTDOWNEngine monitor TB2 terminal assignment
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart.
204OIL PRES SENDERIndicates that the control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected.
210LOW COOLANT TEMPWarning occurs when engine coolant temperature is 70°F (21°C) or lower.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw.
211HIGH COOLANT TEMPIndicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary.WarningReduce load if possible; check air inlets and outlets and remove obstructions to airflow.
212HIGH COOLANT TEMPIndicates engine has overheated (coolant temperature has risen above the shutdown trip point: 215 F (102 C) - standby or 207 F (97 C) - primary).ShutdownCheck for obstructions to cooling airflow; check fan belt; check coolant mixture; check blower fan and circulation pumps; reset control and restart.
213COOLANT SENDERResistance of the coolant temperature sender is out of range.WarningCheck the resistance of the sender; should be 500 to 2k ohms.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningCheck coolant level in radiator and coolant recovery bottle; replenish if low; look for leaks.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.ShutdownAllow engine to cool; check coolant level and leakage points; reset control and restart.
220MAG PICKUPMag pickup speed indication is not being sensed or does not match generator set output frequency.ShutdownRestart and check RPM; check PCC model setting; inspect and test MPU.
221FAIL TO CRANKPossible fault with control or starting system.ShutdownCheck fuse F3 on the Engine Interface board; check battery cable connections; recharge or replace the battery.
222OVERCRANKPossible fuel system problem.ShutdownCheck for empty fuel tank, leaks, plugged fuel lines; replace dirty fuel or air filter; reset and restart.
223OVERSPEEDIndicates engine has exceeded normal operating speed. (115% ±1% of nominal).ShutdownCheck mechanical fuel linkage and governor module/digital board duty cycle.
224FAIL TO SYNCHRONIZEGenerator set has not synchronized to the system bus within the allowable time frame.WarningCheck governor system stability; adjust governing and synchronizer parameters; check fuel system.
226FAIL TO CLOSEParalleling breaker has been given a signal to close, but has not closed properly.ShutdownVerify breaker charging mechanism; check close signal; verify auxiliary contact signals.
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningRecharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningLower battery charger float level if applicable; check engine DC alternator.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningSee LOW DC VOLTAGE 230.
240LOW FUEL−DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.
241LOW FUELLow fuel signal received.WarningCheck fuel supply and replenish; check for short to ground in external wiring.
250EEPROM ERRORPCC memory error; data corruption of critical operating parameters.ShutdownPerform the initial start setup procedure; if the set shuts down on the same EEPROM ERROR message, replace the digital board (A32).
251EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningPerform the adjustment procedures; if the same message occurs, perform calibration procedures; if the message persists, replace the digital board (A32).
252EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningVerify values/choices selected and repeat the save operation; if the same message occurs, replace the digital board (A32).
260CUSTOMER FAULT 1When this customer defined input is closed to ground, the corresponding fault message is displayed. Programmable to initiate a shutdown or a warning.WarningIsolate source of false signal; repair external wiring or replace A34.
261GROUND FAULTWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningIsolate source of false signal; repair external wiring or replace A34.
262RUPTURE BASINWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningIsolate source of false signal; repair external wiring or replace A34.
263HIGH GEN TEMPWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningIsolate source of false signal; repair external wiring or replace A34.
270PHASE ROTATIONThe phase relationship between the generator set and the system bus is not matched.ShutdownVerify genset phase rotation matches bus; verify control wiring to bus PT module.
272FIRST STARTPowerCommand control is not receiving a proper signal from the system master first start sensor.WarningVerify Master First Start Sensor and interconnection wiring.
3FAULT 1 - INPUT TIMEDEngine monitor TB2 terminal assignment
301HIGH AC VOLTAGEOne or more phase voltages exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds.ShutdownSet display to GEN, VOLTS, L-N; determine if the output voltage the control sees is low or high; isolate PCC/alternator/excitation circuit.
303LOW AC VOLTAGEOne or more phase voltages dropped below 85% of nominal for 10 seconds.ShutdownCheck PMG/field wiring, rotating rectifier, load and connectors.
313UNDER FREQUENCYIndicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated.ShutdownCheck fuel supply, intake air supply and load.
320OVERCURRENTIndicates that generator output current has exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
321OVERCURRENTIndicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown.ShutdownCheck load and load lead connections.
322SHORT CIRCUITIndicates that generator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
330OVERLOADThree-phase power output exceeds 105% of standby (or 115% of prime) rating.WarningCheck load and load lead connections.
335REVERSE POWERPower is flowing into the generator set rather than out from the unit.ShutdownVerify CT connections, load sharing lines, and generator set frequency/voltage.
337LOSS OF EXCITATIONAlternator excitation system is improperly adjusted or has failed.ShutdownCheck output voltage calibration, load sharing lines, and leading power factor loads.
4FAULT 1 - OUTPUT SHUTDOWNEngine monitor TB2 terminal assignment
5LAMP TEST/RESETEngine monitor TB2 terminal assignment
6OVERCRANKEngine monitor TB2 terminal assignment
7OVERSPEEDEngine monitor TB2 terminal assignment
8HIGH ENGINE TEMPERATUREEngine monitor TB2 terminal assignment
9LOW OIL PRESSUREEngine monitor TB2 terminal assignment
FAULT 1Fault 1 (Red)Undedicated customer-defined fault; may be programmed as timed or non-timed shutdown or fault light only.ShutdownService as required by the customer-supplied fault indicating switches.
FAULT 2Fault 2 (Red)Undedicated customer-defined fault, same features as Fault 1.ShutdownService as required by the customer-supplied fault indicating switches.
GFGround Fault Alarm (Optional)Ground fault relay monitors neutral to ground connection and line to neutral, activating a fault alarm when the connection is broken or a ground fault is sensed.WarningClear fault condition by pushing the Run/Stop (Reset)/Remote switch to Reset (auto reset link set at factory).
HETHigh Engine Temperature (Red)Engine shut down because of excessively high engine coolant temperature (greater than 230 deg F).ShutdownCheck coolant level and leaks; service cooling system; reset engine control.
HI ENG TEMPHigh Engine TemperatureEngine shut down due to critically high coolant temperature (above 215F/102C).Shutdown
LETLow Engine Temperature (Yellow)Engine temperature is less than 70 deg F and the engine might not start.WarningPlug in, repair or install engine coolant and oil heaters.
LO FUELLow FuelFuel supply is marginally low, if equipped (Detector-12).Warning
LO OIL PRESLow Oil PressureEngine shut down due to critically low oil pressure (below 14 psi/97 kPa).Shutdown
LOPLow Oil Pressure (Red)Engine shut down because of excessively low engine oil pressure (less than 14 psi).ShutdownCheck oil level and oil leaks; service lubricating system; reset engine control.
LOW ENG TEMPLow Engine TemperatureEngine water jacket temperature is 70F/21C or lower; indicates possible inoperative coolant heater (Detector-12).Warning
LOW FUELLow Fuel (Yellow)Fuel level in the supply tank has dropped below the reserve necessary to run the set at full load for the prescribed number of hours.WarningFill the main fuel supply tank with the appropriate grade of fuel.
OCOvercrank (Red)Engine shut down because it did not start during the timed cranking period (approximately 75 seconds, including two rest periods).ShutdownService the set as necessary; reset engine control.
OSOverspeed (Red)Engine shut down because of overspeed.ShutdownAdjust the Electronic Overspeed Module; check governor for binding; reset engine control.
OVERCRANKOvercrankStarter locked out because of excessive cranking time (limited to 75 seconds).Shutdown
OVERSPEEDOverspeedEngine shut down because of excessive speed.Shutdown
PRE HI ENG TEMPPre-High Engine TemperatureCoolant temperature is marginally high (205F/97C or higher).WarningAttend to when generator set is shut down.
PRE LO OIL PRESPre-Low Oil PressureEngine oil pressure is marginally low (20 psi/138 kPa or less).WarningAttend to when generator set is shut down.
PRE-HETPre High Engine Temperature (Yellow)Engine coolant temperature is abnormally high (greater than 220 deg F).WarningShut down if possible or disconnect non-critical loads; service cooling system.
PRE-LOPPre Low Oil Pressure (Yellow)Engine oil pressure is abnormally low (less than 20 psi).WarningShut down if possible or disconnect non-critical loads; service lubricating system.
RUNRun (Green)Green lamp comes on when both primary and secondary starter circuits open after unit starts.Info
SWITCH OFFSwitch-off (Flashing Red)The Run/Stop/Remote switch is in the Stop position, preventing remote automatic operation.InfoPush the Run-Stop-Remote switch to Remote.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Aligning Generator with Engine (Angular Alignment) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
  5. Measure the distance from the center of the generator shaft to the indicator measuring point.
  6. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
  7. Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.

Tools: Dial indicator, Wooden shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point on capscrew head or flat surface of drive disc at bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Record maximum positive and negative dial indicator readings as the engine completes one revolution.
  5. T.I.R. equals the sum of the maximum positive and negative readings.
  6. Maximum T.I.R. should not be more than .001 inch for each inch of radius.
  7. Remove equal shims from under both generator mounting feet to lower the generator.
Angular Alignment Procedure (Generator to Engine) adjustment

⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.

⚠ Do not bar engine over by prying on fan blade.

Tools: dial indicator

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
  4. Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
  5. Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure (Generator to Engine) adjustment

Tools: dial indicator

  1. Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
  2. Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
  3. Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Governor Calibration Checks adjustment

Tools: Frequency meter or tachometer, Jumper wire

  1. Start the generator set.
  2. Adjust engine no-load speed to the desired allowable speed droop using the Run Speed potentiometer.
  3. With no load, turn GAIN clockwise slowly until engine speed oscillates.
  4. Reduce GAIN slowly counterclockwise until engine speed is stable.
  5. Upset the governor by momentarily shorting terminals 7 and 10 on the governor control.
  6. Apply and remove loads to check generator set response.
HC4-7 Axial Alignment Procedure adjustment

Tools: Dial indicator with magnetic base or clamp

  1. Check only when an objectionable vibration is present.
  2. Fasten dial indicator holding device to skid base, engine block, or generator shell with magnetic base or clamp.
  3. Position sensor point on the generator shaft hub.
  4. Bar the engine over in a clockwise rotation as viewed from engine flywheel through a couple of rotations.
  5. Record indicator readings in eight equally spaced points around the shaft diameter.
  6. Remove the capscrews connecting drive discs and flywheel and mark discs and flywheel.
  7. Rotate engine or generator so drive disc holes are repositioned 180 degrees from original location.
  8. Put capscrews back in and retorque. Recheck shaft alignment.
  9. If runout unchanged, rotate discs to 30, 60 or 90 degrees from original location.
  10. If T.I.R. does not improve, inspect flywheel pilot and drive disc runouts.
P7 Axial Alignment Procedure adjustment
  1. Check only when an objectionable vibration is present.
  2. Remove the capscrews connecting drive discs and flywheel.
  3. Mark the drive discs and flywheel with respect to each other.
  4. Rotate engine or generator so drive discs holes are repositioned two bolt holes from original location.
  5. Put capscrews back in and retorque. Recheck/record vibration levels.
  6. Repeat this test until drive disc holes are repositioned 180 degrees from original location.
  7. Review vibration data and position drive disc in lowest recorded level location.
UFRO Adjustments adjustment

⚠ Use an insulated handle screw driver to prevent electrical shock.

Tools: Insulated handle screwdriver, Frequency meter or tachometer

  1. Make a note of the no-load frequency.
  2. Determine roll-off frequency by turning the governor speed pot until the LED lights; if okay go to step 5.
  3. Adjust the governor speed pot to the proper roll-off frequency.
  4. Turn the UFRO pot until LED goes off, then slowly turn it back until the LED just goes on.
  5. Adjust the governor speed pot back to the initial frequency setting.
Voltage and Voltage Stability Adjustments adjustment

⚠ Touching uninsulated high voltage parts inside the control and power output boxes can result in severe personal injury or death.

Tools: Insulated handle screwdriver, AC voltmeter

  1. Use the control panel mounted voltage trimmer, if provided, for small voltage adjustments.
  2. Measure generator output voltage while running without load at nominal frequency.
  3. If trimmer is insufficient, lock it at midpoint.
  4. Turn the VOLTS pot fully counterclockwise and the STABILITY pot to its midpoint.
  5. If the red LED lights, refer to Jumper Reconnections and UFRO Adjustments.
  6. Turn the VOLTS pot clockwise until rated voltage is obtained.
  7. If voltage becomes unstable with a large load, turn the STABILITY pot clockwise until stable.
  8. Check and readjust the VOLTS pot each time the STABILITY pot is readjusted.
Generator/PCC Control Isolation Procedure diagnostic

⚠ HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.

Tools: Voltmeter, Jumpers, 12 volt battery

  1. Throw the line circuit breaker OFF and shut down the set.
  2. Remove accessory box cover; remove plug P10 from A37 J10.
  3. Prepare to measure output voltage across generator terminals.
  4. Connect 12V battery jumpers to X (P10-6 red) and XX (P10-3 brown).
  5. Check polarity; incorrect polarity makes the test inconclusive.
  6. Start set and connect battery negative to the XX lead.
  7. Rated or higher balanced voltage means generator circuitry is OK.
  8. Unbalanced voltage: troubleshoot main stator; low voltage: exciter/field.
Insulation Resistance (Megger) & Polarization Index (PI) Testing diagnostic

⚠ The windings of medium-voltage (601 through 15,000 volts) generator sets must be dry before the generator is operated.

Tools: Megger or insulation resistance meter, Grounding cluster, High voltage gloves

  1. Perform the Generator Set Grounding Procedure.
  2. Disconnect plug J10 from A37 and AC control leads 4,5,6,7,8.
  3. If RTD option installed, ground all six RTD temperature leads (18 leads).
  4. Perform Insulation Resistance Test and PI Test for desired windings.
  5. Megger test: apply voltage for up to one minute.
  6. PI test: apply voltage for ten minutes; record 1-minute and 10-minute readings.
  7. PI ratio of 2 or greater is good for new and in-service sets.
  8. Investigate and correct low readings before returning set to service.
Megger and PI Test diagnostic

⚠ Medium-voltage (601 to 15,000 volts) windings must be dry before the generator is operated.

Tools: Megger or Insulation Resistance Meter, Wheatstone bridge or digital ohmmeter, Grounding Cluster

  1. Perform the Generator Set Grounding Procedure.
  2. Disconnect plug J10 from the voltage regulator output module and the AC control leads (marked 4, 5, 6, 7, 8).
  3. If RTD option installed, ground all six RTD temperature leads (18 leads total).
  4. Perform the Winding Resistance Test for the desired windings.
  5. Perform the Insulation Resistance (Megger) Test and PI Test for the desired windings.
  6. Megger test: apply voltage for up to one minute.
  7. PI test: apply voltage for ten minutes; record resistance at one minute and ten minutes.
  8. PI is the ten-minute reading divided by the one-minute reading; ratio of two or greater is good.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12 lead generator setsLoad wires are routed through the CTsReconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage).
6 lead generator setsGenerator output leads are routed through the CTsNon-reconnectable gensets (6 leads) have single secondary CTs (2 pins).
Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F)Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100).
A (U)CT21U load leads (A phase)CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground.
B (V)CT22V load leads (B phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
C (W)CT23W load leads (C phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
110/1803Reconnection diagram (Figure 5-2); 50 Hz
110/2201Reconnection diagram (Figure 5-2); 50 Hz
118/2003Reconnection diagram (Figure 5-2); 50 Hz
118/2303Reconnection diagram (Figure 5-2); 50 Hz
120/2083Reconnection diagram (Figure 5-2); 60 Hz
120/2401Reconnection diagram (Figure 5-2); phase sequence U-V-W
127/2203Reconnection diagram (Figure 5-2); 60 Hz
220/3803Reconnection diagram (Figure 5-2); 60 Hz
230/4003Reconnection diagram (Figure 5-2); 50 Hz
240/4163Reconnection diagram (Figure 5-2); 60 Hz
254/4403Reconnection diagram (Figure 5-2); 60 Hz
277/4803Reconnection diagram (Figure 5-2); 60 Hz
347/6003Reconnection diagram (Figure 5-2); 60 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan VTA28 family

119
Part #DescriptionCategory
140-2301Cleaner, Air (Includes Replacement Elements) 140−2465Air filter
140-3288-02Cleaner, AirAir filter
140-3349-02Bracket, Air CleanerAir filter
M-1627BOLT DIAGRAMBattery
130-3839-01Guard, Belt − Right SideBelt
130-3839-02Guard, Belt − Left SideBelt
130-3840Guard, Belt − TopBelt
130-3841Guard, Belt − BottomBelt
130-3842Guard, Belt − FrontBelt
130-3843Guard, Belt − Right SideBelt
130-3844Guard, Belt − Bottom BackBelt
130-3845Guard, Belt − Top BackBelt
130-3846Guard, Belt − Left SideBelt
511-0105Belt−VBelt
M-1761AIR CLEANERSCleaner
EXS-1583-3CONTROL HEATERControl heater
960-0630CPCC2100 PowerCommand ControlController
CS-1075-1COOLANT FILTERSCoolant filter
CS-1367-2TYPICAL COOLANT HEATERCoolant heater
0300-4623-18DFGB (600V)Current transformer
0300-4623-34DFGB BR (0-480V)Current transformer
ES-1779-1VOLTAGE REGULATOR AND EXCITATION SWITCHExcitation switch
FS1304FILTERFilter
130-4552Cover, Coolant HeaterFluid
333-0407-05Heater, Oil (300 Watt, 480 Volt)Fluid
502-1337Adapter, Coolant HeaterFluid
FF202Fuel, Spin-OnFuel filter
FS1216Fuel/Water Sep Spin-OnFuel filter
130-1193Gasket, Outlet AdapterGasket
130-4354Radiator (Includes Cap, Sight Gauge And Overflow Hose) (Also Includes Cover Plates, Gaskets, Screws And Lock Washers For All Water Outlets)Gasket
330-0141-04Gasket, CoverGasket
330-0142Box, Terminal (Includes Cover and Gasket − Ref No. 19 and 20)Gasket
128-0108Insulation, Hose – Bulk (Order By The Foot – 12 Feet Required)Hose
130-3874Base, Mounting * − Parts Used On Heat Exchanger Installations With Automatic Water Regulator + − Parts Used On Heat Exchanger Installations Without Automatic Water Regulator # − Cut Off And Discard Swivel Connector End Of Hose So That 1/8 NPT Connector End Measures Length As Indicated AboveHose
130-3875Tube, OutletHose
130-4576TubeHose
130-4577TubeHose
130-4581TubeHose
416-0680Cable, Battery (10")Hose
501-0537-22Hose, Oil (86”)Hose
501-0537-23Hose, Oil (22”)Hose
501-0744-01Hose, CoolantHose
501-0744-05Hose, CoolantHose
502-0313Elbow, Hose − 90° (1/8” Pipe to 1/4” Hose)Hose
502-0395Connector, HoseHose
502-0971Connector, HoseHose
502-1530Union, Hose (1”) − NylonHose
502-1531Connector, HoseHose
503-0189Clamp, HoseHose
503-0249Hose − Bulk (Order by the Foot − 3 Feet Required)Hose
503-0569Hose (3−1/2” ID) Bulk (Order By The Foot − 2 Feet Required)Hose
503-0685Clamp, HoseHose
503-0856Hose, Radiator − Lower (3−1/2” ID x 5−1/2”)Hose
503-1418Hose − Bulk (1/4” ID) (Order By The Foot − 18 Feet Required)Hose
503-1620Hose – Bulk (3/8" ID) (Order by the Foot)Hose
503-1634Hose, Silicon RubberHose
503-1634-01Hose, Rubber (3/4” ID x 4”)Hose
503-1728Hose (3” ID x 5–1/2”)Hose
503-1779Hose − Bulk (1” ID) (Order By The Foot − 1 Foot Required)Hose
503-1870-07Clamp, HoseHose
503-1870-11Clamp, HoseHose
503-1870-12Clamp, HoseHose
503-1870-14Clamp, HoseHose
503-1872-01Clamp, HoseHose
503-1872-05Clamp, HoseHose
503-1872-07Clamp, HoseHose
503-2157-01Clamp, HoseHose
503-2276Elbow, HoseHose
503-2350-04Hose, Coolant (1” x 5‘)Hose
503-2350-05Hose, Coolant (1” x 8‘)Hose
505-0759Adapter − Pipe to Hose (1” x 1”)Hose
518-0548-20Clamp, HoseHose
518-0548-24Clamp, HoseHose
122-0702Head, Oil FilterOil filter
122-0777Filter, Lube OilOil filter
098-7954Label, Information − Element ReplacementService part / kit
102-1335Plug, Oil DrainService part / kit
130-1430Exchanger, HeatService part / kit
130-1515Tank, WaterService part / kit
130-4582Bracket, MountingService part / kit
130-5666-02Tube, Water HeaterService part / kit
130-5852-02Tube, Water HeaterService part / kit
140-1260Fitting, Safety FilterService part / kit
140-1260-01Fitting, Safety FilterService part / kit
193-0128Gauge, Fuel Pressure (0-200 Lbs)Service part / kit
307-2621-02Relay, Start Solenoid (K4)Service part / kit
307-2859Relay, Power - 24VDC (K11)Service part / kit
323-1491* Pin, Contact (Used With Inline G)Service part / kit
323-1492* Socket, Contact (Used In Stations 18, 19)Service part / kit
323-1718* Pin, Contact (Used In Station 17)Service part / kit
332-2634Clamp, HoseService part / kit
333-0639-01Heater, Coolant (4990 Watt)Service part / kit
333-0639-02Heater, Coolant (6420 Watt)Service part / kit
416-0446Cable, Battery - JumperService part / kit
504-0171Valve, ShutoffService part / kit
505-0100Nipple, Pipe - Close (1/2”)Service part / kit
505-1071Coupling, Flexible (For 2" Pipe)Service part / kit
505-1072Valve, WaterService part / kit
518-0548-42Clamp, Retainer 4 Prior To December 1996 Production (Mounted On Top And Side Of Control Box Wrapper)Service part / kit
870-0257Nut, Locking (5/16−18) * − Parts Used On Heat Exchanger Installations With Automatic Water Regulator # − Cut Off And Discard Swivel Connector End Of Hose So That 1/8 NPT Connector End Measures Length As Indicated Above + − Parts Used On Heat Exchanger Installations Without Automatic Water RegulatorService part / kit
898-1254-25Sleeving – Heater Leads (59”)Service part / kit
EXS-1036-1RAIN CAPService part / kit
M-1808-4TYPICAL INSTALLATIONService part / kit
M-CK4911685PCylinder KitService part / kit
MCB4911685Piston KitService part / kit
M-1759INJECTION PUMPPump
323-1445* Seal, Cable (Used With Station 17)Seal
508-0292Washer, Sealing - CopperSeal
151-0411Pickup, MagneticSensor
193-0432Sender, Oil Temperature (S2 Engine Block, E4 Oil Pan)Sensor
193-0444Sender, Oil Pressure (S1)Sensor
193-0468Sender, Low Coolant Level (S7)Sensor
193-0481Sender Assembly - Low Coolant LevelSensor
193-0529-01Sender, Oil TemperatureSensor
309-0269Sender, Temperature-Lo EngineSensor
M-1760PRE-HIGH AND HIGH COOLANT TEMPERATURE SENSORSensor
960-0504PCC Control Service ManualService manual
960-0507Detector Control Service ManualService manual
309-0649Thermostat (Includes Connector Socket) (S11)Thermostat

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan VTA28-G3?

The Cummins/Onan VTA28-G3 engine has an oil capacity of 84.0 liters.

What is the displacement of the Cummins/Onan VTA28-G3?

The Cummins/Onan VTA28-G3 has a displacement of 28.0 liters.

Which generators use the Cummins/Onan VTA28-G3 engine?

The Cummins/Onan VTA28-G3 powers 2 generator set(s), including Cummins/Onan DFGC, Cummins/Onan VTA-28-G3.

What is a common problem with the Cummins/Onan VTA28-G3 engine?

A commonly reported issue on generators using the Cummins/Onan VTA28-G3 is: STOPPING SET AT CONTROL PANEL.