PCC0300 Controller

The PCC0300 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the C15 D5, C15 D6, C22 D5 and C25 D6.

4
Generator sets
Cummins/Onan
Brand
15–25 kW
Power range
Diesel
Fuel

Engines paired with this controller

2

Troubleshooting

31

Fault codes

CodeMeaning
Code 135Oil Pressure Sensor OOR - High
Code 141Oil Pressure Sensor OOR - Low
Code 143Engine Oil Pressure Low (Warning)
Code 144Engine Coolant Temperature OOR Low (Warning)
Code 145Engine Coolant Temperature OOR High (Warning)
Code 146Engine Coolant Temperature Above Normal (Warning)
Code 151Engine Coolant Temperature High (Shutdown)
Code 234Engine Speed High (Shutdown)
Code 359Engine Fail to Start
Code 415Engine Oil Pressure Low (Shutdown)
Code 441Low Battery Voltage
Code 442High Battery Voltage

Symptoms & remedies

SymptomRemedy
Batteries can explodeDo not dispose of the battery in a fire, because it is capable of exploding. Do not open or mutilate the battery. Do not charge frozen batteries. Batteries present the risk of high short circuit current when servicing the generator set: remove watches, rings, or other metal objects; use tools with insulated handles.
DizzinessIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Emergency stop signal is receivedThe generator set immediately shuts down and cannot run or crank with the E-stop switch engaged.
Exhaust gases are deadlyProvide an adequate exhaust system to properly expel discharged gases away from enclosed or sheltered areas, and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust system daily for leaks per the maintenance schedule. Ensure that exhaust manifolds are secured and not warped. Do not use exhaust gases to heat a compartment. Make sure the unit is well ventilated.
Fuel contact with hot engine or exhaustDo not permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source near the generator set or fuel tank. Fuel lines must be adequately secured and free of leaks. Use an approved flexible line for fuel connection at the engine. Do not use copper piping on flexible lines as it will become brittle if continuously vibrated or repeatedly bent. Ensure all fuel supplies have a positive shutoff valve.
High coolant temperature warning/shutdownLevel is pre-set to match the capabilities of the engine used. Control includes time delays to prevent nuisance shutdown signals.
Inability to Think CoherentlyIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Low coolant temperature warningIndicates that engine temperature may not be high enough for 1 min. and start or proper load acceptance.
Low lube oil pressure warning/shutdownLevel is pre-set to match the capabilities of the engine used. Control includes time delays to prevent nuisance shutdown signals.
Muscular TwitchingIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Over/under frequency sensor overfrequency sensing dropout adjustable from 105-115% of nominalDropout adjustable delay from 0.1-15 sec.
Over/under frequency sensor underfrequency sensing pickup and dropout adjustable from 85-100% and 70-85%Dropout adjustable delay from 0.1-15 sec.
Overvoltage sensor dropout adjustable from 105-135% of nominalDropout adjustable delay from 0.5-120 sec.
Sensor failure indicationLogic is provided on the base control to detect analog sensor or interconnecting wiring failures.
Time delay of 0-600 seconds prior to shutdown after signal to stop in normal operation modesDefault for both time delay periods is 0 seconds.
Time delay start and stop (cooldown) configurable for time delay of 0-300 seconds prior to starting after receiving a remote start signalControl provides retransfer time delays including time delay emergency to normal (0-1800 sec), programmed transition delay (0-600 sec), and time delay engine cooldown (0-3600 sec).
Undervoltage sensor pickup and dropout adjustable from 85-100% and 75-98%Dropout adjustable delay from 0.1-30 sec.
VomitingIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Weakness and SleepinessIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.