Home›Controllers›InteliGen NTTMdigital

InteliGen NTTMdigital Controller

The InteliGen NTTMdigital is a generator-set controller. It is used on generator sets from Generac, including the MGG280.

1
Generator sets
Generac
Brand
162–162 kW
Power range
Bi-Fuel (NG/LP)
Fuel

Generator sets using this controller

1

Engines paired with this controller

1

Troubleshooting

27

Fault codes

CodeMeaningCauseRemedy
Al/Hist. msg 1-16Al/Hist. msg 1-16 activity indication (Al/Hist. msg means Alarm/History message)Al/Hist. msg can be used as a customized message for additional protection configured to any controller internal value. See GenConfig manual - Protections
Batt voltIndication of battery voltage protection activityThis protection is based on Analog protect: Batt >V, Batt <V, and Batt volt del setpointsCheck if engine alternator or independent battery charger works properly
ECUIndication of error in communication with ECUCheck if the ECU is: correctly connected to the CAN1 port of the controller (refer to Comap Electronic Engines Support manual for information about ECU connection); powered up; terminating resistors are properly connected; the CAN bus Low and High wires are not swapped
ECUDiagBlockedAlarm is active when Comms settings: ECU diag = DISABLED. This setting means that ECU alarms are not displayed and considered by controller and this alarm is the setting notification
EarthFaultCurrIndication of Earth fault current protection activityThis protection is based on Gener protect: EarthFaultCurr and EthFltCurr del setpoints. Setpoint EarthFltCurrCT from Basic settings group of setpoints is related to this protection too
Gen I unbalGenerator voltage unbalance alarmBased on Gener protect: Gen V unbal and Gen V unb del setpoints
Gen V unbalGenerator voltage unbalance alarmBased on Gener protect: Gen V unbal and Gen V unb del setpoints. The voltage unbalance is calculated as a maximum difference between phase voltages
RTCbatteryFlatThis warning message "RTCbatteryFlat" appears in Alarmlist when battery is close to be completely flatIf power supply cut comes when the RTC battery is flat, the statistic values, history and setpoints settings are lostSend a controller to your distributor for battery exchange if the RTCbatteryFlat message is displayed
SHAinCfgErrShared Analog module configuration errorMore than one source module (SHAOUT) were configured (on the CAN2 bus)Make sure that only one SHAOUT x module is configured in controllers
Wrong configWrong controller configuration indication. Indicates that controller hardware doesn't support PLC used in configurationTo check it send the IDch and Dngl strings from controller Info screen 2 and archive to your technical support

Symptoms & remedies

SymptomCauseRemedy
Controller Cannot Be "Reset"Engine not stoppedVerify the engine is at a complete stop before trying to reset
Controller Does Not Power Up Even With Correct DC Power AppliedWiring mistakeCheck that there are no wiring errors/short circuits connected to the controller
Electrical Shock When Frame Is TouchedStatic chargeGround unit frame at local reference ground
Engine Alarms Are On For High Engine Temperature Or Low Oil Pressure When Engine Is Operating ProperlyWrong temp or pressure calibrationVerify the engine mounted senders have correct resistance values for corresponding input temperature or pressure. Verify calibration
Engine Cranks But Will Not StartNo fuelCheck that fuel valves are open
Engine OverheatsExcessive loadRemove one or more electrical loads
Engine Starts But Will Not Run SmoothlyFuel or ignition problemRefer to engine manual. Contact Generac Mobile Products Technical Service
Engine Temperature Or Oil Pressure Display Is IncorrectFailed engine sensorVerify engine sensors. NOTE: Engine sensors must be factory supplied units only
Engine Will Not Crank (Electric Start)Dead batteryRemove batteries and trickle charge. Never jump start. Even if only one battery is bad, it is recommended that both batteries be replaced at the same time
High Output VoltageExcessive speed (fixed speed mode)Check engine for malfunction. Verify engine RPM
Keypad Buttons (Switches) Do Not OperateKeypad not connected to controllerVerify the interconnecting ribbon cable between the lexan faceplate and main printed circuit board is correctly connected. Replace controller if failed
LCD Display Cannot Be ViewedImproper supply voltageCheck DC supply voltage at terminals B+ & B- (10-30VDC)
Mechanical NoiseInternal failure of alternatorContact service
No "RUN" Output Signal"Shutdown Faults" not resetAll shutdown faults must be reset (red shutdown LED must be off)
No Output VoltageCircuit breaker tripped or failedReset circuit breaker or replace if required
Overspeed Shutdown Occurs At Normal SpeedController programmed values are wrong or controller has failedVerify the controller programmed values are correct for the number of flywheel teeth, nominal RPM, and overspeed set point percentage. Replace controller if failed
Voltage Or Current Metering Is IncorrectController programmed values are wrongVerify the controller programmed values are correct for the voltage sensing PT ratio and/or current sensing CT ratio