Home›Engines›Power Solutions International D146TIC

Power Solutions International D146TIC Engine

The Power Solutions International D146TIC is a 14.62 L turbo cac engine rated at 1800 rpm. It powers generator sets from Generac, including the MGG280. It holds 10.1 L (2.7 gal) of oil and 38 L (10.0 gal) of coolant.

Also known as: PSI D146TIC

14.62 L
Displacement
1800 rpm
Rated speed
10.1 L
Oil capacity

Engine specifications

Oil capacity10.1 L
Coolant capacity38.0 L
Displacement14.62 L
AspirationTurbo CAC
Rated speed1800 rpm

Generator sets powered by this engine

1

Common problems

15
  • Engine Cranks But Will Not Start
    Cause: No fuel
    Fix: Check that fuel valves are open
  • Voltage Or Current Metering Is Incorrect
    Cause: Controller programmed values are wrong
    Fix: Verify the controller programmed values are correct for the voltage sensing PT ratio and/or current sensing CT ratio
  • Mechanical Noise
    Cause: Internal failure of alternator
    Fix: Contact service
  • No Output Voltage
    Cause: Circuit breaker tripped or failed
    Fix: Reset circuit breaker or replace if required
  • No "RUN" Output Signal
    Cause: "Shutdown Faults" not reset
    Fix: All shutdown faults must be reset (red shutdown LED must be off)
  • LCD Display Cannot Be Viewed
    Cause: Improper supply voltage
    Fix: Check DC supply voltage at terminals B+ & B- (10-30VDC)
  • Generator voltage unbalance alarm Gen V unbal
    Cause: Based on Gener protect: Gen V unbal and Gen V unb del setpoints. The voltage unbalance is calculated as a maximum difference between phase voltages
  • Engine Will Not Crank (Electric Start)
    Cause: Dead battery
    Fix: Remove batteries and trickle charge. Never jump start. Even if only one battery is bad, it is recommended that both batteries be replaced at the same time
  • Engine Temperature Or Oil Pressure Display Is Incorrect
    Cause: Failed engine sensor
    Fix: Verify engine sensors. NOTE: Engine sensors must be factory supplied units only
  • Engine Overheats
    Cause: Excessive load
    Fix: Remove one or more electrical loads
  • Electrical Shock When Frame Is Touched
    Cause: Static charge
    Fix: Ground unit frame at local reference ground
  • Controller Does Not Power Up Even With Correct DC Power Applied
    Cause: Wiring mistake
    Fix: Check that there are no wiring errors/short circuits connected to the controller
  • Controller Cannot Be "Reset"
    Cause: Engine not stopped
    Fix: Verify the engine is at a complete stop before trying to reset
  • Wrong controller configuration indication. Indicates that controller hardware doesn't support PLC used in configuration Wrong config
    Fix: To check it send the IDch and Dngl strings from controller Info screen 2 and archive to your technical support
  • This warning message "RTCbatteryFlat" appears in Alarmlist when battery is close to be completely flat RTCbatteryFlat
    Cause: If power supply cut comes when the RTC battery is flat, the statistic values, history and setpoints settings are lost
    Fix: Send a controller to your distributor for battery exchange if the RTCbatteryFlat message is displayed

Compiled from service & troubleshooting documentation across every generator set that uses the Power Solutions International D146TIC.

Maintenance schedule

ItemSpecCapacityPart #Interval
Coolant50/50 mix of coolant and water44.0 qt (L)—
OilSAE 15W-40 low ash, API CD/CF or higher11.1 qt (L)—250 hr
Spark plugGap 0.015 in (0.4 mm)—

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

1
ItemActionHoursMonthsNotes
Engine Oil and Filter (initial)Change50 hrFirst service — Initial oil and filter change after first 50 hours or first 3 months

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

1
TypeItemValueUnitCondition
GapSpark plug gap0.015in (0.4 mm)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50/50 mix of coolant and waterMGG280N2 38 qt (43.2 L) incl. engine; MGG350N2 44 qt (50.0 L) incl. engine
Engine oilSAE 15W-40 low ashAPI CD/CF or higherMGG280N2 10.1 qt (38.1 L) incl. filter; MGG350N2 11.1 qt (42.1 L) incl. filter

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Power Solutions International D146TIC?

The Power Solutions International D146TIC engine has an oil capacity of 10.1 liters.

What is the displacement of the Power Solutions International D146TIC?

The Power Solutions International D146TIC has a displacement of 14.62 liters.

Which generators use the Power Solutions International D146TIC engine?

The Power Solutions International D146TIC powers 1 generator set(s), including Generac MGG280.

How often should you change the oil in the Power Solutions International D146TIC?

The Power Solutions International D146TIC oil change interval is every 250 hours.

What is a common problem with the Power Solutions International D146TIC engine?

A commonly reported issue on generators using the Power Solutions International D146TIC is: Engine Cranks But Will Not Start. Cause: No fuel. Fix: Check that fuel valves are open.