Engine Monitor Controller

The Engine Monitor is a generator-set controller. It is used on generator sets from Cummins/Onan, including the 50.0 DDB 15R.

5
Generator sets
Cummins/Onan
Brand
50–300 kW
Power range
Diesel
Fuel

Generator sets using this controller

5

Also fitted to: Cummins/Onan 200 DFP 17R (60 Hz), Cummins/Onan 230 DFP 17R (60 Hz), Cummins/Onan DFS 17R / 60Hz, Cummins/Onan DFS 517R / 50Hz.

Engines paired with this controller

2

Troubleshooting

29

Symptoms & remedies

SymptomCauseRemedy
Engine runs, shuts down and cranks for 75-seconds. Cranking cycle stops; fault lamp lightsCheck fuel supply
Engine runs, shuts down and cranks for 75-seconds; cranking cycle stops; fault lamp lightsFuel supplyCheck fuel supply.
Engine runs, shuts down, cranks for 75-seconds, cranking cycle stops, overcrank light ONFuel supplyCheck fuel supply.
Engine stops cranking and fault lamp lights, after cranking approximately 75 secondsSee engine service manual for troubleshooting fuel system; after correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset, then back to the required running position.
Fault lamp lights - no fault condition existsBe certain that no fault condition exists; Disconnect lead 29, 30 and 31 from TB11 inside control box (refer to wiring diagram); If fault lamp still lights with leads disconnected, remove and replace engine monitor plug-in printed circuit board
Fault lamp lights after engine is runningOil level - engine will shut down after approximately 12-1/2 seconds if low oil pressure sensor does not openCheck oil level
Fault lamp lights and engine shuts down after running for a periodOil level (engine will shut down if sensor is closed)Check oil level.
Fault lamp lights and engine stops cranking after approximately 75 secondsSee engine service manual for troubleshooting fuel system; After correcting fault, reset monitor by moving run-stop/reset-remote switch to reset position, then to either run or remote to restart engine
Fault lamp lights immediately after engine startsOverspeed condition as engine startsCheck for overspeed condition as engine starts
Fault lamp lights, no fault existsTo check a no-fault condition, disconnect leads from TB11 terminals 29, 30 and 31; if fault lamp lights with leads disconnected, replace engine monitor board; reconnect leads.
High engine temperature fault lamp lights - no fault condition existsBe certain that no fault condition exists; Remove lead 31 from TB11 inside control box (refer to wiring diagram); If high engine temperature lamp still lights, remove and replace engine monitor plug-in printed circuit board
High engine temperature lamp lights after engine is runningDefective thermostat/thermostatsCheck for defective thermostat/thermostats
High engine temperature lamp lights as soon as engine startsDefective sensor or actual high temperature conditionCheck for defective sensor or actual high temperature condition
High engine temperature light ON, no shutdownDisconnect wire at TB11-31; light ON after relay reset — replace engine monitor board.
High engine temperature light ON. No shutdownDisconnect wire at TB11-31; Light ON after relay reset; Replace engine monitor board
High engine temperature shutdownCoolant levelCheck coolant level; replenish if necessary.
Low oil pressure fault lamp lights - no fault condition existsBe certain that no fault condition exists; Disconnect lead 30 from TB11 inside control box (refer to wiring diagram); If low oil pressure lamp still lights, remove and replace engine monitor plug-in printed circuit board
Low oil pressure lamp lights after engine is runningOil level - engine will shut down after approximately 12-1/2 seconds if oil pressure is lowCheck oil level
Low oil pressure light ON, no shutdownDisconnect wire at TB11-30; light ON after relay reset — replace engine monitor board.
Low oil pressure light ON. No shutdownDisconnect wire at TB11-30; Light ON after relay reset; Replace engine monitor board
Low oil pressure shutdownOil levelCheck oil level; replenish if necessary.
Non-Start: engine fails to start after a few seconds of cranking, or starts and runs then stops and fault lamp lightsRefer to appropriate troubleshooting chart, Table 3 or Table 4
Overcrank fault lamp lights after engine has run for approximately 75 secondsReplace start-disconnect circuit board
Overcrank fault lamp lights and engine stops cranking after approximately 75 secondsSee engine service manual for troubleshooting fuel system; After correcting fault, reset monitor by moving run-stop/reset-remote switch to reset position, then to either run or remote to restart engine
Overcrank fault lamp lights and engine stops cranking after approximately 75-secondsSee engine service manual for troubleshooting fuel system; after correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position.
Overspeed lamp lights - no fault condition existsReplace overspeed circuit board
Overspeed light on, no shutdownDisconnect wire at TB11-29; light on after reset — replace engine monitor board.
Overspeed shutdownGovernor and throttle linkages, overspeed switchCheck governor and throttle linkages for freedom of movement; check overspeed switch.
When pressing test lamp button - one or more fault lamps do not lightFault lamp/lamps burned outReplace

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.