The Electronics Model DSE8610 MKII is a generator-set controller. It is used on generator sets from Generac, including the MDE330.
| Symptom | Cause | Remedy |
|---|---|---|
| Emergency Stop indicator LED is illuminated. | Emergency Stop switch is active (pushed in). | Deactivate (pull out) Emergency Stop switch. |
| Low Load indicator LED is illuminated. | Genset has operated at less than 30% capacity for more than 15 minutes. | Increase electrical load. If unable to operate genset at more than 30% load, use a smaller generator. |
| Lug Door Open indicator LED is illuminated. | Lug-box door is open. | Close lug-box door. If condition remains unresolved, inspect lug-box door safety switch for proper operation. |
| Shutdown indicator LED is illuminated. | Resolve shutdown condition. |
Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.