DSE702 Controller
The DSE702 is a generator-set controller. It is used on generator sets from Hipower, including the HRJW 75 T6.
Specifications
| Digital inputs | ["Remote Start Input", "Low Oil Pressure Input", "High Engine Temp Input"] |
|---|
| Relay outputs | ["Start relay Output", "Fuel relay Output", "Preheat Output relay"] |
|---|
| Supply voltage | 8 Volts to 35 Volts DC Continuous |
|---|
| Operating temperature | -30C to + 700C |
|---|
| Dimensions | 84mm x 72mm x 34.9mm (3.3” x 2.8” x 1.4”) |
|---|
| Protections | ["Shutdown on high engine temperature", "Immediate shutdown on overspeed", "Shutdown on underspeed"] |
|---|
Troubleshooting
7Fault codes
| Code | Meaning | Cause |
|---|
| FAIL TO START | FAIL TO START | if the engine does not fire after the pre-set 3 attempts at starting, a shutdown will be initiated |
| HIGH ENGINE TEMPERATURE | HIGH ENGINE TEMPERATURE | |
| LOW OIL PRESSURE | LOW OIL PRESSURE | if the module detects that the engine oil pressure has fallen below the low oil pressure switch after the Safety On timer has expired |
Symptoms & remedies
| Symptom | Cause |
|---|
| BATTERY CHARGE FAILURE | if the module does not detect a voltage from the warning light terminal on the auxiliary charge alternator |
| Engine coolant temperature has exceeded the high engine temperature switch after the Safety On timer has expired | |
| Overspeed, if the engine speed exceeds the pre-set trip (14% above the nominal frequency) a shutdown is initiated. Overspeed is not delayed, it is an immediate shutdown. | |
| Underspeed, if the engine speed falls below 20Hz (fixed) after the Safety On timer has expired, a shutdown is initiated. | |
Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Extracted directly from this controller's manual.