ADC 2100 Digital Controller

The ADC 2100 Digital is a generator-set controller. It is used on generator sets from Kohler, including the 15RES and 30RES.

2
Generator sets
Kohler
Brand
15–30 kW
Power range
Bi-Fuel (NG/LP)
Fuel

Generator sets using this controller

2

Engines paired with this controller

1

Troubleshooting

3

Symptoms & remedies

SymptomRemedy
Battery short circuitsDisconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Gas fuel leaks can cause an explosion.Check the LPG vapor or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
LPG liquid withdrawal fuel leaks can cause an explosion.Check the LPG liquid withdrawal fuel system for leakage by using a soap and water solution with the fuel system test pressurized to at least 90 psi (621 kPa). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.