A6060) Controller

The A6060) is a generator-set controller. It is used on generator sets from Generac, including the 0940 and 0941.

4
Generator sets
Generac
Brand
2
Fuel types

Generator sets using this controller

4
Generac 0940Generac 0941

Also fitted to: Generac 00940-2 / Impact-36G plus II, Generac 00941-2 / Impact-36LPG plus II.

Engines paired with this controller

2

Troubleshooting

21

Symptoms & remedies

SymptomCauseRemedy
Engine cranks but will not startFuel level lowReplenish fuel supply
Engine does not accelerate when load is appliedCarburetor linkage sticking with throttle stuck closedRepair sticking throttle
Engine shuts down under loadOil pressure lowSee Section 5.1, ENGINE OIL SYSTEM
Engine speed and AC output voltage erratic under constant load. AC output does not turn off intermittentlyStepper Motor failureReplace Stepper Motor
Engine speed is maintained and no-load voltage is good. However, when load is applied output voltage dropsCarburetor linkage sticking with throttle partly openRepair sticking throttle
Engine starts but Stepper Motor does not move. Shut down occurs after several secondsStator Timing winding is openRepair/replace bad wire(s) TIM1/TIM2 or replace Stator
Engine starts hard and runs roughBadly fouled spark plugClean and regap or replace spark plug as necessary
Engine starts then shuts down after a few secondsOil pressure switch defective or Wire 85 circuit faultReplace oil pressure switch if it is defective or repair Wire 85 circuit as necessary
Engine starts, accelerates, shuts down at 4500 rpmCarburetor linkage sticking with throttle stuck openRepair sticking throttle
Engine will not crankBlown 7.5 amp fuseReplace the fuse
Generator circuit breaker trips / no AC voltageShort circuit on the AC output sideLocate and repair short circuit
Generator doesn't pull full loadCarburetion problemAdjust or repair carburetor or fuel system as necessary
Generator loses AC power then shuts downInverter overheat conditionAllow inverter to cool; check for cause of overheating
No AC outputShort circuit on the AC output sideLocate and repair short circuit
Overvoltage condition and speed control system cannot reduce output voltageCarburetor linkage sticking with throttle stuck partly openRepair sticking throttle
Priming function does not workBlown 7.5 amp fuseReplace the fuse
The engine runs for about 10 seconds and then stops after a restart following a low oil pressure shutdown.Low oil level was not corrected.
The engine shuts down by itself.Oil pressure is too low.Check the engine oil level.
The engine shuts down due to high temperature.Engine temperature exceeds the preset temperature.
The engine speed is increased beyond the control of the computer control system.Do not attempt to physically adjust or control the engine speed.
The generator voltage output drops below a preset level.Once the unit has shutdown, the computer is automatically reset when you restart the engine.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.