HomeControllers7310 MKII

7310 MKII Controller

The 7310 MKII is a generator-set controller. It is used on generator sets from Winco, including the DR100F4 and DR130F4.

2
Generator sets
Winco
Brand
100–100 kW
Power range
Diesel
Fuel

Generator sets using this controller

2

Engines paired with this controller

1

Troubleshooting

7

Symptoms & remedies

SymptomCause
ATS will not re-transfer to normal powerProper power line not available at line terminals in ATS panel Defective ATS control board. See ATS manual
ATS will not transfer to Emergency Supply (generator)No AC generator output Defective ATS control board. See ATS manual Circuit breaker open or defective
Engine cranks but will not startImproper fuel delivery to the unit Fuel supply shut off Fuel tank empty Air in the fuel system Engine fuel solenoid has not opened Defective fuel pump Defective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid
Engine starts, then stops and alarm light comes onEngine oil pressure is low Engine has high water temperature Engine has overspeed Engine has gone into overcrank
Engine won’t crankLow/dead battery Blown DC fuses Defective DSE 7310 MKII Defective key switch Loose or dirty battery terminals Defective starter Defective start solenoid
No output from AC generatorLoss of speed signal Loss of run signal Engine will not come up to speed after it starts Insufficient fuel volume getting to the unit 1. Too small of fuel line 2. Fuel racks not open properly Governor is defective AC short in generator components
Unit will not crank when power failsDigital genset not in AUTO Transfer control switch not in AUTOMATIC position Incorrect wiring between ATS and genset Defective control relay in ATS Fuse(s) blown in the DSE 7310 MKII Defective DSE 7310 MKII Loose or dirty battery terminals Defective starter Defective start solenoid Low/dead battery

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.