550 Controller

The 550 is a generator-set controller. It is used on generator sets from Kohler, including the 100EFOZ, 125EOZ, 125REZG and 30REOZJ.

35
Generator sets
Kohler
Brand
30–128 kW
Power range
4
Fuel types

Engines paired with this controller

2

Troubleshooting

21

Symptoms & remedies

SymptomCauseRemedy
Cranks but does not startBattery connections loose, corroded, or incorrectVerify that the battery connections are correct, clean, and tight.
Display is blackNo/low battery chargeRecharge/replace battery
Display locks upNo/low battery chargeRecharge/replace battery
Display shows an EEPROM WRITE ERROR messageEEPROM fault caused by component failure, lightening strike, or voltage spikeReinitialize the problem data block; Contact an Authorized Distributor/Dealer
Display shows an error messageController firmware or keypad entry errorReview the Request and Error Message Section
Display shows single segmentLow battery voltageRecharge battery
Displays error message/locks upController firmware errorReview the controller display troubleshooting chart.
Does not crankBattery connections loose, corroded, or incorrectVerify that the battery connections are correct, clean, and tight.
Excessive or abnormal noiseCompression weakCheck the compression.
Exercise run time and/or event records inoperativeController clock not setReset time and date.
High fuel consumptionAir cleaner cloggedClean or replace the filter element.
Lacks powerAir cleaner cloggedClean or replace the filter element.
Low oil pressureCrankcase oil type incorrect for ambient temperatureChange the oil. Use oil with a viscosity suitable for the operating climate.
No or low output voltageAC output circuit breaker openReset the breaker and check for AC voltage at the generator set side of the circuit breaker.
Output voltage rampsDefective exciter windingTroubleshoot alternator components
Output voltage unstableVoltage regulation calibration incorrectReadjust voltage regulation
OverheatsEngine overloadReduce the electrical load. See the generator set spec sheet for wattage specifications.
Speed adjust does not functionAnalog input A06 is supported with Doosan, GM, and Volvo engines onlyCheck calibration values
Starts hardController fuse blownReplace the blown controller fuse. If the fuse blows again, troubleshoot the controller.
Stops suddenlyHigh water temperature switch inoperativeReplace the inoperative switch.
Voltage adjust does not function for paralleling applicationsAnalog input A07 description does not match Analog Volt AdjustChange description to Analog Volt Adjust using Monitor III software or enable analog voltage adjust in Menu 11

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.