3.3 MLD Controller

The 3.3 MLD is a generator-set controller. It is used on generator sets from Cummins/Onan, including the DFEJ and DFEK.

3
Generator sets
Cummins/Onan
Brand
450–500 kW
Power range
Diesel
Fuel

Generator sets using this controller

3

Also fitted to: Cummins/Onan QSK60 Engine with the PowerCommand® 3.3 or 3.3MLD.

Engines paired with this controller

1

Troubleshooting

60

Fault codes

CodeMeaningCause
121SPEED SIGNAL LOSTIndicates that no magnetic pickup pulses were sensed for a Loss of Speed delay. If a magnetic pickup is disabled, this fault is not activated.
1225Low Genset Voltage
1226Genset Frequency Error
1243Engine Derated
1244Engine Normal Shutdown
1245Engine Shutdown Fault
1246Unknown Engine Fault
1248Engine Warning
1311 and 1312Customer Input #1 and #2 (Warning or Shutdown)
1312Config Input #2 Fault
1317Low Coolant Level (Warning or Shutdown)
1318Low Fuel (Warning or Shutdown)
1322KW Setpoint OOR Hi
1323KW Setpoint OOR Lo
1324KVAR Setpoint OOR Hi
1325KVAR Setpoint OOR Lo
1328Genset CB Tripped
135OIL PRESS SENSOR OOR HIGHIndicates the oil pressure sensor output is out of range (OOR), high.
141OIL PRESS SENSOR OOR LOWIndicates the oil pressure sensor output is out of range (OOR), low.
1416Fail To Shutdown
1417Power Down Failure
143PRE-LOW OIL PRESSUREIndicates the engine oil pressure is approaching an unacceptable level.
1433Local E-Stop
1434Remote E-Stop
1435Low Coolant Temperature
1438Fail to Crank (Shutdown)
1439Low Day Tank Fuel
144COOLANT SENSOR OOR LOWIndicates the coolant temperature sensor output is out of range (OOR), low.
1441Low Fuel Level
1444KW Overload
1445Short Circuit
1446High AC Voltage
1447Low AC Voltage (Shutdown)
1448Underfrequency
1449Overfrequency
145COOLANT SENSOR OOR HIGHIndicates the coolant temperature sensor output is out of range (OOR), high.
1451Genset/Bus V Mismatch
1452Genset CB Fail To Close
1453Genset CB Fail To Open
1454Genset CB Pos Error
1455Utility CB Pos Error
1456Bus Out Of Sync Range
1457Fail To Synchronize
1458Sync Ph Rot Mismatch
1459Reverse Power
146PRE-HIGH COOLANT TEMPIndicates that the engine is operating near cooling system capacity. Increase in load or higher ambient temperature may cause High Coolant Temp (code 151) shutdown.
1461Loss of Field
1464Load Dump
1469Speed/Hz Mismatch
1471High AC Current (Warning)
1472High AC Current (Shutdown)
1475First Start Backup Fail
1483Common Alarm
151HIGH COOLANT TEMPIndicates that the engine coolant temperature is above normal and has reached the Shutdown trip point.
153INTAKE MANIFOLD TEMP OOR HIGHIndicates that the intake manifold temperature sensor is out of range (OOR), high.
154INTAKE MANIFOLD TEMP OOR LOWIndicates that the intake manifold temperature sensor is out of range (OOR), low.
1540Common Warning
1541Common Shutdown
155INTAKE MANIFOLD TEMP HIGHIndicates that the intake manifold temperature sensor is above normal and has reached
1573Config Input #1 Fault

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.