Home› Troubleshooting›Terex T90C

Terex T90C Troubleshooting

Terex T90C troubleshooting: 67 symptom-cause-remedy entries from the manufacturer's own service documentation.

Terex T90C — full specs, parts & maintenance.

Troubleshooting

67

Symptoms & remedies

SymptomCauseRemedy
No generator output voltageCircuit breaker trippedReset circuit breaker
No generator output voltageVoltage regulatorCheck voltage regulator wiring
No generator output voltageDefective voltage regulatorReplace voltage regulator
No generator output voltageDefective Selector SwitchBy pass by hardwiring generator
No generator output voltageDefective generatorRefer to generator manual
Low generator output voltageVoltage adjustment set too lowAdjust voltage potentiometer
Low generator output voltageDefective potentiometerBy pass or replace
Low generator output voltageLow engine speedCall TEREX Service
Low generator output voltageLoose wire on voltage selector switchCheck wiring
Low generator output voltageFluctuating or surging engine speedCheck engine fuel, oil, and air filters
Low generator output voltageLoose wire on voltage regulator sensing circuitCheck wiring
Low generator output voltageDefective voltage regulatorReplace voltage regulator
High generator output voltageVoltage adjustment potentiometerAdjust potentiometer
High generator output voltageHigh engine speedCall TEREX Service
High generator output voltageDefective automatic voltage regulatorReplace voltage regulator
High generator output voltageLoose wire on voltage adjustment potentiometerCheck wiring
High generator output voltageNeutral binding strap not in place.Install neutral binding strap
Fluctuating generator output voltageAn “ON/OFF” type load may be the causeRedistribute load if possible
Fluctuating generator output voltageFluctuating or surging engine speedCheck engine fuel, oil, and air filters
Fluctuating generator output voltageLoose wiring in generatorCheck connections
Fluctuating generator output voltageAutomatic voltage regulator stability setting may be wrongCall TEREX Service
Fluctuating generator output voltageLoose wire on the automatic voltage regulator sensing leadCheck wiring
Fluctuating generator output voltageLow engine speedCall TEREX Service
Fluctuating generator output voltageEngine speed adjustment has slippedCall TEREX Service
Fluctuating generator output voltageClogged fuel systemCheck for air leaks, clogged fuel filter, kinked fuel line, or clogged fuel pick-up tube
Fluctuating generator output voltageBlocked air intakeCheck air filter
Fluctuating generator output voltageBlocked exhaust systemCheck engine exhaust system, remove obstructions
Fluctuating generator output voltageContaminated fuelCheck fuel/water separator and fuel tank for contamination. Replace fuel if needed
Fluctuating generator output voltageDefective governor on engineCall TEREX Service
Low SpeedDefective injectors on engineHave injectors checked by a qualified technician
Low Speed“Surging” engine speedCheck engine fuel, oil, and air filters
Engine turns over (cranks), but won’t runUnit out of fuelCheck fuel level in tank, fill as needed
Engine turns over (cranks), but won’t runLoose or broken wire in control circuit fuel injection pump solenoidCheck wiring to verify 12V DC is being supplied to the pump solenoid
Engine turns over (cranks), but won’t runDefective solenoidReplace solenoid
Engine turns over (cranks), but won’t runClogged fuel systemCheck fuel system
Engine turns over (cranks), but won’t runAir in fuel system“Bleed” fuel system
Engine turns over (cranks), but won’t runDefective fuel pumpCheck and replace if defective
Engine turns over (cranks), but won’t runClogged air intakeCheck air cleaner
Engine turns over (cranks), but won’t runClogged exhaustCheck exhaust system
Engine turns over (cranks), but won’t runContaminated fuelCheck fuel/water separator and tank for contamination
Engine turns over (cranks), but won’t runDefective injectorsHave injection system checked by a trained technician
Engine turns over (cranks), but won’t runLost engine compressionHave compression checked by a trained technician
Engine won’t crankLoose battery cable or discharged batteryCheck cables and battery electrolyte level. Recharge as necessary
Engine won’t crankEngine “ON/OFF” switch set in “OFF” positionCheck switch position
Engine won’t crankBlown fuse in DC control circuitReplace with 25 Amp. SLO-BLO TYPE fuse if needed.
Engine won’t crankE-StopCheck to see if engaged
Engine won’t crankDefective starter solenoidReplace solenoid
Engine won’t crankDefective starterReplace starter
Engine won’t crankSeized engineHave engine checked by a qualified technician
Engine runs, but loses speedUnit is overloadedReduce load
Engine runs, but loses speedImproper connectionCheck or Call TEREX Service
Engine runs, but loses power under loadClogged fuel system air in fuel linesCheck fuel system
Engine runs, but loses power under loadBlocked air intakeCheck air cleaner
Engine runs, but loses power under loadBlocked exhaustCheck exhaust system
Engine runs, but loses power under loadContaminated fuelCheck fuel/water separator and fuel tank for contamination
Engine runs, but loses power under loadFaulty governor, defective injectors, or defective fuel pumpHave unit checked by a trained service technician for all of these items
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedOil Pressure Switch Not opening
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedImproper coolant or water mixtureUse a 50/50 mix of water and anti-freeze only
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedOverloaded engineReduce load
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedBroken fan beltInspect fan belt and replace as needed
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedDefective thermostat or thermocouple switchInspect thermostat switch
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedDefective water pumpInspect water pump and replace if needed
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedBlocked cooling air inlet or exhaustInspect and remove any obstructions
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedDefective or grounded temperature switchInspect switch and repair or replace
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedDefective injectors or injector pumpHave the engine inspected by a trained service technician
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedDefective oil pumpHave the engine inspected by a trained service technician
Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminatedDefective or grounded oil pressure switchInspect switch and repair or replace

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Terex T90C: Fluctuating generator output voltage — what causes it?

Documented causes: An “ON/OFF” type load may be the cause; Fluctuating or surging engine speed; Loose wiring in generator; Automatic voltage regulator stability setting may be wrong. See the table for the matching fixes.

Terex T90C: Engine turns over (cranks), but won’t run — what causes it?

Documented causes: Unit out of fuel; Loose or broken wire in control circuit fuel injection pump solenoid; Defective solenoid; Clogged fuel system. See the table for the matching fixes.

Terex T90C: Engine shuts down automatically and TROUBLE LIGHT on CONTROL PANEL is illuminated — what causes it?

Documented causes: Oil Pressure Switch Not opening; Improper coolant or water mixture; Overloaded engine; Broken fan belt. See the table for the matching fixes.