Home TroubleshootingPower Solutions International 4.3L

Power Solutions International 4.3L Troubleshooting

Power Solutions International 4.3L troubleshooting: 24 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Power Solutions International 4.3L — full specs, parts & maintenance.

All Power Solutions International fault codes →

Troubleshooting

24

Fault codes

CodeMeaningRemedy
8Low Water Temp LED
9High Engine Temp Pre-alarm LED
10Low Oil Pressure Pre-alarm LED
11Low Fuel LEDCheck fuel supply and replenish as required.
12Unit Not In Auto LEDMove the AUTO/OFF/MANUAL switch to the AUTO position for automatic starting.
13Press To Test Button
14Engine Overheat LEDReduce load if possible by turning off non-critical loads. Check air inlets and outlets and remove any obstructions to airflow. Open doors or windows in generator area to increase ventilation.
15Engine Overheat Shutdown LEDAllow engine to cool down completely before proceeding with the following checks: Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. Check for obstructions to cooling airflow and correct as necessary. Check for a slipping fan belt and tighten if loose.
16Low Oil Pressure LEDCheck oil level, lines and filters. If the oil system is okay but oil level is low, replenish.
17Overcrank LEDCheck for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required. Check for dirty fuel filter and replace if necessary (See Maintenance section of Engine Manual). Check for dirty or plugged air filter and replace if necessary (See Maintenance section of Engine Manual).
18Engine Over-speed LEDRefer to governor adjust procedure. Contact your Dealer or Distributor for service.
19Unit Not In Auto LEDMove the AUTO/OFF/MANUAL switch to the AUTO position for automatic starting.
20Low Fuel LEDCheck fuel level and replenish as required. See Engine Manual for fuel system priming procedure.
21Low Coolant Temperature LEDCheck for the following conditions: Coolant heater not connected to power supply. Check for blown fuse, open circuit breaker or disconnected heater cord and correct as required. Check for low-coolant level and replenish if required. Look for possible coolant leakage points and repair as required.
22Charger Malfunction LEDCheck and repair. Contact Dealer or Distributor for assistance.
23Low Battery LEDCheck electrolyte level and charger output or replace the battery.
24Fault LED on but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits.Contact your Dealer or Distributor for service.
25Engine Start from Generator Control Panel but will not start automatically or from a remote panel.Check the following: Check wire to ATS. See ATS section for further troubleshooting. Contact your Dealer or Distributor for assistance.
26Engine will not crank.Check for the following conditions: Fault lamp on. Correct fault and reset control. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. Discharged or defective battery. Recharge or replace the battery.
27No AC Output Voltage.Verify output with another meter if ok check meter, if ok check meter fuses. Regulator fuse is blown. Replace fuse. Contact your Dealer or Distributor if voltage build-up causes fuse to blow. Check rotating rectifier for damaged diodes. Replace all diodes if any are failed.
28No Engine Start.Check Engine Start connections. Investigate why the Engine Control Switch was put in Manual. Contact your Dealer or Distributor for assistance.
29No Engine Stop.Check Engine Start Timer setting. Check Engine Start Connections. Investigate why the Engine Control Switch was put in Manual. Contact your Dealer or Distributor for assistance.
30ATS will not transfer to Emergency.Check Engine Start connections, Generator output, and Engine Control Switch. Plug in Power Supply harness. Plug in Limit Switch harness. Check transfer to Emergency Timer setting. Contact your Dealer or Distributor for assistance.
31ATS will not transfer to Normal.Check Utility and Utility breakers. Plug in Power Supply harness. Plug in Limit Switch harness. Check retransfer to Normal Timer setting. Contact your Dealer or Distributor for assistance.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.