Doosan G60-SIIIA Troubleshooting

Doosan G60-SIIIA troubleshooting: 29 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Doosan G60-SIIIA — full specs, parts & maintenance.

All Doosan fault codes →

Troubleshooting

29

Symptoms & remedies

SymptomCauseRemedy
Engine cranks but will not startIncorrect starting procedure.Verify correct starting procedure.
No fuelCheck fuel in tank and manual shut-off valve.
Exhaust restrictedCheck and correct exhaust restriction.
Fuel filter plugged or full of waterReplace fuel filter or drain water from filter.
Injection pump not getting fuel or air in fuel systemCheck fuel flow at supply pump or bleed fuel system.
Faulty injection pump or nozzlesConsult authorized diesel repair station for repair or replacement.
Engine hard to start or will not startEngine starting under load.Remove load.
Injection pump shut-off not resetTurn key switch to 'OFF' then to 'ON'.
Engine knocksLow engine oil level.Add oil to engine crankcase.
Low coolant temperatureRemove and check thermostat.
Engine overheatingSee 'Engine Overheats'.
Engine runs irregularly or stalls frequentlyLow coolant temperature.Remove and check thermostat.
Below normal engine temperatureDefective thermostat.Remove and check thermostat.
Lack of powerEngine overloaded.Reduce load.
Engine runs but generator will not take loadCheck Warm up timer has timed out. Ensure generator load inhibit signal is not present on the module inputs. Check connections to the switching device.
Incorrect reading on Engine gaugesFail to stop alarm when engine is at rest Check engine is operating correctly. Check that sensor is compatible with the module and that the module configuration is suited to the sensor.
CAN ECU WARNING CAN ECU SHUTDOWNThis indicates a fault condition detected by the engine ECU and transmitted to the DSE controller.
CAN DATA FAILIndicates failure of the CAN data link to the engine ECU. Check all wiring and termination resistors (if required).
Inaccurate generator measurements on controller displayCheck that the CT primary, CT secondary and VT ratio settings are correct for the application. Check that the CTs are wired correctly with regards to the direction of current flow (pt, p2 and s1, s2) and additionally ensure that CTs are connected to the correct phase (errors will occur if CT1 is connected to phase 2). Remember to consider the power factor (kW = kVA x powerfactor). The controller is true RMS measuring so gives more accurate display when compared with an 'averaging' meter such as an analogue panel meter or some lower specified digital multimeters. Accuracy of the controller is better than 1% of full scale. Generator voltage full scale is 415V ph-N, accuracy is ±4,15V (1% of 415V).
Module appears to 'revert' to an earlier configurationWhen editing a configuration using the PC software it is vital that the configuration is first 'read' from the controller before editing it. This edited configuration must then be 'written' back to the controller for the changes to take effect. When editing a configuration using the fascia editor, be sure to press the Auto Mode button to save the change before moving to another item or exiting the fascia editor.
Engine does not startStarter does not turn.Battery discharged, Bad cable connections., Starter or starter switch failure., Safety relay failure.
Engine fires but stalls immediatelyAir in the fuel system.
Unit is inoperativeRead/Write configuration does not operate Check the battery and wiring to the unit. Check the DC supply. Check the DC fuse.
Unit shuts downCheck DC supply voltage is not above 35 Volts or below 9 Volts. Check the operating temperature is not above 70°C. Check the DC fuse.
Fail to Start is activated after pre-set number of attempts to start.Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery supply is present on the Fuel output of the module. Check the speed-sensing signal is present on the module's inputs.
Continuous starting of generator when in the Auto Mode.Check that there is no signal present on the 'Remote Start' input. Check configured polarity is correct. Check the mains supply is available and within configured limits.
Generator fails to start on receipt of Remote Start signal.Check Start Delay timer has timed out. Check signal is on 'Remote Start' input. Confirm correct configuration of input is configured to be used as 'Remote Start'. Check that the oil pressure switch or sensor is indicating low oil pressure to the controller.
Pre-heat inoperativeCheck wiring to engine heater plugs. Check battery supply. Check battery supply is present on the Pre-heat output of module. Check pre-heat configuration is correct.
Starter motor inoperativeCheck wiring to starter solenoid. Check battery supply.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Cross-brand guides for these symptoms

Common questions

Doosan G60-SIIIA: Engine cranks but will not start — what causes it?

Documented causes: Incorrect starting procedure.. See the table for the matching fixes.

Doosan G60-SIIIA: Engine hard to start or will not start — what causes it?

Documented causes: Engine starting under load.. See the table for the matching fixes.

Doosan G60-SIIIA: Engine knocks — what causes it?

Documented causes: Low engine oil level.. See the table for the matching fixes.