Home› Troubleshooting›Doosan G60-SIIIA

Doosan G60-SIIIA Troubleshooting

Doosan G60-SIIIA troubleshooting: 3 fault codes and 116 symptom-cause-remedy entries from the manufacturer's own service documentation.

Doosan G60-SIIIA — full specs, parts & maintenance.

All Doosan fault codes →

Troubleshooting

119

Fault codes

CodeMeaningCauseRemedy
CAN ECU WARNINGCAN ECU WARNINGThis indicates a fault condition detected by the engine ECU and transmitted to the DSE controller
CAN ECU SHUTDOWNCAN ECU SHUTDOWNThis indicates a fault condition detected by the engine ECU and transmitted to the DSE controller
CAN DATA FAILCAN DATA FAILIndicates failure of the CAN data link to the engine ECUCheck all wiring and termination resistors (if required)

Symptoms & remedies

SymptomCauseRemedy
Engine cranks but will not startIncorrect starting procedureVerify correct starting procedure
Engine cranks but will not startNo fuelCheck fuel in tank and manual shut-off valve
Engine cranks but will not startExhaust restrictedCheck and correct exhaust restriction
Engine cranks but will not startFuel filter plugged or full of waterReplace fuel filter or drain water from filter
Engine cranks but will not startInjection pump not getting fuel or air in fuel systemCheck fuel flow at supply pump or bleed fuel system
Engine cranks but will not startFaulty injection pump or nozzlesConsult authorized diesel repair station for repair or replacement
Engine hard to start or will not startEngine starting under loadRemove load
Engine hard to start or will not startImproper starting procedureReview starting procedure
Engine hard to start or will not startNo fuelCheck fuel tank
Engine hard to start or will not startAir in fuel lineBleed fuel line
Engine hard to start or will not startCold weatherUse cold weather starting aids
Engine hard to start or will not startSlow starter speedSee "Starter Cranks Slowly"
Engine hard to start or will not startCrankcase oil too heavyUse oil of proper viscosity
Engine hard to start or will not startImproper type of fuelConsult fuel supplier; use proper type fuel for operating conditions
Engine hard to start or will not startWater, dirt, or air in fuel systemDrain, flush fill and bleed system
Engine hard to start or will not startClogged fuel filterReplace filter element
Engine hard to start or will not startDirty or faulty injection nozzlesHave authorized servicing dealer or engine distributor check injectors
Engine hard to start or will not startInjection pump shut-off not resetTurn key switch to "OFF" then to "ON"
Engine knocksLow engine oil levelAdd oil to engine crankcase
Engine knocksInjection pump out of timeSee your authorized servicing dealer or engine distributor
Engine knocksLow coolant temperatureRemove and check thermostat
Engine knocksEngine overheatingSee "Engine Overheats"
Engine runs irregularly or stalls frequentlyLow coolant temperatureRemove and check thermostat
Engine runs irregularly or stalls frequentlyClogged fuel filterReplace fuel filter element
Engine runs irregularly or stalls frequentlyWater, dirt, or air in fuel systemDrain, flush fill and bleed system
Engine runs irregularly or stalls frequentlyDirty or faulty injection nozzlesHave authorized servicing dealer or engine distributor check injectors
Below normal engine temperatureDefective thermostatRemove and check thermostat
Below normal engine temperatureDefective temperature gauge or senderCheck gauge, sender, and connections
Lack of powerEngine overloadedReduce load
Lack of powerIntake air restrictionService air cleaner
Lack of powerClogged fuel filterReplace filter elements
Lack of powerImproper type of fuelUse proper fuel
Lack of powerOverheated engineSee "Engine Overheats"
Lack of powerBelow normal engine temperatureRemove and check thermostat
Lack of powerImproper valve clearanceSee your authorized servicing dealer or engine distributor
Unit is inoperative / Read/Write configuration does not operateCheck the battery and wiring to the unit; Check the DC supply; Check the DC fuse
Unit shuts downCheck DC supply voltage is not above 35 Volts or below 9 Volts; Check the operating temperature is not above 70°C; Check the DC fuse
Fail to Start is activated after pre-set number of attempts to startCheck wiring of fuel solenoid; Check fuel; Check battery supply; Check battery supply is present on the Fuel output of the module; Check the speed-sensing signal is present on the module's inputs; Refer to engine manual
Continuous starting of generator when in the Auto ModeCheck that there is no signal present on the 'Remote Start' input; Check configured polarity is correct; Check the mains supply is available and within configured limits
Generator fails to start on receipt of Remote Start signalCheck Start Delay timer has timed out; Check signal is on 'Remote Start' input; Confirm correct configuration of input is configured to be used as 'Remote Start'; Check that the oil pressure switch or sensor is indicating low oil pressure to the controller; Depending upon configuration, then set will not start if oil pressure is not low
Pre-heat inoperativeCheck wiring to engine heater plugs; Check battery supply; Check battery supply is present on the Pre-heat output of module; Check pre-heat configuration is correct
Starter motor inoperativeCheck wiring to starter solenoid; Check battery supply; Check battery supply is present on the Starter output of module; Ensure oil pressure switch or sensor is indicating the 'low oil pressure' state to the controller
Engine runs but generator will not take loadCheck Warm up timer has timed out; Ensure generator load inhibit signal is not present on the module inputs; Check connections to the switching device; Note that the set will not take load in manual mode unless there is an active load signal
Incorrect reading on Engine gauges / Fail to stop alarm when engine is at restCheck engine is operating correctly; Check that sensor is compatible with the module and that the module configuration is suited to the sensor
Low oil Pressure fault operates after engine has firedCheck engine oil pressure; Check oil pressure switch/sensor and wiring; Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sensor is compatible with the module and is correctly configured
High engine temperature fault operates after engine has firedCheck engine temperature; Check switch/sensor and wiring; Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sensor is compatible with the module
Shutdown fault operatesCheck relevant switch and wiring of fault indicated on LCD display; Check configuration of input
Electrical Trip fault operatesCheck relevant switch and wiring of fault indicated on LCD display; Check configuration of input
Warning fault operatesCheck relevant switch and wiring of fault indicated on LCD display; Check configuration of input
Inaccurate generator measurements on controller displayCheck that the CT primary, CT secondary and VT ratio settings are correct for the application; Check that the CTs are wired correctly with regards to the direction of current flow (pt, p2 and s1, s2) and additionally ensure that CTs are connected to the correct phase (errors will occur if CT1 is connected to phase 2); Remember to consider the power factor (kW = kVA x powerfactor); The controller is true RMS measuring so gives more accurate display when compared with an 'averaging' meter such as an analogue panel meter or some lower specified digital multimeters; Accuracy of the controller is better than 1% of full scale. Generator voltage full scale is 415V ph-N, accuracy is ±4,15V (1% of 415V)
Module appears to 'revert' to an earlier configurationWhen editing a configuration using the PC software it is vital that the configuration is first 'read' from the controller before editing it. This edited configuration must then be 'written' back to the controller for the changes to take effect; When editing a configuration using the fascia editor, be sure to press the Auto Mode button to save the change before
Engine does not start — Starter does not turnBattery discharged
Engine does not start — Starter does not turnBad cable connections
Engine does not start — Starter does not turnStarter or starter switch failure
Engine does not start — Starter does not turnSafety relay failure
Engine does not start — Starter turns but engine does not fireNo fuel injection
Engine does not start — Starter turns but engine does not fireNo fuel in the fuel tank
Engine does not start — Starter turns but engine does not fireClogged fuel filter element
Engine does not start — Starter turns but engine does not fireAir in the fuel system
Engine does not start — Starter turns but engine does not fireControl rack is stuck at no fuel position
Engine does not start — Fuel is injected but engine does not fireIncorrect preheating operation
Engine does not start — Fuel is injected but engine does not fireFaulty air heater
Engine does not start — Fuel is injected but engine does not fireIncorrect injection timing
Engine does not start — Fuel is injected but engine does not fireLow cylinder compression pressure
Engine does not start — Engine fires but stalls immediatelyAir in the fuel system
Unstable engine running — Unstable low idlingCrack in injection pipe
Unstable engine running — Unstable low idlingInjection nozzle failure
Unstable engine running — Unstable low idlingUneven compression pressure between cylinders
Unstable engine running — Unstable low idlingIncorrect high idle speed adjustment
Unstable engine running — Unstable low idlingSoftware/Electronic malfunction
Unstable engine running — Engine hunting in medium speed rangeSoftware/Electronic malfunction
Unstable engine running — Engine malfunction in high speed rangeInsufficient fuel supply
Unstable engine running — Engine malfunction in high speed rangeAir in the fuel system
Unstable engine running — Engine malfunction in high speed rangeClogged fuel filter element
Unstable engine running — Engine malfunction in high speed rangePiping failure (squeezed/restricted etc.)
Unstable engine running — Engine malfunction in high speed rangeUneven fuel injection amount between cylinders
Unstable engine running — Engine malfunction in high speed rangeIncorrect valve clearance adjustment
Unstable engine running — Engine malfunction in high speed rangeDeteriorated valve spring
Unstable engine running — Engine speed stuck at high idleEngine control restriction or seizure
Engine overheat — Cooling system defectInsufficient coolant volume
Engine overheat — Cooling system defectFan belt slippage
Engine overheat — Cooling system defectThermostat malfunction
Engine overheat — Cooling system defectRadiator filler cap malfunction
Engine overheat — Cooling system defectCooling system interior fouled
Engine overheat — Cooling system defectRadiator clogged
Engine overheat — Improper servicingEngine over-loaded
Engine overheat — Improper servicingAir cleaner element clogged
Engine overheat — Improper servicingInsufficient airflow/restriction
Engine overheat — Improper servicingRestricted coolant flow (high concentration of antifreeze, etc.)
Low oil pressure — Lack of oilOil leakage
High oil consumption — Wrong oilWrong type and viscosity
High oil consumption — High coolant temperatureOver heat
High oil consumption — Clogged filter and strainerClean and/or replace
High oil consumption — Worn bearings and oil pumpReplace
High oil consumption — Faulty relief valveReplace
Low engine output — Incorrect injection pump adjustmentIncorrect injection timing
Low engine output — Incorrect injection pump adjustmentToo far advanced
Low engine output — Incorrect injection pump adjustmentToo far retarded
Low engine output — Injection nozzle malfunctionIncorrect injection pressure
Low engine output — Injection nozzle malfunctionIncorrect spray condition
Low engine output — Insufficient fuel supply to the injection pumpLack of fuel in tank
Low engine output — Insufficient fuel supply to the injection pumpAir in injection pump
Low engine output — Insufficient fuel supply to the injection pumpFuel filter clogged
Low engine output — Insufficient fuel supply to the injection pumpOverflow valve malfunction
Low engine output — Governor malfunctionIncorrect engine control adjustment
Low engine output — Governor malfunctionDeteriorated governor spring
Low engine output — Low cylinder compression pressureCylinder compression leakage
Low engine output — Low cylinder compression pressureIncorrect valve clearance adjustment
Low engine output — Low cylinder compression pressureInjector nozzle misalignment
Low engine output — Low cylinder compression pressureCylinder bore wear
Low engine output — Insufficient air intake volumeAir cleaner clogged
Low engine output — Insufficient air intake volumeRestricted air flow
Excessive oil consumption — Incorrect oilWrong selection of type and viscosity
Excessive oil consumption — Incorrect oilToo much oil quantity
Excessive oil consumption — Engine burning oilFaulty piston rings/damaged cylinder bores
Excessive oil consumption — Engine burning oilFaulty valve

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Cross-brand guides for these symptoms

Common questions

Doosan G60-SIIIA: Engine hard to start or will not start — what causes it?

Documented causes: Engine starting under load; Improper starting procedure; No fuel; Air in fuel line. See the table for the matching fixes.

Doosan G60-SIIIA: Lack of power — what causes it?

Documented causes: Engine overloaded; Intake air restriction; Clogged fuel filter; Improper type of fuel. See the table for the matching fixes.

Doosan G60-SIIIA: Unstable engine running — Engine malfunction in high speed range — what causes it?

Documented causes: Insufficient fuel supply; Air in the fuel system; Clogged fuel filter element; Piping failure (squeezed/restricted etc.). See the table for the matching fixes.