Cummins/Onan DQKC Troubleshooting

Cummins/Onan DQKC troubleshooting: 46 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Cummins/Onan DQKC — full specs, parts & maintenance.

All Cummins/Onan fault codes →

Troubleshooting

46

Fault codes

CodeMeaningRemedy
235COOLANT LEVEL ALARMA. Check jacket water coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Reset control and restart after locating and correcting problem.
253OIL LEVEL ALARMCheck oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart.
326OIL LEVEL WARNINGIf generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow 688 High Oil Level Alarm procedure. If engine can be stopped follow 688 procedure.
359ENGINE FAILED TO STARTA. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. b. Discharged or defective battery. Recharge or replace the battery.
441LOW BATTERY VOLTAGEA. Discharged or defective battery. Check the battery charger fuse. Recharge or replace the battery. b. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. c. Check engine DC alternator. Replace engine DC alternator if normal battery charging voltage (24 to 26 VDC) is not obtained. d. Check float level if applicable (raise float level).
442HIGH BATTERY VOLTAGECheck float level on battery charger if applicable (lower float level). Check engine DC alternator. Replace engine DC alternator if normal battery charging voltage (24 to 26 VDC) is not obtained.
471LOW OIL LEVELIf generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow 253 Oil Level Alarm procedure. If engine can be stopped follow 253 procedure.
611ENGINE HOTThis type of shutdown should be avoided. Can cause possible loss of performance and engine damage.
688HIGH OIL LEVEL ALARMCheck oil level. Drain oil to operating level.
1311 through 1318Customer Defined Fault
1416FAIL TO SHUTDOWNStatus ï indicates that the “Fault Bypass” mode is enabled. This mode is primarily used by service personnel for troubleshooting purposes.
1417POWER DOWN ERRORPossible drain on battery. Contact an authorized service center for service.
1433 / 1434EMERGENCY STOP ï LOCAL / EMERGENCY STOP ï REMOTETo reset the local/remote Emergency Stop button: Pull the button out. Move the O/Manual/Auto switch to O (off). Press the front panel Fault Acknowledge button. Select Manual or Auto, as required.
1438FAIL TO CRANKA. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. b. Discharged or defective battery. Recharge or replace the battery.
1439FUEL LEVEL LOW IN DAYCheck fuel supply and replenish as required.
111Internal ECM error
112Actuator not responding
113Actuator sensor fault
115No speed signal
116Time press sensor high
117Time press sensor low
118Pump press sensor high
119Pump press sensor low
121No engine speed signal
122Manifold air press sensor
135Oil pressure sensor
143Low oil pressure
144Coolant temperature sensor
152Low coolant temp
153Manifold air temp sensor
688LAMP: Shutdown MESSAGE: HIGH OIL LEVEL ALARMIndicates that the engine oil level has exceeded the alarm trip point for high oil level. Check oil level. Drain oil to operating level.
1311 through 1318LAMP: Shutdown/Warning MESSAGE: Customer Defined FaultWhen any one of these customer defined inputs is detected by the control, the corresponding fault message is displayed. The nature of the fault is an optional customer selection. These fault functions can be programmed to initiate a shutdown or warning as indicated by the Warning or Shutdown lamp. Note: Customer fault messages are editable. The message displayed for the code shown (1311 through 1318) is determined by the customer.
1416LAMP: Warning MESSAGE: FAIL TO SHUTDOWNStatus – indicates that the “Fault Bypass” mode is enabled. This mode is primarily used by service personnel for troubleshooting purposes. In this mode the generator set ignores the majority of system shutdown faults.
1417LAMP: Warning MESSAGE: POWER DOWN ERRORIndicates that the control can not power down due to some unknown condition. Possible drain on battery. Contact an authorized service center for service.
1433 / 1434LAMP: Shutdown MESSAGE: EMERGENCY STOP – LOCAL / EMERGENCY STOP – REMOTEIndicates local or remote Emergency Stop. Emergency Stop shutdown status can be reset only at the local control panel. To reset the local/remote Emergency Stop button: Pull the button out. Move the O/Manual/Auto switch to O (off). Press the front panel Fault Acknowledge button. Select Manual or Auto, as required.
1438LAMP: Warning MESSAGE: FAIL TO CRANKIndicates possible fault with control or starting system. Check for the following conditions: a. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. b. Discharged or defective battery. Recharge or replace the battery.
1439LAMP: Warning MESSAGE: FUEL LEVEL LOW IN DAYIndicates fuel supply is running low. Check fuel supply and replenish as required.
1441LAMP: Warning MESSAGE: FUEL LEVEL LOW IN MAINIndicates fuel supply is running low. Check fuel supply and replenish as required.
1442LAMP: Warning MESSAGE: BATTERY IS WEAKIndicates battery voltage drops below 14.4 volts for two seconds, during starting. Discharged or defective battery. See Warning message 441 Low Battery Voltage.
1443LAMP: Warning MESSAGE: BATTERY IS DEADIndicates battery has dropped below genset operating range (3.5 volts when cranking) to power the starter and the control circuitry. See Warning message 441 Low Battery Voltage.
146HIGH COOLANT TEMP WARNINGA. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. c. If engine can be stopped, follow 151 High Coolant Temp Alarm procedure.
151HIGH COOLANT TEMP ALARMA. Check jacket water coolant level and replenish if low. Look for coolant leakage and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check fan belt and repair if necessary. d. Reset control and restart after locating and correcting problem.
197COOLANT LEVEL WARNINGA. Wait until next shutdown period, then follow 235 Coolant Level Alarm procedure. b. If engine can be stopped, follow 235 procedure.

Symptoms & remedies

SymptomRemedy
The genset control continuously monitors engine sensors for abnormal conditions, such as low oil pressure and high coolant temperature.If any of these conditions occur, the control will light a yellow Warning lamp or a red Shutdown lamp and display a message on the graphical display panel.
The shutdown status indicator is lit whenever the control detects a shutdown condition.After the condition is corrected, the shutdown indicator can be reset by turning the O/Manual/Auto switch to the O (off) position, and pressing the Fault Acknowledge button. The generator set can not be started when this lamp is on.
The warning status indicator is lit whenever the control detects a warning condition.After the condition is corrected, the warning indicator can be reset by pressing the Fault Acknowledge button. (It is not necessary to stop the generator set if the fault becomes inactive during genset operation.)