Cummins/Onan DFEJ Troubleshooting

Cummins/Onan DFEJ troubleshooting: 98 fault codes and 15 symptom-cause-remedy entries from the manufacturer's own service documentation.

Cummins/Onan DFEJ — full specs, parts & maintenance.

All Cummins/Onan fault codes →

Troubleshooting

113

Fault codes

CodeMeaningCauseRemedy
1131Battle Short Active
1416Fail to Shutdown
121Speed Signal Lost (Loss of Speed Sense)
234Overspeed
1433Local Emergency Stop
1434Remote Emergency Stop
2335Excitation Fault (Loss of Voltage Sense)
1123Shutdown After Battle Short
121SPEED SIGNAL LOST — ShutdownNo magnetic pickup pulses were sensed for a Loss of Speed delay. If a magnetic pickup is disabled, this fault is not activated.
135OIL PRESS SENSOR OOR HIGH — WarningThe oil pressure sensor output is out of range (OOR), high.
141OIL PRESS SENSOR OOR LOW — WarningThe oil pressure sensor output is out of range (OOR), low.
143PRE-LOW OIL PRESSURE — WarningThe engine oil pressure is approaching an unacceptable level.Indicates engine oil pressure has dropped below the warning trip point. If the generator is powering critical loads and cannot be shut down, wait until the next shutdown period and then follow the code 415 procedure.
144COOLANT SENSOR OOR LOW — WarningThe coolant temperature sensor output is out of range (OOR), low.
145COOLANT SENSOR OOR HIGH — WarningThe coolant temperature sensor output is out of range (OOR), high.
146PRE-HIGH COOLANT TEMP — WarningThe engine is operating near cooling system capacity. Increase in load or higher ambient temperature may cause High Coolant Temp (code 151) shutdown.Indicates the engine is operating near cooling system capacity. Increase in load or higher ambient temperature may cause a High Coolant Temp (151) shutdown. Review code 151 correction list for other possible causes.
151HIGH COOLANT TEMP — ShutdownThe engine coolant temperature is above normal and has reached the Shutdown trip point.Allow the engine to cool down completely before proceeding with the following checks: 1. Look for possible coolant leakage points and repair them if necessary. 2. Check the coolant level and replenish it if low. 3. Check for obstructions to cooling airflow and correct them as necessary. 4. Check the fan belt, and repair or tighten it if necessary. 5. Check the blower fan and circulation pumps on remote radiator installations. 6. Reset the control and restart after locating and correcting the problem.
153INTAKE MANIFOLD TEMP OOR HIGH — WarningThe intake manifold temperature sensor is out of range (OOR), high.
154INTAKE MANIFOLD TEMP OOR LOW — WarningThe intake manifold temperature sensor is out of range (OOR), low.
155INTAKE MANIFOLD TEMP HIGH — ShutdownThe intake manifold temperature sensor is above normal and has reached the shutdown trip point. Large load or high ambient temperature may be the cause.Indicates the engine has overheated (intake manifold temperature has risen above the shutdown trip point). Large load or high ambient temperature may be the cause. Review the code 151 correction list for other possible causes.
195COOLANT LEVEL OOR HIGH — WarningA sensor on the radiator has detected that the coolant level is out of range (OOR), high.
196COOLANT LEVEL OOR LOW — WarningA sensor on the radiator has detected that the coolant level is out of range (OOR), low.
197COOLANT LEVEL LOW — WarningA sensor on the radiator has detected that the coolant level is below normal.Indicates engine coolant level has fallen below the trip point. If the generator is powering critical loads and cannot be shut down, wait until the next shutdown period. If the engine can be stopped, allow the engine to cool down completely before proceeding: 1. Look for coolant leakage points and repair if necessary. 2. Check the coolant level and replenish it if low. 3. Reset the control and restart after locating and correcting problem.
234OVERSPEED — ShutdownThe engine has exceeded normal operating speed. The default thresholds are 1725 RPM (50 Hz) or 2075 RPM (60 Hz).
285ECM PGN TIMEOUT — ShutdownDatalink failure. PowerCommand® 2.3 control not responding to the engine control module.
286ECM CONFIGURABLE ERROR — ShutdownAn engine control module configuration error – out of calibration.
359FAIL TO START — ShutdownThe system has failed to start after a set number of crank attempts. This indicates a possible fuel system or air induction problem (engine cranks but fails to start).Allow the engine to cool down completely before proceeding with the following checks: 1. Check for an empty fuel tank, fuel leaks, or blocked fuel lines, and correct as required. 2. Check for a dirty fuel filter and replace it if necessary. 3. Check for a dirty or blocked air filter and replace it if necessary. 4. Reset the control and restart after correcting the problem.
415LOW OIL PRESSURE — ShutdownThe engine oil pressure has dropped below normal and has reached the shutdown trip point.Allow the engine to cool down completely before proceeding with the following checks: 1. Check the oil level, lines, and filters. 2. If the oil system is OK but the oil level is low, replenish it. 3. Reset the control and restart after locating and correcting the problem.
421OIL TEMP HIGH — ShutdownThe engine oil temperature is above normal and has reached the shutdown trip point. (I/O Module option).
425OIL TEMP OOR — ShutdownThe engine oil temperature output is out of range (OOR). High or low. (I/O Module option).
426DATA LINK ERROR — ShutdownDatalink failure. No communications between the PowerCommand® 2.3 control and the engine control module.
427CAN LINK LOST — WarningDatalink fault. Indicates that important data was lost between the PowerCommand® 2.3 control and the engine control module.
441LOW BATTERY — WarningBattery voltage supply to the control is approaching a low level at which unpredictable operation can occur.If the engine can be stopped, allow the engine to cool down completely before proceeding: 1. If there are poor battery cable connections, clean the battery cable terminals and tighten all connections. 2. Check the battery charge voltage float level if applicable (raise float level). 3. If there is a discharged or defective battery, check the battery charger fuse. Recharge or replace the battery.
442HIGH BATTERY — WarningBattery voltage supply to the control is approaching a high level at which damage to the control can occur.If the engine can be stopped, allow the engine to cool down completely before proceeding: 1. If there are poor battery cable connections, clean the battery cable terminals and tighten all connections. 2. Check the battery charge float level, if applicable (lower float level).
488INTAKE MANIFOLD TEMP HIGH — ShutdownThe intake manifold temperature is above normal and has reached the shutdown trip point. (I/O Module option). Large load or high ambient temperature may be the cause.Indicates the engine has overheated (intake manifold temperature has risen above the shutdown trip point). Large load or high ambient temperature may be the cause. Review the code 151 correction list for other possible causes.
689ENGINE SPEED ERRATIC — ShutdownA fault condition in the engine crankshaft sensor circuit.
781CAN LINK LOST — ShutdownDatalink failure. No communications between the PowerCommand® 2.3 control and the engine control module.
1117ECM POWER LOST — WarningBattery voltage supply to the engine control module was lost. "Keyswitch" to the ECM was NOT removed for 30 seconds before removing battery power to the ECM (removing battery cable).To reset: 1. Press the Stop button, then press the Emergency Stop button and wait for 30 seconds. 2. Re-set the Emergency Stop and select an operating mode (manual or remote).
1123SHUTDOWN AFTER BS — ShutdownA shutdown fault occurred while the Battle Short mode was enabled.
1131BATTLE SHORT ACTIVE — WarningThe control is in Battle Short mode – used to bypass several fault shutdowns for generator set operation during emergencies.
1246GENERIC ENGINE FAULT — WarningEngine control fault code not recognized by the PowerCommand® 2.3 control.
1311CONFIGURABLE INPUT 1 — ConfigurableThe nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etc.Each of the fault functions can be programmed (using the InPower service tool or by accessing the Setup menu), as follows: 1. Event, Warning, or Shutdown level if Function Select = Fault Input. 2. Change the display name using up to 32 characters.
1312CONFIGURABLE INPUT 2 — ConfigurableThe nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etc.Each of the fault functions can be programmed (using the InPower service tool or by accessing the Setup menu), as follows: 1. Event, Warning, or Shutdown level if Function Select = Fault Input. 2. Change the display name using up to 32 characters.
1317CONFIGURABLE INPUT 3 — ConfigurableThe nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etc.Each of the fault functions can be programmed (using the InPower service tool or by accessing the Setup menu), as follows: 1. Event, Warning, or Shutdown level if Function Select = Fault Input. 2. Change the display name using up to 32 characters.
1318CONFIGURABLE INPUT 4 — ConfigurableThe nature of the fault is an optional generator set input. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etc.Each of the fault functions can be programmed (using the InPower service tool or by accessing the Setup menu), as follows: 1. Event, Warning, or Shutdown level if Function Select = Fault Input. 2. Change the display name using up to 32 characters.
1416FAIL TO SHUTDOWN — WarningA shutdown fault is active, but is being bypassed by Battle Short. The generator set continues to run after receiving a shutdown command from the controller. The Battle Short feature is enabled (this is used to bypass several critical fault shutdowns therefore allowing generator set operation during emergencies).
1417FAILURE TO POWER DOWN — ShutdownThe control is powered up after attempting to go to sleep.
1433LOCAL EMERGENCY STOP — ShutdownA Local Emergency Stop has been activated.Emergency Stop shutdown status can be reset only at the local control panel. After locating and correcting problem, reset the local/remote Emergency Stop button as follows: 1. De-activate (disable) the Emergency Stop button. 2. Press the Stop button. 3. Select the desired operating mode (manual or remote).
1434REMOTE EMERGENCY STOP — ShutdownA Remote Emergency Stop has been activated.Emergency Stop shutdown status can be reset only at the local control panel. After locating and correcting problem, reset the local/remote Emergency Stop button as follows: 1. De-activate (disable) the Emergency Stop button. 2. Press the Stop button. 3. Select the desired operating mode (manual or remote).
1435LOW COOLANT TEMP — WarningThe engine coolant temperature is below the adjusted setpoint. This may indicate that the coolant heater is not operating or is not circulating coolant.If the engine can be stopped, allow the engine to cool down completely before proceeding with the following checks: 1. The coolant heater is not connected to a power supply. Check for a blown fuse or disconnected heater cable, and correct it as required. 2. Look for possible coolant leaks and repair as required. Check for low coolant level and replenish, if required.
1438FAIL TO CRANK — ShutdownThe generator set has failed to sense rotation for two start attempts. This indicates a possible fault with the control, speed sensing, or the starting system.See code 441 for corrective action.
1442WEAK BATTERY — WarningThe generator set battery voltage is below battery thresholds during cranking. During cranking, the battery voltage is at, or below, the weak battery warning trip point for a time greater than, or equal to, the weak battery set time.See code 441 for corrective action.
1446HIGH AC VOLTAGE — ShutdownOne or more measured AC output voltages have exceeded the threshold for longer than a specified time limit. The threshold and time limits are 130% of nominal for zero seconds or 110% of nominal for ten seconds.
1447LOW AC VOLTAGE — ShutdownThe measured AC output voltage is below the threshold for longer than a specified time limit. The threshold and time limits are 85% of nominal for ten seconds.
1448UNDER FREQUENCY — ShutdownThe alternator frequency is 6 Hz under the nominal frequency. The generator set frequency has dropped below 90% of nominal for approximately ten seconds.Allow the engine to cool down completely before proceeding with the following checks: 1. Check the fuel supply. 2. Check the air intake supply. 3. Check the load and correct any overload.
1449OVER FREQUENCY — ShutdownThe alternator frequency is 6 Hz above the nominal frequency.
1469SPEED HZ MATCH — ShutdownMeasured engine speed and measured alternator AC output frequency do not agree.
1471HIGH AC CURRENT — WarningThe alternator output current (one or more phases) has exceeded safe operating limits.
1472HIGH AC CURRENT — ShutdownThe alternator output current (one or more phases) has exceeded the alternator's current rating.
1845WATER IN FUEL OOR HIGH — WarningThe water in fuel sensor is out of range (OOR), high.
1846WATER IN FUEL OOR LOW — WarningThe water in fuel sensor is out of range (OOR), low.
1852WATER IN FUEL — WarningThe water in fuel is above normal and has reached the warning trip point.If the engine can be stopped, allow the engine to cool down completely before proceeding with the following checks: 1. Check the fuel in the tank (local or remote). 2. Drain and re-fill the tank if necessary. Be aware of all Health and Safety, and environmental issues if draining the tank.
1853Annunciator Fault 2 — ConfigurableThe nature of the annunciator fault is an optional customer selection.
1854Annunciator Fault 3 — ConfigurableThe nature of the annunciator fault is an optional customer selection.
1855Annunciator Fault 1 — ConfigurableThe nature of the annunciator fault is an optional customer selection.
1944ANNUNCIATOR OUTPUT CONFIGURATION ERROR — WarningA mismatch in the configuration of one of the annunciator relay outputs.
1965EXHAUST TEMPERATURE OOR — WarningThe exhaust temperature sensor is out of range (OOR), high or low. (Aux 101 I/O option).
1992ENGINE OVERSPEED — WarningThe engine has exceeded normal operating speed. The default thresholds are 1725 RPM (50 Hz) or 2075 RPM (60 Hz). (ECM fault code).
2224FUEL LEVEL OOR — WarningThe fuel level sensor is out of range (OOR), high or low. (Aux 101 I/O option).
2335EXCITATION FAULT — ShutdownA loss of voltage or frequency sensing from the generator has occurred.
2398AMBIENT TEMPERATURE OOR — WarningThe ambient temperature sensor is out of range (OOR), high or low. (Aux 101 I/O option).
2542VOLTAGE BIAS OOR — WarningThe voltage bias circuit output is out of range (OOR), high or low. (Aux 101 I/O option).
2545KEYSWITCH RESET REQUIRED — ShutdownA datalink failure. Communications are lost between the PowerCommand® 2.3 control and the engine control module.
2619AUX 101 ANALOG INPUT 1 — DiagnosticThe nature of the Base I/O Module event is an optional customer selection. (Aux 101 I/O Module option).Each event function can be programmed (using InPower service tool or access to the Setup menu), as follows: 1. Change display name using up to 32 characters 2. Select active low or high input.
2621AUX 101 ANALOG INPUT 2 — DiagnosticThe nature of the Base I/O Module event is an optional customer selection. (Aux 101 I/O Module option).See code 2619
2622AUX 101 ANALOG INPUT 3 — DiagnosticThe nature of the Base I/O Module event is an optional customer selection. (Aux 101 I/O Module option).See code 2619
2623AUX 101 ANALOG INPUT 4 — DiagnosticThe nature of the Base I/O Module event is an optional customer selection. (Aux 101 I/O Module option).See code 2619
2624AUX 101 ANALOG INPUT 5 — DiagnosticThe nature of the Base I/O Module event is an optional customer selection. (Aux 101 I/O Module option).See code 2619
2625AUX 101 ANALOG INPUT 6 — DiagnosticThe nature of the Base I/O Module event is an optional customer selection. (Aux 101 I/O Module option).See code 2619
2626AUX 101 ANALOG INPUT 7 — DiagnosticThe nature of the Base I/O Module event is an optional customer selection. (Aux 101 I/O Module option).See code 2619
2627AUX 101 ANALOG INPUT 8 — DiagnosticThe nature of the Base I/O Module event is an optional customer selection. (Aux 101 I/O Module option).See code 2619
2628AUX 102 DIGITAL INPUT 9 — DiagnosticThe nature of the Aux I/O Module event is an optional customer selection. (Aux 102 I/O Module option).Each event function can be programmed (using InPower service tool or access to the Setup menu), as follows: 1. Change display name using up to 32 characters 2. Select active low or high input.
2629AUX 102 DIGITAL INPUT 10 — DiagnosticThe nature of the Aux I/O Module event is an optional customer selection. (Aux 102 I/O Module option).See code 2628
2631AUX 102 DIGITAL INPUT 11 — DiagnosticThe nature of the Aux I/O Module event is an optional customer selection. (Aux 102 I/O Module option).See code 2628
2632AUX 102 DIGITAL INPUT 12 — DiagnosticThe nature of the Aux I/O Module event is an optional customer selection. (Aux 102 I/O Module option).See code 2628
2676ALTERNATOR FREQUENCY CONFLICT — ShutdownThe measured alternator line frequency and measured alternator excitation frequency do not agree.
2677FAIL TO STOP — ShutdownThe generator set continues to run after receiving a stop command from the controller.
2678CHARGER FAILURE — WarningThe battery charging alternator has not reached an acceptable voltage range within the selected time period (default is 120 seconds). This warning is also displayed if your alternator is a type that does not support the control's charging alternator logic functionality.If this occurs, this warning can be disabled if the Charging Alt. Enable setting is set to "No".
2693SPEED BIAS OOR — WarningThe speed bias circuit output is out of range (OOR), high or low. (Aux 101 I/O Module option).
2694ALTERNATOR RTD OOR — WarningThe alternator RTD sensor is out of range (OOR), high or low. (Aux 101 I/O Module option).
2696ALTERNATOR RTD TEMP HIGH — ShutdownThe alternator temperature is above normal and has reached the shutdown trip point. (I/O Module option).
2729I/O MODULE LOST — WarningAn intermittent datalink between the I/O module and the control board. (Aux 101 I/O Module option).
2731I/O MODULE LOST — ShutdownThe datalink between the I/O module and the control board is lost. (Aux 101 I/O Module option).
2897FACTORY BLOCK CORRUPT — ShutdownA fatal software error occurred in the PowerCommand® 2.3 control.
2898PERIODIC/FAULT CORRUPT — WarningEither the periodic data file or the fault history file has been corrupted.Remove and re-apply power to the control to clear the fault. (Periodic and/or fault history data will be lost after re-setting the control).
2899USER BLOCK CORRUPT — ShutdownA fatal software error occurred in the PowerCommand® 2.3 control.
2911TRIM BLOCK CORRUPT — ShutdownA fatal software error occurred in the PowerCommand® 2.3 control.
2964INTAKE MANIFOLD TEMPERATURE HIGH — WarningThe engine has begun to overheat (intake manifold temperature has risen to an unacceptable level). Increase in load or higher ambient temperature may cause Intake Manifold Temp High (code 155) shutdown.If the engine can be stopped, allow the engine to cool down completely before proceeding with the following check: 1. Review the code 151 correction list for possible causes.
2972FIELD OVERLOAD — ShutdownThe Field Voltage has been above 70 V for eight seconds.

Symptoms & remedies

SymptomCauseRemedy
Battery completely dischargedPoor battery terminal connectionClean connections, replace and tighten.
Battery completely dischargedCharge alternator/alternator connection faultContact your nearest Cummins distributor.
Battery completely dischargedMains battery charger/charger connections fault/mains supply faultContact your nearest Cummins distributor.
Battery completely dischargedBlown fuseContact your nearest Cummins distributor.
Battery completely dischargedBattery faultContact your nearest Cummins distributor.
Battery completely dischargedNewly installed battery shipped dryFill with electrolyte and give commissioning charge.
Battery low chargePoor battery connectionClean connections, reconnect and tighten securely.
Battery low chargeCharge alternator/alternator connection faultContact your nearest Cummins distributor.
Battery low chargeMains battery charger/charger connections faultContact your nearest Cummins distributor.
Battery low chargeInequality in cell chargeContact your nearest Cummins distributor.
Battery low chargeBattery faultContact your nearest Cummins distributor.
Battery overchargedCharge alternator faultContact your nearest Cummins distributor.
Battery overchargedMains battery charge faultContact your nearest Cummins distributor.
Battery overchargedLow battery fluid levelCheck the charger; it may not be shutting off when the charge is complete.
Battery terminals getting hotPoor battery connectionClean connections, reconnect and tighten securely; Contact your nearest Cummins distributor.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Cross-brand guides for these symptoms

Common questions

Cummins/Onan DFEJ: Battery completely discharged — what causes it?

Documented causes: Poor battery terminal connection; Charge alternator/alternator connection fault; Mains battery charger/charger connections fault/mains supply fault; Blown fuse. See the table for the matching fixes.

Cummins/Onan DFEJ: Battery low charge — what causes it?

Documented causes: Poor battery connection; Charge alternator/alternator connection fault; Mains battery charger/charger connections fault; Inequality in cell charge. See the table for the matching fixes.

Cummins/Onan DFEJ: Battery overcharged — what causes it?

Documented causes: Charge alternator fault; Mains battery charge fault; Low battery fluid level. See the table for the matching fixes.