Home TroubleshootingCummins/Onan 6.0MDJE-53CR

Cummins/Onan 6.0MDJE-53CR Troubleshooting

Cummins/Onan 6.0MDJE-53CR troubleshooting: 13 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Cummins/Onan 6.0MDJE-53CR — full specs, parts & maintenance.

All Cummins/Onan fault codes →

Troubleshooting

13

Fault codes

CodeMeaning
e008No specific name provided for e008
10Overload

Symptoms & remedies

SymptomCauseRemedy
Incomplete circuit between exciter and slip rings.Slip ring brush shunt brokenCheck all slip ring brush shunts with an ohmmeter and replace broken brush shunts.
Slip ring brushes not contacting the slip rings.Replace slip ring brush spring which may have come off or broken; or replace brushes which may have become worn down to far to contact the slip rings.
Insulating film on slip rings.Clean slip rings with stone or fine sandpaper and blow out dust.
Short circuit in fieldDampness or deteriorated insulation.Bake if damp, repair or replace if insulation is deteriorated.
Open circuit in fieldRough usage or original short circuit which may have burned a coil or connection.Examine field connections and test with ohmmeter. If a coil is open, replace it.
No generator output or low output.Defective shunt field bridge rectifierCheck AC components as listed above and preceding page. Check bridge rectifier with an ohmmeter. Replace if necessary.
No battery charger output (1 amp normal).Diode CR2 bad.Open component in charging circuit. Check diode with an ohmmeter and replace if open or shorted.
AC stator winding shortedInsulation or coils broken.Rewind or replace stator winding.
AC stator winding openOriginal short circuit may have burned a coil or connection.Test with an ohmmeter and if open, rewind or replace with a new stator winding.
Faulty loadOpen circuit or short circuit on line.Check line and load and the load.
Ammeter indicating ‘O’Generator has not built up voltageCheck the automatic field flash circuit which receives power from the § terminal of the start solenoid. When the start solenoid is energized, power should be applied to the static exciter and revolving field for faster voltage build-up.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Cummins/Onan 6.0MDJE-53CR: Incomplete circuit between exciter and slip rings — what causes it?

Documented causes: Slip ring brush shunt broken. See the table for the matching fixes.

Cummins/Onan 6.0MDJE-53CR: Short circuit in field — what causes it?

Documented causes: Dampness or deteriorated insulation.. See the table for the matching fixes.

Cummins/Onan 6.0MDJE-53CR: Open circuit in field — what causes it?

Documented causes: Rough usage or original short circuit which may have burned a coil or connection.. See the table for the matching fixes.