| Symptom | Cause | Remedy |
|---|---|---|
| Fault lamp lights and engine stops cranking after approximately 75 seconds | See engine service manual for troubleshooting fuel system; After correcting fault, reset monitor by moving run-stop/reset-remote switch to reset position, then to either run or remote to restart engine | |
| Fault lamp lights immediately after engine starts | Overspeed condition as engine starts | Check for overspeed condition as engine starts |
| Fault lamp lights immediately after engine starts | High temperature condition | Check for high temperature condition |
| Fault lamp lights immediately after engine starts | Faulty high engine temperature sensor or overspeed switch | Check for faulty high engine temperature sensor or overspeed switch |
| Fault lamp lights immediately after engine starts | Faulty starter disconnect | Check for faulty starter disconnect |
| Fault lamp lights after engine is running | Oil level - engine will shut down after approximately 12-1/2 seconds if low oil pressure sensor does not open | Check oil level |
| Fault lamp lights after engine is running | Oil pressure sensor may be defective | Check oil pressure sensor |
| Fault lamp lights after engine is running | High engine temperature - caused by low coolant level, faulty thermostat, etc. | Check for high engine temperature |
| Fault lamp lights after engine is running | Faulty high engine temperature sensor | Check high engine temperature sensor |
| Fault lamp lights after engine is running | Faulty starter disconnect | Check starter disconnect |
| Fault lamp lights - no fault condition exists | Be certain that no fault condition exists; Disconnect lead 29, 30 and 31 from TB11 inside control box (refer to wiring diagram); If fault lamp still lights with leads disconnected, remove and replace engine monitor plug-in printed circuit board | |
| Overcrank fault lamp lights and engine stops cranking after approximately 75 seconds | See engine service manual for troubleshooting fuel system; After correcting fault, reset monitor by moving run-stop/reset-remote switch to reset position, then to either run or remote to restart engine | |
| Overcrank fault lamp lights after engine has run for approximately 75 seconds | Replace start-disconnect circuit board | |
| High engine temperature lamp lights as soon as engine starts | Defective sensor or actual high temperature condition | Check for defective sensor or actual high temperature condition |
| Low oil pressure lamp lights after engine is running | Oil level - engine will shut down after approximately 12-1/2 seconds if oil pressure is low | Check oil level |
| High engine temperature lamp lights after engine is running | Defective thermostat/thermostats | Check for defective thermostat/thermostats |
| High engine temperature lamp lights after engine is running | Low coolant level | Check for low coolant level |
| High engine temperature lamp lights after engine is running | Defective high engine temperature sensor | Check for defective high engine temperature sensor |
| Overspeed lamp lights - no fault condition exists | Replace overspeed circuit board | |
| Low oil pressure fault lamp lights - no fault condition exists | Be certain that no fault condition exists; Disconnect lead 30 from TB11 inside control box (refer to wiring diagram); If low oil pressure lamp still lights, remove and replace engine monitor plug-in printed circuit board | |
| High engine temperature fault lamp lights - no fault condition exists | Be certain that no fault condition exists; Remove lead 31 from TB11 inside control box (refer to wiring diagram); If high engine temperature lamp still lights, remove and replace engine monitor plug-in printed circuit board | |
| When pressing test lamp button - one or more fault lamps do not light | Fault lamp/lamps burned out | Replace |
| Non-Start: engine fails to start after a few seconds of cranking, or starts and runs then stops and fault lamp lights | Refer to appropriate troubleshooting chart, Table 3 or Table 4 |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Documented causes: Oil level - engine will shut down after approximately 12-1/2 seconds if low oil pressure sensor does not open; Oil pressure sensor may be defective; High engine temperature - caused by low coolant level, faulty thermostat, etc.; Faulty high engine temperature sensor. See the table for the matching fixes.
Documented causes: Overspeed condition as engine starts; High temperature condition; Faulty high engine temperature sensor or overspeed switch; Faulty starter disconnect. See the table for the matching fixes.
Documented causes: Defective thermostat/thermostats; Low coolant level; Defective high engine temperature sensor. See the table for the matching fixes.