Home› Troubleshooting›Clarke RC60D

Clarke RC60D Troubleshooting

Clarke RC60D troubleshooting: 48 symptom-cause-remedy entries from the manufacturer's own service documentation.

Clarke RC60D — full specs, parts & maintenance.

Troubleshooting

48

Symptoms & remedies

SymptomCauseRemedy
Alternator does not work normally when first commissionedProtective devices not fitted correctly; connections do not comply with the diagrams in the manuals supplied with the machine; speed of the unit is incorrectCheck that the protective devices are fitted correctly; check that all connections comply with the diagrams in the manuals supplied with the machine; check that the speed of the unit is correct and repeat the operations instructions
Excessive overheating of one or both bearings (temp of bearings over 80°C) (With or without abnormal bearing noise)Bearing has turned blue or the grease has turned black; bearing race badly locked (moving in its housing)Change the bearing
Excessive overheating of alternator frame (temperature rise of more than 40°C above ambient)Air flow (inlet-outlet) partially clogged or hot air is being recycled either from alternator or prime mover; alternator is functioning at too high a voltage (over 105% of rated voltage on load); alternator overloaded
Too much vibrationMisalignment (coupling); defective mounting or play in coupling; incorrect balancing of shaft (Engine-Alternator)
Excessive vibration and humming noise coming from the alternatorThree phase alternator is single phase loaded in excess of acceptable level; short circuit in the alternator stator
Alternator damaged by a significant impact which is followed by humming and vibrationSystem short circuit; MIS parallelingPossible consequences (according to the seriousness of the above faults): broken or damaged coupling; broken or bent shaft end; shifting and short circuit of main field rotor; fractured fan or coming loose on shaft; blown rotating diodes, or and AVR
No voltage at no load or startupLack of residual magnetism in alternatorConnect a battery of 4 to 12 volts to terminals E+(F+) or E- (F-) respecting the polarity on the A.V.R for 2 to 3 seconds
No voltage at no load or startup — The alternator builds up but voltage does not reach nominal value when the battery is removedFaulty rotating diode; short-circuit on rotor windingsCheck the connections of the sensing leads to the A.V.R.
No voltage at no load or startup — The alternator builds up but voltage collapses when the battery is removedFaulty A.V.R.; exciter field short-circuited or open circuit (check windings); main field winding open circuit (check resistance)
Voltage too lowIncorrect speedCheck the prime mover speed
Voltage too lowPossible AVR failure; exciter field short-circuited; rotating diode(s) burnt out; main field rotor short-circuitedCheck A.V.R. connections; check the resistance
Voltage too highNo adjustment of voltage, measure voltage F+/F- on AVR; voltage between F+ and F- > 12V or AVR faulty; one faulty diodeAdjust potentiometer voltage
Voltage oscillationsLoose connections; faulty A.V.R; speed below nominal when on load (or LAM set too high)Adjust the stability potentiometer on A.V.R; if no effect: change recovery mode normal/rapid; check speed for possible cyclic irregularity
Voltage correct on no load too low on load (*) — Voltage between F+ and F- <10V (DC)Check speed (or U/F knee point set too high)Run on no-load and check voltage between F+ and F- on the AVR
Voltage correct on no load too low on load (*) — Voltage between F+ and F- >15V (DC)Faulty rotating diodes; short circuit in the main field; faulty exciter armature; bad IEX setting (See LED status)Check resistance; check resistance; check LED status
Voltage collapses during normal operation (**) — The output voltage does not return the rated valueExciter winding open circuit; faulty exciter armature; faulty AVR; main field rotor winding open circuit or short circuit overload (See LED status)Check the AVR, the surge suppressor, the rotating diodes and replace any defective part
Circuit Breaker Tripped — Heat, smoke, burn or smell from loadFaulty load device; overcurrentCheck for short circuit in load
Circuit Breaker Tripped — Repeated tripsOvercurrent relay (OCR activated); defective circuit breaker or incorrect settingsConfirm load requirements and reduce; confirm correct setting of the overcurrent relay dial
Circuit Breaker Tripped — Repeated tripsIncorrect settingsMake correct setting on OCR; replace OCR
Circuit Breaker Tripped — Repeated tripsFaulty trip coilMake correct settings
Circuit Breaker Tripped — Repeated tripsFaulty breakerMake correct settings
Any Red Diagnostic message is on the control panelRefer to Manual sections on Engine Operating, Panel Operation & Engine Status/Warning Lamps, and also Engine Diagnostic Trouble Code Display Operation; correct condition, sensor as appropriate
Low Oil Pressure DisplayLow oil levelFill if low
High Coolant Temperature DisplayDoors are openClose doors
High Coolant Temperature DisplayLow airflow circulating through radiatorClean radiator, grill
High Coolant Temperature DisplayFan slippageCheck fan drive and speed
High Coolant Temperature DisplayLeaking exhaustReplace/repair gaskets or faulty parts
High Coolant Temperature DisplayGenerator being overloadedCheck/reduce load
High Coolant Temperature DisplayThermostat failureReplace thermostat
High Coolant Temperature DisplayAir intake blockedClean all air intakes
High Coolant Temperature DisplayTemperature switch failureReplace temperature switch
Overspeed DisplayEngine controller needs recalibrationRefer to dealer
Low Fuel DisplayLow fuel levelAdd fuel
Low Fuel DisplayUnit is excessively out of levelLevel unit
No reaction from control panel when OFF button is pressedEmergency stop actuatedReset emergency stop button
No reaction from control panel when OFF button is pressedBatteries not connectedConnect batteries
No reaction from control panel when OFF button is pressedControl Panel circuit breaker trippedReset breaker
No reaction from control panel when OFF button is pressedController fuse in control box blownReplace fuse
Engine fails to crank or startLow battery chargeCheck the battery alternator belt tension, battery and cable connections
Engine fails to crank or startBad frame ground connectionsCheck the ground cables, clean and tighten connections as needed
Engine fails to crank or startFuel starvationCheck the fuel system components. Replace the fuel filter if necessary
Engine fails to crank or startFaulty starter relayReplace relay
Engine fails to crank or startNo crank signal from generator controllerVerify correct controller programming or replace controller
Engine speed too lowUnit set in IDLE modeSet to RUN mode
Engine speed too lowGenerator is overloadedCheck load and reduce
Engine speed too lowLAM is improperly set to enable step loading or motor startingCheck LAM setting and correct
Engine speed too lowBlocked fuel filterCheck and replace
Engine speed too lowBlocked air filterCheck and replace

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Clarke RC60D: High Coolant Temperature Display — what causes it?

Documented causes: Doors are open; Low airflow circulating through radiator; Fan slippage; Leaking exhaust. See the table for the matching fixes.

Clarke RC60D: Engine fails to crank or start — what causes it?

Documented causes: Low battery charge; Bad frame ground connections; Fuel starvation; Faulty starter relay. See the table for the matching fixes.

Clarke RC60D: Engine speed too low — what causes it?

Documented causes: Unit set in IDLE mode; Generator is overloaded; LAM is improperly set to enable step loading or motor starting; Blocked fuel filter. See the table for the matching fixes.