Atlas Copco QAS246 Gd USA Troubleshooting

Atlas Copco QAS246 Gd USA troubleshooting: 31 fault codes and 25 symptom-cause-remedy entries from the manufacturer's own service documentation.

Atlas Copco QAS246 Gd USA — full specs, parts & maintenance.

All Atlas Copco fault codes →

Troubleshooting

56

Fault codes

CodeMeaningCauseRemedy
11VSG input low
12VSG input high
13Coolant level circuit low
14Intercooler, coolant or oil temperature circuit high
15Intercooler, coolant or oil temperature circuit low
16Coolant level circuit high
17Bypass position circuit high
18Bypass position circuit low
21TPS circuit high
22TPS circuit low
23Fuel temperature circuit high
24Fuel temperature circuit low
46Battery voltage low
47Fuel pressure high
48Fuel pressure low
52A/D conversion fail
53EEPROM write or nonvolatile checksum fail
54Vehicle speed sensor fault
55J1939 data link fault
56J1587 data link fault
57J1922 data link fault
58Torque overload
61Injector response time long
62Auxiliary output open or short to
Blown fuseAlternator does not excite.Replace fuse.
Increase the speed by 15 %Insufficient residual voltage.
Reset voltageLow voltage at no load.Voltage potentiometer out of setting.
Check rpmIntervention of protection.Winding failure.Check windings.
Substitute regulator.High voltage at no load.Voltage potentiometer out of setting.
Reset voltage potentiometer.Lower than rated voltage at load.
Substitute regulator.Current too high, power factor lower than 0.8; speed lower than 10 % of rated speed.

Symptoms & remedies

SymptomCauseRemedy
Alternator does not exciteBlown fuseReplace fuse
Alternator does not exciteInsufficient residual voltageIncrease the speed by 15 %
Alternator does not exciteNo residual voltageFor an instant apply on the + and – terminals of the electronic regulator a 12 V battery voltage with a 30 Ω resistor in series respecting the polarities
After being excited alternator does not exciteConnections are interruptedCheck connection cables as per attached drawings
Low voltage at no loadVoltage potentiometer out of settingReset voltage
Low voltage at no loadIntervention of protectionCheck rpm
Low voltage at no loadWinding failureCheck windings
High voltage at no loadVoltage potentiometer out of settingReset voltage
High voltage at no loadFailed regulatorSubstitute regulator
Lower than rated voltage at loadVoltage potentiometer out of settingReset voltage potentiometer
Lower than rated voltage at loadIntervention by protectionCurrent too high, power factor lower than 0.8; speed lower than 10 % of rated speed
Lower than rated voltage at loadFailed regulatorSubstitute regulator
Lower than rated voltage at loadRotating bridge failureCheck diodes, disconnect cables
Higher than rated voltage at loadVoltage potentiometer out of settingReset voltage potentiometer
Higher than rated voltage at loadLoose sensing wires on AVRCheck sensing wires on AVR
Higher than rated voltage at loadFailed regulatorSubstitute regulator
Unstable voltageSpeed variation in engineCheck regularity of rotation
Unstable voltageRegulator out of settingRegulate stability of regulator by acting on “STABILITY” potentiometer
Engine runs in idle speedNo SAPE connectedPut single/parallel switch in single position
No residual voltage.
After being excited alternator does not excite.Connections are interrupted.
Failed regulator.Rotating bridge failure.
Higher than rated voltage at load.
Unstable voltage.Speed variation in engine.
Engine runs in idle speed.No SAPE connected.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Atlas Copco QAS246 Gd USA: Low voltage at no load — what causes it?

Documented causes: Voltage potentiometer out of setting; Intervention of protection; Winding failure; Voltage potentiometer out of setting.. See the table for the matching fixes.

Atlas Copco QAS246 Gd USA: Lower than rated voltage at load — what causes it?

Documented causes: Voltage potentiometer out of setting; Intervention by protection; Failed regulator; Rotating bridge failure. See the table for the matching fixes.

Atlas Copco QAS246 Gd USA: Alternator does not excite — what causes it?

Documented causes: Blown fuse; Insufficient residual voltage; No residual voltage. See the table for the matching fixes.