Atlas Copco QAS246 Gd USA Troubleshooting

Atlas Copco QAS246 Gd USA troubleshooting: 13 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Atlas Copco QAS246 Gd USA — full specs, parts & maintenance.

All Atlas Copco fault codes →

Troubleshooting

13

Fault codes

CodeMeaningCauseRemedy
Blown fuseAlternator does not excite.Replace fuse.
Increase the speed by 15 %Insufficient residual voltage.
Reset voltageLow voltage at no load.Voltage potentiometer out of setting.
Check rpmIntervention of protection.Winding failure.Check windings.
Substitute regulator.High voltage at no load.Voltage potentiometer out of setting.
Reset voltage potentiometer.Lower than rated voltage at load.
Substitute regulator.Current too high, power factor lower than 0.8; speed lower than 10 % of rated speed.

Symptoms & remedies

SymptomCause
No residual voltage.
After being excited alternator does not excite.Connections are interrupted.
Failed regulator.Rotating bridge failure.
Higher than rated voltage at load.
Unstable voltage.Speed variation in engine.
Engine runs in idle speed.No SAPE connected.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Atlas Copco QAS246 Gd USA: After being excited alternator does not excite — what causes it?

Documented causes: Connections are interrupted.. See the table for the matching fixes.

Atlas Copco QAS246 Gd USA: Low voltage at no load — what causes it?

Documented causes: Voltage potentiometer out of setting.. See the table for the matching fixes.

Atlas Copco QAS246 Gd USA: Intervention of protection — what causes it?

Documented causes: Winding failure.. See the table for the matching fixes.