Home›Repair guides›Yanmar›Vibration Isolating Installation - Flexible Pipe Installation

Yanmar — Vibration Isolating Installation - Flexible Pipe Installation

Installation · External piping flexible joints

From a Yanmar manual — check it applies to your exact model before use.

Browse Yanmar generators & specs →

Before you start

  • Avoid excessive contraction, elongation, offset, bending or twisting.

Procedure

  1. Fit the pipes naturally to avoid initial stress such as elongation, offset or twisting.
  2. Do not contract the pipe for installation; cut surplus length if too long.
  3. Do not elongate the pipe forcibly; cut opponent piping to accurate length.
  4. Do not offset or bend the pipe.
  5. Do not twist the pipe.
  6. Install the pipe at a right angle to the direction of vibration.
  7. Install the pipe at a place with small pressure changes.
  8. Install the anchor as near as possible to the vibrating body.
  9. Do not use the pipe to support heavy things; install a hanger to support external forces.
  10. Cover flexible tubes for oil and flammable liquid with lagging material.

Specs & values

  • Exhaust flexible tube: within 0 mm - +4.0 mm of axis length, less than 1.0 mm offset
  • Lub. oil/cooling water/fuel oil/mist flexible tube: within -2.0 mm - +3.0 mm of axis length, less than 2.0 mm offset

Source: Yanmar manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.