Yanmar — Long Storage Maintenance (approx. 6 months - 1 year)

Maintenance · Engine

From a Yanmar manual — check it applies to your exact model before use.

Browse Yanmar generators & specs →

Before you start

  • Do not expose the equipment to rainwater or briny air.

Procedure

  1. Provide sufficient ventilation and humidity prevention; keep indoor temperature at 40°C or below and humidity 75% or below.
  2. Store indoors; place equipment 300-500 mm above the floor and cover with a dust-proof sheet.
  3. Once every month, check the exterior and spray or brush anti-rust oil.
  4. Fill the common bed system oil and conduct turning once a month while priming the lubricating oil.
  5. Once every three months, open the crank case side cover, turn the crankshaft and spray anti-rust oil.
  6. If a turbocharger is installed, every 3 months spray anti-rust oil to the turbine wheel and inlet inducer.

Specs & values

  • Indoor temperature 40°C or below
  • Humidity 75% or below
  • Place equipment 300-500 Amazon eBay mm above floor

Source: Yanmar manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.