Westerbeke — Checking Main Rotor Windings for Short (Housing Removed)
Testing & diagnosis
From a Westerbeke service manual covering: WTA 15, WTA 20, WTA 25, WTA12KW, WTA15KW, WTA16KW, WTAl5KW. Check it applies to your exact model before use.
Before you start
- Possibility of thermal damage from the 24 volt DC battery exists if not monitored and controlled during the test.
Procedure
- Disconnect the two main rotor winding leads and the ground lead from the rotor shaft.
- Attach a 24 VDC source across these leads (plus to DC lead, minus to ground lead).
- Pass a long metal scale or hacksaw blade around the armature outer surface.
- Observe for obvious difference in magnetic strength indicating a shorted area.
- Allow windings to heat until uncomfortable to touch, then remove DC source.
- Measure resistance again; if hot resistance much lower than cold, rotor likely has shorted windings.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 24 VDC source
Source: Westerbeke service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.