HDT — Refer to MP-6345, Operation/Installation, for more
For the HDT.
Procedure
- 2.2
- Controls
- The controller’s user interface panel is accessible
- through an opening in the transfer switch cover (the
- inner panel on NEMA type 3R enclosures). Figure 2-1
- explains the operation of the controller pushbuttons and
- LED indicators.
- The LEDs light steadily or flash to indicate different ATS
- conditions as shown in Figure 4-7. See Section 4.3 for
- more information on fault conditions.
- Press and hold 3 seconds to set the exerciser to run the
- generator set. Generator source LED flashes.
- Press and hold for 6 seconds to set the exerciser to
- start the generator set and transfer the load. Generator
- source and position LEDs flash.
- The exerciser will run at the same day and time each
- week.
- Press again and hold for 2 seconds to end the exercise.
- tp6345
- Exercise Button
- Press and hold for 3 seconds to start the generator set.
- Generator source LED flashes.
- Press and hold for 6 seconds to start the generator set
- and transfer the load. Generator source and position
- LEDs flash.
- Press again and hold for 2 seconds to end the test.
- Test Button
- Utility Source Position LED
- Green LED lights when the
- electrical load is connected to the
- Normal source (typically utility
- power). Flashes to indicate faults;
- see Figure 4-7.
- Utility Source Available LED
- Green LED lights when the the ATS
Source: manual:MP6346.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.