HomeRepair guidesThe disassembly procedure of the mechanism is the reverse of the above. However, it is recom-

Transfer Switches - LakeShore — The disassembly procedure of the mechanism is the reverse of the above. However, it is recom-

A Transfer Switches - LakeShore service procedure — check it applies to your exact model before use.

Browse Transfer Switches - LakeShore generators & specs →

Procedure

  1. 5. MOLDED CASE SWITCHES
  2. 6. TIMING RELAYS to
  3. 7. VOLTAGE RELAYS
  4. 1. Select proper voltage range.
  5. 2. Set pickup potentiometer full clockwise.
  6. 3. Set dropout potentiometer full counter-clockwise
  7. 4. Using a small screwdriver, turn the calibrate potentiometer fully clockwise.
  8. 5. Apply nominal input voltage to unit.
  9. 6. Slowly turn the calibration potentiometer counter-clockwise until the units
  10. 7. Set pickup and dropout potentiometers to desired settings.
  11. 8. Unit is ready for operation.
  12. 1. Remove protective black plugs.
  13. 2. Using a small slotted screwdriver, turn the dropout potentiometer fully
  14. 3. Using a small slotted screwdriver, turn the pickup potentiometer fully clock-
  15. 4. Apply required level of pickup voltage to the unit.
  16. 5. Turn the pickup potentiometer slowly counter-clockwise until the meter
  17. 6. Reduce the voltage to the required voltage dropout level.
  18. 7. Turn the dropout potentiometer slowly clockwise until the meter shows no
  19. 8. PROGRAM TIME CLOCK
  20. 1. To remove unit from enclosure: Push tab on right to swing unit to the left and remove.

Source: manual:Styles 2, 3 and T-200 New Manual.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.