Transfer Switches - LakeShore — The auxiliary microswitches are mounted internally to the molded case switch. Internal mounting
A Transfer Switches - LakeShore service procedure — check it applies to your exact model before use.
Browse Transfer Switches - LakeShore generators & specs →
Procedure
- 6. TIMING RELAYS to
- 7. VOLTAGE RELAYS
- 1. Select proper voltage range.
- 2. Set pickup potentiometer full clockwise.
- 3. Set dropout potentiometer full counter-clockwise
- 4. Using a small screwdriver, turn the calibrate potentiometer fully clockwise.
- 5. Apply nominal input voltage to unit.
- 6. Slowly turn the calibration potentiometer counter-clockwise until the units
- 7. Set pickup and dropout potentiometers to desired settings.
- 8. Unit is ready for operation.
- 1. Remove protective black plugs.
- 2. Using a small slotted screwdriver, turn the dropout potentiometer fully
- 3. Using a small slotted screwdriver, turn the pickup potentiometer fully clock-
- 4. Apply required level of pickup voltage to the unit.
- 5. Turn the pickup potentiometer slowly counter-clockwise until the meter
- 6. Reduce the voltage to the required voltage dropout level.
- 7. Turn the dropout potentiometer slowly clockwise until the meter shows no
- 8. PROGRAM TIME CLOCK
- 1. To remove unit from enclosure: Push tab on right to swing unit to the left and remove.
- 2. Mount the enclosure at eye level using screws or other suitable fastening device. Bring
Source: manual:Styles 2, 3 and T-200 New Manual.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.