Procedure
- 2. Open both switching devices Manual Operation Instructions
- 4. Verify source availability
- 5. Close switching device on available source
- 1. Disconnect Logic Connectors
- 3. Verify "OPEN" flags 7805C60H05 MANUAL CLOSE BUTTON Operating Instructions Do Not Use Without Reading Manual OVERLAPPING CONTACTS must be Synchronized SOURCE 1 AND SOURCE 2 WARNING 7805C60H04 THIS PRODUCT CONTAINS A SPECIAL CON- TACT ARRANGEMENT (OVERLAPPING CON- TACTS). MISUSE CAN RESULT IN DEATH SEVERE PERSONAL INJURY OR PROPERTY DAMAGE. (THIS LABEL IS APPLIED TO THE DOOR ) FOLLOW THE INSTRUCTIONS OUTLINED IN THE NEXT WARNING LABEL. (THIS LABEL IS APPLIED TO THE COVER OF THE MANUAL CLOSE BUTTON ON EACH THESE INSTRUCTIONS ONLY PERTAIN TO MANUALLY CLOSING A SINGLE SWITCHING DEVICE. ATTEMPTING TO CLOSE BOTH SWITCHING DEVICES CAN CAUSE SEVERE INJURY OR DEATH. THIS LABEL IS APPLIED TO THE DOOR. For more information visit: www.Eaton.com IB01602011E Instructional Booklet Page 22 Effective: March 2007 Fixed and Drawout Magnum Transfer Switches Section 6: Drawout and Fixed Switching Devices
- 6.1 Installing a Drawout Switching Device In transfer switches equipped with drawout switching devices, bolted-in carriages with extendable rails support the switching devices.