From a Perkins owner's manual covering: 4000 Series, 4006-23 TAG1A, 4006-23 TAG2A, 4006-23 TAG3A. Check it applies to your exact model before use.
Applies to: Perkins 4006-23 TAG1A, Perkins 4006-23 TAG2A, Perkins 4006-23 TAG3A
Before you start
- Disconnect the batteries and any other power that can start the engine.
Procedure
- Remove the three bolts (A5) from the plate (A6) and remove the plate.
- Remove the bolt (A3).
- Remove the top bolt (A1) and the bottom bolt (A4) and remove the two parts of the guard (A2).
- Apply 15,6 N (3.5 lbf) 1,5 kgf of pressure midway between the two pulleys (B2); correct deflection is 1,5 mm (0.0625 in).
- Adjust the belt if necessary.
- Fit the guard assembly and tighten all the bolts securely.
- Connect the power supply to the starter motor.
Specs & values
- Deflection 1,5 mm (0.0625 in) at 15,6 N (3.5 lbf) 1,5 kgf