Perkins — How to adjust the fan belts
Adjustments
From a Perkins owner's manual covering: 4000 Series, 4006-23 TAG1A, 4006-23 TAG2A, 4006-23 TAG3A. Check it applies to your exact model before use.
Applies to: Perkins 4006-23 TAG1A, Perkins 4006-23 TAG2A, Perkins 4006-23 TAG3A
Procedure
- Remove the fan guards.
- Loosen the 6 nuts (B3) and loosen the lock nut (B2).
- Rotate the adjusting screw (B1) clockwise to increase tension, anti-clockwise to loosen tension.
- When all belts are at the correct tension, tighten the 6 nuts (B3) to 85 Nm (62.7 lbf ft) 8,6 kgf m and tighten the locking nut (B2).
- Check that the fan belt tension is correct on each belt.
- Fit the fan guards.
- Connect the power supply to the starter motor.
Specs & values
- Nut torque 85 Nm (62.7 lbf ft) 8,6 kgf m
Source: Perkins owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.