Perkins — Fuel Transfer Pump - Install
Repair & overhaul
From a Perkins service manual — check it applies to your exact model before use.
Browse Perkins generators & specs →
Procedure
- Ensure the fuel transfer pump is clean and free from damage.
- Lubricate a new O-ring seal with clean engine oil and install to fuel transfer pump (4).
- Position fuel transfer pump (4) on pump drive (5). Ensure splines on pump shaft engage correctly in pump drive.
- Install bolts (3). Tighten to 55 N·m (41 lb ft).
- Remove caps from hose assemblies and connect hose assemblies (1) and (2) to fuel transfer pump (4).
- Turn the fuel supply to the "ON" position.
- Remove the air from the fuel system.
Specs & values
- 55 N·m (41 lb ft) bolts (3)
Source: Perkins service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.