Home›Repair guides›Perkins›Removal from Storage

Perkins 1506 — Removal from Storage

Maintenance · Engine

For the Perkins 1506, from the Perkins owner's manual.

Applies to: Perkins 1506A engine, Perkins 1506C engine, Perkins 1506D engine

Procedure

  1. Remove all covers from engine and air cleaner; check the condition of the air filter element.
  2. Check the coolant pump belt and fan drive belts, then tension both belts.
  3. Check the coolant level.
  4. Remove valve cover, lubricate the valve train, install valve cover.
  5. Replace the fuel filters and prime the fuel system.
  6. Use a bar or turning tool to turn the engine in the normal direction of rotation.
  7. If stored more than 1 year, pre-lubricate with engine oil at minimum 0.25 bar (3.6 psi) for 15 seconds.
  8. Check engine oil level and visually inspect all hoses and connections before starting the engine.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Prelube pressure 0.25 bar (3.6 psi) for 15 seconds
  • Prelube connection 9/16" x 18 tpi
  • Plug torque 30 N·m (265 lb in)
  • Minimum ambient temperature 10 °C (50 °F)

Source: Perkins owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.