Perkins 1106 — Speed Demand Input Setup

Adjustments · ECM / Speed Demand Input

For the Perkins 1106, from the Perkins service manual.

Applies to: Perkins 1106, Perkins 1106D engine

Procedure

  1. From the menu select Services.
  2. On the Services screen select Throttle Configuration.
  3. Select the type of input: Analog throttle, PWM throttle, or Communications port throttle (J1939 TSC1).
  4. If analog input is selected, program the analog parameters into the ECM.

Tools required

  • Electronic Service Tool Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Lower Diagnostic Limit default 5
  • Lower Position Limit default 10
  • Initial Lower Position default 20
  • Lower Dead Zone % default 5
  • Upper Dead Zone % default 5
  • Initial Upper Position default 70
  • Upper Position Limit default 85
  • Upper Diagnostic Limit default 90

Full service-parts list: Perkins 1106 →, Perkins 1106D engine →

Source: Perkins service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.